any reason you must have fittings or filters between the 

pump and tank and they cause switch chatter you should 

move the pressure switch to the tank cross tee. Go To 

“Install HydroPro Water Systems Tank” to Complete 

Shallow Well Installation.

DEEP WELL TWIN PIPE

 – start here

Twin Pipe Suction Piping

A twin pipe jet assembly is used in wells 4" and larger. 

Our 4" jet assemblies require a minimum 1¼" suction and 

1" drive water pipe; 5" jets require a minimum 1½" suc-

tion and 1¼" drive water pipe. Use of smaller piping will 

reduce performance in gpm and pressure. Offsets over 

50' require larger pipes to reduce friction loss and  

to obtain published performance.

Install Twin Pipe Jet Assembly

Check to make sure the nozzle is installed in 

the jet assembly. Install the venturi tube in line 

with the nozzle. On 4" jets attach the 1¼" suc-

tion and 1" pressure pipe to the jet assembly 

female threads. On 5" jets the pipes should be 

1½" and 1¼". Install a foot valve on the male 

thread bottom port on the jet assembly or on the end of 

a 34' tail pipe. The tail pipe prevents over pumping a low 

yield well so the pump will not break  

suction. See Tail Pipe in Technical Section.

Lower the jet assembly into the well. It should be set at 

least 5' below the static water level. Keep the jet a few 

feet off the well bottom to lessen the possibility of suck-

ing debris into the jet. The connections at the well head 

can be either a pitless adapter or a well seal. Priming will 

be easier if you fill the pipes with water before attaching 

the pump.

Connect the suction and pressure pipes to the threaded 

connections on the face of the pump. This can be done 

using unions and threaded pipe nipples, or barbed con-

nectors with poly pipe. Always double clamp barbed 

connectors. Make sure that the piping slopes upward to 

the pump and that no point is above the pump suction. 

On long offsets it is easier to prime the system if you fill 

the pipes with water before connecting the pipes to the 

pump. Go to Deep Well Discharge Piping.

DEEP WELL PACKER SYSTEM

 – start here

Packer Suction Piping

Packers use the area between the well casing 

and the suction pipe as the drive water (pres-

sure) pipe. The 2" or 3" well casing must be 

smooth and clean to insure a good seal with 

the packer leathers or the system will leak and 

not hold prime. The 2" packer requires 1¼" 

threaded suction pipe and the 3" requires 1½". On 2" 

packers only: Use the Goulds Water Technology turned 

couplings part #64655 to connect the sections of 1¼" 

threaded pipe. This special diameter turned coupling 

increases the clearance between the 2" well I.D. and the 

O.D. of the coupling to allow the drive (pressure) water 

to easily pass the couplings. Failure to use them will have 

a negative impact on pump performance, both pressure 

and gpm will decrease. The pump may easily lose prime 

while pumping due to the restriction!

Using smaller than recommended pipe may reduce gpm 

output. The longer the pipe the worse the affect.

Install Packer Assembly

To ease installation soak the 2" or 3" packer assembly in 

warm water to make the leathers soft and pliable. DO 

NOT lubricate them with grease, oil, or petroleum jelly! 

The leathers must absorb water to seal the packer assem-

bly against the well casing. 

Check to make sure the nozzle is installed in the jet 

assembly. Install the venturi tube in line with the nozzle. 

Install a strainer (not supplied with packer assembly) on 

the bottom port of the packer assembly or on the end of 

a 34' tail pipe. The tail pipe prevents over pumping a low 

yield well so the pump will not break suction. Attach the 

packer assembly to the suction pipes using the Goulds 

Water Technology’ turned couplings to connect the 

sections. Insert the packer assembly into the well casing 

and push it down.  Attach the other pipe sections as 
you lower the jet into the well.

 

See Tail Pipe in Technical 

Section.  

Attach Suction Pipe To Packer Adapter

Packer systems always require a Packer Adapter at the 

well head. The adapter makes the transition from vertical 

to horizontal for horizontal pumps, and it connects verti-

cal pump casings to the well casing and suction pipe. See 

the list of Packer Adapters/Pump Models to see which 
one your pump system requires. See Chart 1 for a list of 
Packer Adapters/Pump Models
.

After the jet assembly is inserted into the well, attach 

the Packer Adapter to the top of the suction pipe. Screw 

the top section of 1¼" male threaded suction pipe or a 

threaded adapter into the 1¼" NPT female threaded hole 

in the 2" packer adapter or a 1½" suction pipe into the 3" 

packer adapter. 

