Goodman GSZ16 Скачать руководство пользователя страница 6

6

NOTES:

1) TERMINAL BLOCK MARKINGS ARE FOR GOODMAN/AMANA

    AIR HANDLERS.

NOMENCLATURE

EHR -EMERGENCY HEAT RELAY (OPTIONAL)

COLOR CODES

BL-- BLUE

BR--BROWN

GR--GREEN
OR--ORANGE

RD--RED

WH-WHITE

 Y--YELLOW

BL/PK--BLUE/PINK STRIPE

O
R
A
N
G

E

#18 GA. 5 WIRE

BL

O

W

BL

W

G

C

BLUE

W2

G

WHITE

GREEN

ROOM THERMOSTAT

HEAT PUMP

B
L
U
E

W

H

I

T
E

R

E

D

R

#18 GA. 7 WIRE

R

INDOOR UNIT

R

RED

W3

BROWN

BR

R

G

BR

BL

W2

C

O

Y

R

Y

O

C

G

R

E

SYSTEM COMPOSITE DIAGRAM - ALL SIZES (EXCEPT 5T 16 SEER) HEAT PUMPS - ABOVE 10 KW

W2

TYPICAL H/P

ROOM THERMOSTAT

HEAT PUMP

R

G

C

W2

RED

GREEN

WHITE

BLUE

INDOOR UNIT

R

O

W

BL

#18 GA. 5 WIRE

R

G

BR

W

BL

R
E
D

O
R
A
N
G
E

W

H

I

T
E

B
L
U
E

BL

W

G

R

C

O

Y

R

Y

O

C

W2

G

R

E

SYSTEM COMPOSITE DIAGRAM - ALL SIZES (EXCEPT 5T 16 SEER) HEAT PUMPS - 10 KW & BELOW

NOTES:

1) TERMINAL BLOCK MARKINGS ARE FOR GOODMAN/AMANA

    AIR HANDLERS.

NOMENCLATURE

EHR -EMERGENCY HEAT RELAY (OPTIONAL)

COLOR CODES

BL-- BLUE

BR--BROWN

GR--GREEN
OR--ORANGE

PU--PURPLE

RD--RED

WH-WHITE
 Y--YELLOW

BL/PK--BLUE/PINK STRIPE

O
R
A
N
G
E

#18 GA. 5 WIRE

BL

O

W

ROOM THERMOSTAT

HEAT PUMP

B
L
U
E

W

H

I

T
E

W2

C

O

Y

Y

Y2

Y

BL

W

G

C

BLUE

W2

G

WHITE

GREEN

R

INDOOR UNIT

R

RED

W3

BROWN

BR

R

G

BR

BL

O

C

G

R

E

SYSTEM COMPOSITE DIAGRAM - 5T 16 SEER ONLY HEAT PUMPS - ABOVE 10 KW

W2

ROOM THERMOSTAT

HEAT PUMP

R

O

W

BL

#18 GA. 5 WIRE

O
R
A
N
G
E

W

H

I

T
E

B
L
U
E

C

O

Y

R
E
D

R

Y

R

G

C

W2

RED

GREEN

WHITE

BLUE

INDOOR UNIT

R

G

BR

W

BL

BL

W

G

R

O

C

W

G

R

E

SYSTEM COMPOSITE DIAGRAM -  5T 16 SEER ONLY HEAT PUMPS - 10 KW & BELOW

Y2

Y2

Y

R
E
D

R

R

Y2

 Thermostat

with Low Voltage Wires to Heat Pump Unit

System Start Up

NOTE: 

Units with crankcase heaters should have high

voltage power energized for 24 hours prior to start up.

Heat pumps are equipped with a time/temperature defrost
control with field selectable defrost intervals of 30, 60, or
90 minutes.  This setting should be adjusted at this time if
needed. The defrost control also has SmartShift

technology, which delays compressor operation at defrost
initiation and termination.  If disabling this function is
desired, move the jumper from 

DLY

 to 

NORM

 on the

defrost control

Adequate refrigerant charge for the matching HSVTC evapora-
tor coil and 15 feet of lineset is supplied with the condensing
unit. If using evaporator coils other than HSVTC coil, it may be
necessary to add or remove refrigerant to attain proper charge.
If line set exceeds 15 feet in length, refrigerant should be added
at .6 ounces per foot of liquid line.

