Device Description HG G-7335xZA | English, Revision 05 | Date: 19.02.2020
45
Profibus Interface (HG G-73351) – Chapter 9
9
Profibus Interface (HG G-73351)
The Node-ID has to be selected via the serial monitor described in section 7.2 on
page 20. Using the GSD file
73351A0.GSD
(see section 12.4 on page 52 in the ap
-
pendix) two different configurations can be displayed, see below. The order of the
bytes within a 16 bit word can be altered using the Profibus menu, point
(see sec
-
tion 7.3.4 on page 26).
1. Reading only of 5 input bytes according to the following table:
The meaning of the status bits is determined as follows:
2. In addition to item 1 the frequencies of the two wires can be
adjusted
If values outside of the defined value range are transmitted they will be ignored. Fre
-
quency changes are carried out with the frequency switch time specified in the
Technical Data.
Table 51
Format of the 5 Profibus Input Bytes
Value
Format
Range
Description
Status unsigned 8
0..0xff
Status bits according to Table 52 below
X1
signed 16
-255…..+255
-255 [mm]…..+255 [mm]
X2
signed 16
-255…..+255
-255 [mm]…..+255 [mm]
Table 52
Profibus: Meaning of the Profibus Status bits
Bit number
Valency
Description
7
0x80
Us1 has exceeded the set threshold for channel 1
6
0x40
Us2 has exceeded the set threshold for channel 2
5
0x20
Not used
4
0x10
Calibration active
3
0x08
DC supervision Ud1 OK
2
0x04
DC supervision Ud2 OK
1
0x02
Not used
0
0x01
The checksum of the EEPROM parameters is wrong
Table 53
Profibus: Structure of the Profibus Output Bytes
Wire
Format
Range
Description
F1
Unsigned 16
1000....28000
Wire frequency channel 1 [kHz]
F2
Unsigned 16
1000....28000
Wire frequency channel 2 [kHz]