Make sure that the O.D. of the well casing is free of dirt 

and burrs. With the gland bolts loosened the tapered seal 

ring on the packer adapter should slide over the well 

casing. After insuring that it is in place tighten the two 

gland nuts to compress the seal ring and seal it to the 

well casing O.D. 

Install the pump by attaching it to the Packer Adapter 

using the bolts and gaskets provided. Vertical models use 
studs and nuts for ease of assembly.

DEEP WELL DISCHARGE PIPING

All deep well jet pumps require back pressu-

re to operate the jet assembly. To insure we 

have the required back pressure or drive water 

pressure we must use a pressure control valve 

or some type of flow restrictor in the discharge 

line. The valve must be located between the 

pump and the first discharge port. It is best to locate it as 

close to the pump as possible. Failure to install and adjust 

a pressure control valve will result in loss of prime during 

peak usage such as filling a washing machine, bathtub or 

using outside hose bibs.

All ½

 

hp pumps can use a simple gas cock or full port ball 

valve, such as our AV15. 

DEEP WELL DISCHARGE PIPING

DEEP WELL TWIN PIPE

DEEP WELL PACKER SYSTEM

Hazardous pressure can
cause personal injury or
property damage.

WARNING

Hazardous pressure can
cause personal injury or
property damage.

WARNING

Hazardous pressure can
cause personal injury or
property damage.

WARNING

Содержание HSJ07

Страница 1: ...Jet Pumps INSTALLATION OPERATION AND TROUBLESHOOTING MANUAL INSTRUCTION MANUAL IM102R07 ...

Страница 2: ...alling or servicing any electri cal equipment Many pumps are equipped with auto matic thermal overload protection which may allow an overheated pump to restart unexpectedly Never over pressurize the tank piping or system to a pressure higher than the tank s maximum pressure rating This will damage the tank voids the warranty and may create a serious hazard Protect tanks from excessive moisture and...

Страница 3: ...re are two types of deep well jet assemblies twin pipe and packer systems Deep well pumps come in both vertical and horizontal designs and in single and multi stage models See Typical Installation Drawing Fig 2 and 3 Consult with your Professional Dealer or Distributor to select the best pump system for your application Liquid temperature must not exceed 140 F 60 C Protect unit from freezing SHALL...

Страница 4: ...o prevent over pumping a low yield well you can throttle a jet pump using a ball valve in the suction line You should install a compound pressure vacuum gauge between the well and the valve Do not throttle to more than 22 Hg 25 lift In areas where freezing occurs make the transition from vertical to horizontal below the frost line using a pitless adapter consult with your plumbing supplier for pit...

Страница 5: ...ommended pipe may reduce gpm output The longer the pipe the worse the affect Install Packer Assembly To ease installation soak the 2 or 3 packer assembly in warm water to make the leathers soft and pliable DO NOT lubricate them with grease oil or petroleum jelly The leathers must absorb water to seal the packer assem bly against the well casing Check to make sure the nozzle is installed in the jet...

Страница 6: ...ol AVC to replenish air lost through absorption The AVC re quires connection to a vacuum port on the pump The suction side of the AVC must have a minimum 3 vacuum for 15 seconds when the pump starts Follow the instruc tions provided with the air volume control Priming a Shallow Well System Priming means filling the pump and suction pipe with water Most shallow well jet pumps handle air well and wi...

Страница 7: ...ly Black and neutral N usually white 115 volt wires to on the switch The same goes for a 230 volt hook up either wire can go on either Line terminal Re install the switch cover NOTE Motor voltage is NOT changed in the pressure switch See Fig 7 in Technical Data Check to insure that the motor is wired to match the incoming voltage All motors have a sticker near the pressure switch that identifies t...

Страница 8: ...3 53 3 27 30 70 AWCJ3 AV22 and JDW FT5 48 4 40 70 110 FP3 54 3 30 70 110 FT4 44 4 31 30 60 FP2 48 2 35 30 60 AWJ2 FT4 43 4 33 60 80 FP2 43 2 36 60 100 AV22KIT J10 FT4 18 4 35 80 110 AV22 and JDW FT5 49 4 30 30 80 FP3 55 3 28 30 80 AWCJ3 FT5 11 4 32 80 120 FP3 14 3 32 80 120 FT5 12 4 35 30 70 FP3 16 3 34 30 60 J15 FT5 11 4 40 70 140 FP3 18 3 34 60 90 AWCJ3 AV22KIT FP3 21 3 34 90 150 AV22 and JDW FP...