NOTE:

 Charge should always be checked using superheat when

using a piston and subcooling when using TXV equipped in-
door coil to verify proper charge.

Open the suction service valve first! If the liquid service valve is
opened first, oil from the compressor may be drawn into the
indoor coil TXV, restricting refrigerant flow and affecting opera-
tion of the system.

POSSIBLE REFRIGERANT LEAK
To avoid a possible refrigerant leak, open the service 
valves until the top of the stem is 1/8

 from the retainer.

CAUTION

When opening valves with retainers, open each valve only until
the top of the stem is 1/8

 from the retainer.  To avoid loss of

refrigerant, DO NOT apply pressure to the retainer. When open-
ing valves without a retainer remove service valve cap and in-
sert a hex wrench into the valve stem and back out the stem
by turning the hex wrench counterclockwise. Open the valve
until it contacts the rolled lip of the valve body.

NOTE: 

These are not back-seating valves. It is not necessary

to force the stem tightly against the rolled lip.

After the refrigerant charge has bled into the system, open the
liquid service valve. The service valve cap is the secondary seal
for the valve and must be properly tightened to prevent leaks.
Make sure cap is clean and apply refrigerant oil to threads and
sealing surface on inside of cap. Tighten cap finger-tight and
then tighten additional 1/6 of a turn (1 wrench flat), or to the
following specification,  to properly seat the sealing surfaces.

1. 3/8

 valve to 5 - 10 in-lbs

2. 5/8

 valve to 5 - 20 in-lbs

3. 3/4

 valve to 5 - 20 in-lbs

4. 7/8

 valve to 5 - 20 in-lbs

Do not introduce liquid refrigerant from the cylinder into the
crankcase of the compressor as this may damage the
compressor.

Содержание GSZ16

Страница 1: ...lity of the carrier Verify the model number specifications electrical characteristics and accessories are correct prior to installation The distribu tor or manufacturer will not accept claims from dea...

Страница 2: ...r springs can be installed between the con densing unit legs or frame and the roof mounting assembly to reduce noise vibration NOTE These units require special location consideration in areas of heavy...

Страница 3: ...tance Cond Unit Tons Suct Liq Suct Liq Suct Liq 1 1 2 5 8 1 4 3 4 3 8 3 4 3 8 2 5 8 1 4 3 4 3 8 3 4 3 8 2 1 2 5 8 1 4 3 4 3 8 7 8 3 8 3 3 4 3 8 7 8 3 8 1 1 8 3 8 3 1 2 7 8 3 8 1 1 8 3 8 1 1 8 3 8 4 7...

Страница 4: ...ented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size...

Страница 5: ...ch located near the unit do not install the switch on the unit Refer to the installa tion instructions supplied with the indoor furnace air handler for specific wiring connections and indoor unit conf...

Страница 6: ...f disabling this function is desired move the jumper from DLY to NORM on the defrost control Adequate refrigerant charge for the matching HSVTC evapora tor coil and 15 feet of lineset is supplied with...

Страница 7: ...Charge Adjustment The outdoor temperature must be 60 F or higher Set the room thermostat to COOL fan switch to AUTO and set the tem perature control well below room temperature Purge gauge lines Conne...

Страница 8: ...URATED SUCTION TEMPERATURE F LIQUID PRESSURE PSIG R 22 R 410A 200 101 70 210 105 73 220 108 76 225 110 78 235 113 80 245 116 83 255 119 85 265 121 88 275 124 90 285 127 92 295 130 95 305 133 97 325 13...

Страница 9: ...nit and refrigerant tubing sizes These adjustments should only be performed by qualified service personnel AdvancedAdjustmentRecommendations SUPERHEATFORMULA SUCTIONLINETEMPERA TURE SATURATEDSUCTIONTE...

Страница 10: ...t with Voltmeter Low Voltage Test Voltage Faulty Evap Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortag...

Страница 11: ...airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually c...

Страница 12: ...gh not required to get the protection of the standard warranty registering your product is a relatively short process and entitles you to additional warranty protection except that failure by Californ...

Отзывы: