Components and Operation
Revision 04 (English), Date: 26.04.2016
8
2.2.2.3
Front Plate Elements
Figure 1
Front plate HG 57400
24V
shows that power supply is on
O.K.
correct load impedance
Z<Zmin
short- circuit or load impedance too low
Z>Zmax
cable break or load impedance too high
Frequenz
Frequency setting (see Table 2 on page 7)
2.2.2.4
Short-circuit or Cable Break
A low load impedance is indicated by the red LED „Z<Zmin“. Tran-
sitional resistances amongst other things add to the load imped-
ance of a system; therefore it is not guaranteed that a short-circuit
would be indicated. High load impedances are detected as an in-
terruption within the loop and are indicated by the red LED „Z>Z
max“. In the normal load range the green LED „O.K“. is lit. The detection range is de-
pendant upon the chosen outputs and current rate.
Load impedance range when connected to loop end:
For the correct detection of cable break or short-circuit the actual required current and
size of impedance should be known, so that the generator can be set to these require-
ments.
2.2.2.5
Connection Plan for the Generator
LED
Short (I = 600 mA)
Long (I = 300 mA)
LED Z<Zmin
–
0 to 3
LED O.K.
1 to 15
3 to 75
LED Z>Zmax
> 15
> 75
Table 3
Load Impedance Ranges of the Generator
Connection Plan (according to DIN 41612, Form C, 64 pins, ac-equipped)
1ac
+24 V
25ac
Loop Start
2ac
26ac
15ac
Loop End Long
31ac
Ground
16ac
32ac
20ac
Loop End Short
21ac
Table 4
Connection plan generator