Страница 9: ...ONTROLVALVE DEPTH JET WELL CONTROLVALVE DEPTH PACKER CONTROLVALVE ASSEMBLY DIAMETER SETTING PSI TO JET ASSEMBLY DIAMETER SETTING PSI TO JET ADAPTER see fig 4 FT3 09 3 30 30 50 FP2 13 2 30 30 50 FT4 13 4 30 30 50 AV15 JRD5 FT4 31 4 30 30 70 FP2 31 2 30 30 60 AWJ2 or FT4 08 4 30 60 90 FP2 08 2 30 60 80 AV22KIT FT5 14 4 30 70 90 FT4 14 4 27 30 60 FP2 40 2 30 30 60 FT4 34 4 29 60 90 FP2 47 2 32 60 90 ...

Страница 10: ...JB05 C48C04A06 115 230 1 1 6 12 6 6 3 990 25 15 SFJ05860 JRS7 JRD7 JB07 C48C05A06 115 230 1 1 5 14 8 7 4 1200 30 15 SFJ06860 JRS10 JRD10 JB10 C48C06A06 1 115 230 1 1 4 16 2 8 1 1400 30 20 Effective July 1998 230 V only VOLTAGE CHANGE PROCEDURE AND TERMINAL BOARD DESIGN Jet pump motors have a voltage plug to facilitate simple voltage changes from 115V to 230V All HP motors are fac tory wired for 11...

Страница 11: ...less than pump capacity throttle a ball valve in suction line do not exceed 22 Hg to reduce pump capacity USE OF TAILPIPE ON DEEP WELL JET PUMPS If the capacity of a deep well jet pump exceeds the well production well drawdown will allow your pump to break suction and lose prime This can be overcome by using a 34 tailpipe between the jet assembly and the foot valve Since the capacity of a pump fal...

Страница 12: ... have these definitions 1 Distributor means any individual partnership corporation association or other legal relationship that stands between Goulds Water Technology and the dealer in pur chases consignments or contracts for sale of the subject pumps 2 Dealer means any individual partnership corporation association or other legal relationship which engages in the business of selling or leasing pu...

Страница 13: ...MANUAL DE INSTRUCCIÓN IM102R07 Bombas de Inyección MANUAL DE INSTALACIÓN OPERACIÓN E IDENTIFICACIÓN Y RESOLUCIÓN DE PROBLEMAS ...

Страница 14: ...rvicio a cualquier equipo eléctrico Muchas bombas están equi padas con protección automática contra la sobrecarga térmica la cual podría permitir que una bomba demasiado caliente rear ranque inesperadamente Nunca presurice demasiado el tanque las tuberías o el sistema a una presión superior a la clasificación de presión máxima del tanque El hacerlo dañará el tanque anula la garantía y puede crear ...

Страница 15: ...vaciones de más de 25 pies y deben tener dos tuberías que vayan al pozo Hay dos tipos de conjun tos de inyección para pozos profundos los sistemas de tubo doble y los sistemas de obturador Las bombas para pozos profundos se ofrecen en diseños tanto verticales como horizontales y en modelos de una etapa y de etapas múltiples Consulte los dibujos de instalaciones típicas Figuras 2 y 3 Consulte con s...

Страница 16: ...ar Para impedir bombear en exceso un pozo de baja producción usted puede estrangular una bomba de inyección con una vál vula de bola en la línea de succión Usted debe instalar un indicador compuesto de presión vacío entre el pozo y la válvula No estrangule a más de 22 pulg Hg 25 pies de elevación En áreas donde ocurre congelación haga la transición de vertical a horizontal debajo del nivel de pene...

Страница 17: ... de la bomba y tanto la presión como los gpm disminuirán La bomba puede perder cebado fácilmente durante el bombeo debido a la restricción Si se utiliza tubería más pequeña que la recomendada podría reducirse la salida de gpm Mientras más larga es la tubería peor es el efecto Instale el conjunto del obturador Para facilitar la instalación remoje el conjunto del obtu rador de 2 ó 3 pulgadas en agua...

Страница 18: ...de su tanque Los tanques galvanizados se instalan de la misma manera que los tanques precargados excepto que requieren un control de volumen de aire AVC para reponer el aire perdido por absorción El control de volumen de aire requiere una conexión a un orificio de vacío en la bomba El lado de succión de dicho control debe tener un mínimo de 3 pulg de vacío durante 15 segundos cuando arranca la bom...

Страница 19: ... a las terminales de línea del interruptor por caída de presión Conecte el alambre verde o alambre desnudo de con exión a tierra a cualquiera de los tornillos verdes de conexión a tierra en el interruptor No hace ninguna dife rencia a qué terminal de línea se conecte el alambre L1 activado habitualmente de color negro y el neutro N de 115 voltios en el interruptor Lo mismo corresponde a la conexió...

