*Neutral conductor shall be blue, line conductor shall be black or brown (preferred), protective earth bonding line shall be
yellow-green.
*Fix (moment: 0.6N.m) the connector of AC cable to the corresponding terminals
3.4.1 Connection to grid (AC side Connection)
3.4 Electrical Connection
(1) Check the grid voltage and frequency if it can comply with the required voltage and frequency of inverter connection.
(2) Add breaker or fuse to AC side, the specification should be more than 1.25 times of rated AC output current.
(3) The PE line of inverter should be connected to the earth, make sure the impedance of neutral wire and earth wire less than
10 ohm.
(4) Disconnect the breaker or fuse between the inverter and the utility.
(S) Connect the inverter to the grid as follows:
There are two AC connector brands for inverter, VACONN and WIELAND. Please refer to Figure 3.4.1-1
(6)The AC line construction shall be such that if the cord should slip in its anchorage, placing a strain on conductors, the
protective earthing conductor will be the last to take the strain. such as the PE line is longger than L and N.
Installation instruction of VACONN series please refer to Figure 3.4.1-2.
fasten screw cap clockwise
4mm Copper Conductor
Material (Annealed copper wire)
2
fasten screw cap clockwise
fasten screw cap clockwise
Fastening three screws
to ensure each screw head
is not exceeding the surface
Fastening three screws
to ensure each screw head
is not exceeding the surface
Material (Annealed copper wire)
Installation instruction of WIELAND series please refer to Figure 3.4.1-3.
Cable specification of AC side please refer to Figure 3.4.1-4
.
Annealed copper wire
Conductor Material
Sectional Area
O.D.
A
Bare Wire Length
C
Grade Description
Value
10mm around