28
6. Technical data METRAVOLT VT 1500:
Nominal voltage
certified in accordance with
range:
IEC 61243-3
0 ... 1000 V AC / 1500 V DC
Display range:
0.03 V ... 1500 V DC
0.15 V ... 1200 V AC
Measurement range/
0.10 V ... 19.99 V
± 1 % + 3 D
Accuracy:
20.1 V ... 99.9 V
± 1 % + 3 D
100 V ... 1200 V AC ± 1 % + 3 D
100 V ... 1500 V DC ± 1 % + 3 D
< 500 Hz (TRMS)
> 500 Hz (Sin eff)
± 10 % + 3 D
Frequency:
16
- Hz ... 10 kHz < 500 V,
16
- Hz ... 2 kHz > 500 V
Display of voltage / phase/ phase sequence:
red LED for voltage,
yellow for phase sequence,
LCD digital display,
bicolour backlight,
7-segment-figure, 2 lines,
0 ... 1999 digit
Display of resistance / continuity / diodes:
green LED for continuity up to
999 kΩ and diodes, LCD
3½-digit for kΩ-reading,
buzzer ≤ 1.00 kΩ for 5 seconds
Measuring range - Resistance:
0.00 ... 999 kΩ
(5 % + 5 D)
Measuring range - Frequency:
16
- Hz ... 99.9 Hz / 100 ... 9999 Hz
Input resistance:
317 kΩ at 50 V / 50 Hz
200 kΩ at 1000 V AC,
589 kΩ at 1000 V DC
Current (Peak value):
direct: 3.5 mA at 1000 V
switched: < 300 mA at 1000 V
On-time ton / recovery time toff):
at 230 V / 400 V unlimited
at U
N
2 min ton / 2 min toff
Overvoltage category:
CAT IV 1000 V
in acc. to IEC 60664-1 (VDE 0110)
Surge withstand capability:
>19.2 kV housing-insulation
to operator
>12.0 kV circuit between
the test electrodes
Insulation test voltage:
6 kV / 5 s - routine test
housing and connection line
Operating temperatures:
-15°C ... + 55°C
Power supply:
2 x 1.5 V AAA LR03
automatic off after 30 s of
inactivity
multi-stage display of battery
status
Housing:
ABS/PC/TPE,
display cover PC impact resistant,
handle to lock in place,
belt clip
2
3
2
3
2
3