Страница 20: ... 14 4 28 30 60 FP2 40 2 30 30 60 AWJ2 FT4 34 4 29 70 90 FP2 47 2 32 60 90 AV22KIT J7 FT4 18 4 30 90 110 o FT5 47 4 28 30 70 FP3 53 3 27 30 70 AWCJ3 AV22 and JDW FT5 48 4 40 70 110 FP3 54 3 30 70 110 FT4 44 4 31 30 60 FP2 48 2 35 30 60 AWJ2 FT4 43 4 33 60 80 FP2 43 2 36 60 100 AV22KIT J10 FT4 18 4 35 80 110 AV22 y JDW FT5 49 4 30 30 80 FP3 55 3 28 30 80 AWCJ3 FT5 11 4 32 80 120 FP3 14 3 32 80 120 F...

Страница 21: ...INYECCIÓN POZO LBS PULG CUADR INYECTOR INYECCIÓN LBS PULG CUADR INYECTOR OBTURADOR FT3 09 3 30 30 50 FP2 13 2 30 30 50 FT4 13 4 30 30 50 AV15 JRD5 FT4 31 4 30 30 70 FP2 31 2 30 30 60 AWJ2 o FT4 08 4 30 60 90 FP2 08 2 30 60 80 AV22KIT FT5 14 4 30 70 90 FT4 14 4 27 30 60 FP2 40 2 30 30 60 FT4 34 4 29 60 90 FP2 47 2 32 60 90 AWJ2 AV22KIT JRD7 FT4 18 4 30 90 110 AV22 y JDW FT5 47 4 27 30 70 NA FT5 48 ...

Страница 22: ...7 JRD7 JB07 C48C05A06 115 230 1 1 5 14 8 7 4 1200 30 15 SFJ06860 JRS10 JRD10 JB10 C48C06A06 1 115 230 1 1 4 16 2 8 1 1400 30 20 Fecha de vigencia julio de 1998 230 V únicamente DATOS TÉCNICOS Fig 7 PROCEDIMIENTO PARA EL CAMBIO DE TENSIÓN Y DISEÑO DE LA PLACA TERMINAL Los motores de las bombas de chorro A O Smith tienen un tapón de tensión para facilitar cambios simples de tensión de 115V a 230V To...

Страница 23: ...cidad de la bomba estrangule una válvula de bola en la línea de succión sin exceder 22 pulg de Hg para reducir la capacidad de la bomba USO DEL TUBO DE ASPIRACIÓN EN BOMBAS DE INYECCIÓN PARA POZOS PROFUNDOS Si la capacidad de una bomba de inyección para pozos profundos excede la producción del pozo el descenso de nivel del pozo hará que la bomba interrumpa la succión y pierda cebado Esto puede cor...

Страница 24: ...rporación asociación u otra persona jurídica que opera en relación legal entre Goulds Water Technology y el comerciante para la compra consignación o contratos de venta de las bombas en cuestión 2 Comerciante es todo individuo sociedad corporación asociación u otra persona jurídica que en el marco de una relación legal realiza negocios de venta o alquiler venta leasing de bombas a clientes 3 Clien...

Страница 25: ...Pompes À Jet MANUEL D INSTALLATION D UTILISATION ET DE DÉPANNAGE MANUEL D UTILISATION IM102R07 ...

Страница 26: ... ou l entretien des dispositifs électriques Le protecteur thermique de certains moteurs coupe le courant lorsqu il y a surcharge thermique et le rétablit automatiquement redémarrant ainsi la pompe inopinément Pour le système et le réservoir ne jamais utiliser une pression excédant la pres sion nominale maximale de ce dernier afin de ne pas l endommager annuler la garantie ni constituer un grave da...

Страница 27: ... descendant dans le puits Il en existe deux types à tuyaux jumelés ou à tuyaux concentriques Les pompes pour puits profonds sont offertes en versions horizontales ou verticales multi étagées ou non Voir les systèmes types aux fig 2 et 3 Consulter un détaillant professionnel ou le distributeur pour choisir le système qui convienne le mieux La température du liquide ne doit pas dépasser 60 C 140 F P...

Страница 28: ...ou dans la pompe Dans le cas des installations à pointe filtrante ou en puits tubulaires on peut poser un clapet de non retour près de la tête de puits ou de la pompe et utiliser le cuvelage comme tuyau d aspiration Plus le clapet de non retour est près du puits plus l amorçage sera facile Pour empêcher le surpompage des puits à faible débit on peut poser un robinet à tournant sphérique sur le tuy...

Страница 29: ... de soupapes ni de filtres entre la pompe et le réservoir sauf s il s agit d un robinet vanne grand ouvert ou d un robinet à tournant sphérique à passage intégral La plupart des robinets à tournant sphérique ordinaires ne sont pas à passage intégral La majorité des soupapes des robinets et des filtres causent une perte de charge excessive et le cliquetis répétitif du pressostat fonctionnement cycl...

Страница 30: ...our puits profonds Amorcer un système pour puits profonds signifie remplir d eau les tuyaux d aspiration et d alimentation en eau motrice ainsi que la pompe Les pompes multi étagées ou non pour puits profonds requièrent un amorçage complet avant d être mises en service Remplir les tuyaux avant d y fixer la pompe facilite l amorçage et fait gagner du temps Fixer la pompe à l adaptateur de tête de p...

Страница 31: ...étique DISJONCTEUR OU BOÎTE À FUSIBLE S PRESSOSTAT ROB À TOURNANT SPHÉR DANGER Lestensionsdangereuses peuventcauserunchoc électrique desbrûlureset lamort DANGER Lestensionsdangereuses peuventcauserunchoc électrique desbrûlureset lamort NE JAMAIS FAIRE FONCTIONNER LA POMPE À SEC CAR CELA L ENDOMMA GERAIT ET ANNULERAIT LA GARANTIE ON DOIT TOUJOURS VERROUILLER LE DISJONCTEUR OU LE SECTIONNEUR SELON L...

Страница 32: ... 120 FT5 12 4 35 30 70 FP3 16 3 34 30 60 J15 FT5 11 4 40 70 140 FP3 18 3 34 60 90 AWCJ3 AV22KIT FP3 21 3 34 90 150 AV22 et JDW FP3 24 3 39 100 170 FT4 48 4 37 30 70 FP2 51 30 70 SJ07 et FT4 47 4 40 70 90 FP2 50 2 40 70 90 AWD2 HSJ07 FT4 06 4 90 130 FP2 06 90 130 FP3 40 3 36 30 80 AWD3 FP3 42 40 80 130 FT4 47 4 40 30 70 FP2 50 30 60 SJ10 et FT4 24 4 43 70 110 FP2 07 2 45 60 110 AWD2 HSJ10 FT4 08 4 ...

Страница 33: ...WJ2 AV22KIT JRD7 FT4 18 4 30 90 110 AV22 et JDW FT5 47 4 27 30 70 S O FT5 48 4 30 70 110 FT4 44 4 31 30 60 FP2 48 2 35 30 60 FT4 43 4 33 60 80 FP2 43 2 36 60 100 AWJ2 AV22KIT JRD10 FT4 18 4 35 80 110 AV22 et JDW FT5 49 4 28 30 80 S O FT5 11 4 32 80 120 FT4 46 4 23 30 60 FP2 38 2 30 60 AWD2 VJ05 FT4 08 4 60 90 FP2 08 23 60 90 30 60 FP3 42 3 30 60 AWD3 60 100 FP3 09 60 100 FT4 47 4 34 30 60 FP2 50 3...

Страница 34: ...05 C48C04A06 115 230 1 1 6 12 6 6 3 990 25 15 SFJ05860 JRS7 JRD7 JB07 C48C05A06 115 230 1 1 5 14 8 7 4 1200 30 15 SFJ06860 JRS10 JRD10 JB10 C48C06A06 1 115 230 1 1 4 16 2 8 1 1400 30 20 230 V seulement à partir de juillet 1998 DONNÉES TECHNIQUES Fig 7 DANGER Lestensionsdangereuses peuventcauserunchoc électrique desbrûlureset lamort COMMUTATION DE TENSION AU BORNIER Le bornier des moteurs A O Smith...

Страница 35: ... débit de celle ci à l aide d un robinet à tournant sphérique posé sur le tuyau d aspiration et réglé pour augmenter la dépression qui ne doit cependant pas dépasser 22 po de Hg EMPLOI D UN TUYAU RALLONGE AVEC LES POMPES À JET POUR PUITS PROFONDS Si le débit d une pompe à jet pour puits profonds dépasse le débit entrant du puits il en résultera un rabattement baisse de niveau excessif donc l aspir...

Страница 36: ... servant d intermédiaire entre Goulds Water Technology et le détaillant pour les achats les consignations ou les contrats de vente des pompes en question 2 Détaillant veut dire une personne une société de personnes une société de capitaux une association ou autre entité juridique dont les activités commerciales sont la vente ou la location de pompes à des clients 3 Client désigne une entité qui ac...

Отзывы: