Goodman GSZ16 Скачать руководство пользователя страница 5

5

5000

4500

4000

3500

3000

2500

2000

1500

1000

500

0      1      2      3      4       5      6      7      8       9

10

LEAK(S)
PRESENT

MINUTES

V

AC

U

U

M

 

IN

 

MI

C

R

O

N

S

CONDENSIBLES OR SMALL
LEAK PRESENT

NO LEAKS
NO CONDENSIBLES

If the pressure rises to 1000 microns or less and remains
steady the system is considered leak-free; proceed to
startup.

If pressure rises above 1000 microns but holds steady
below 2000 microns, moisture and/or noncondensibles
may be present or the system may have a small leak.
Return to step 2: If the same result is encountered check
for leaks as previously indicated and repair as necessary
then repeat evacuation.

If pressure rises above 2000 microns, a leak is present.
Check for leaks as previously indicated and repair as nec-
essary then repeat evacuation.

Electrical Connections

HIGH VOLTAGE!

 

Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death due to electric shock.
Wiring must conform with NEC or CEC and all
local codes. Undersized wires could cause
poor equipment performance, equipment damage
or fire.

WARNING

To avoid the risk of fire or equipment damage, use
copper conductors.

WARNING

NOTICE

Units with reciprocating or rotary compressors and
non-bleed TXV

s require a Hard Start Kit

.

The condensing unit rating plate lists pertinent electrical data
necessary for proper electrical service and overcurrent protec-
tion.  Wires should be sized to limit voltage drop to 2% (max.)
from the main breaker or fuse panel to the condensing unit.
Consult the NEC, CEC, and all local codes to determine the
correct wire gauge and length.

Local codes often require a disconnect switch located near the
unit; do not install the switch on the unit.  Refer to the installa-
tion instructions supplied with the indoor furnace/air handler for
specific wiring connections and indoor unit configuration.  Like-
wise, consult the instructions packaged with the thermostat
for mounting and location information.

Overcurrent Protection

The following overcurrent protection devices are approved for
use.

Time delay fuses

HACR type circuit breakers

These devices have sufficient time delay to permit the motor-
compressor to start and accelerate its load.

Three Phase Compressor Rotation

Use care when handling scroll compressors. Dome temp-
eratures could be hot.

CAUTION

Three phase compressors are power phase dependent and
can rotate in either direction.

Verify proper rotation for three phase compressors by ensuring
the suction pressure drops and discharge pressure rises when
the compressor is energized. 

NOTE: 

 When operated in re-

verse, a three phase scroll compressors is noisier and its cur-
rent draw substantially reduced compared to marked values.

To correct, disconnect power and switch any two leads at the
unit contactor and re-observe.

High Voltage Connections

Route power supply and ground wires through the high voltage
port and terminate in accordance with the wiring diagram pro-
vided inside the control panel cover.

Low Voltage Connections

The indoor transformer must supply 24 volt AC low voltage
power to the outdoor section for the control wiring.  Cooling
only units require 25VA minimum and heat pump units require
40VA minimum.  Low voltage wiring for two-stage units de-
pends on the thermostat used and the number of control wires
between the indoor unit and the condensing unit.  Route con-
trol wires through the low voltage port and terminate in accor-
dance with the wiring diagram provided inside the control panel
cover.

Содержание GSZ16

Страница 1: ...lity of the carrier Verify the model number specifications electrical characteristics and accessories are correct prior to installation The distribu tor or manufacturer will not accept claims from dea...

Страница 2: ...r springs can be installed between the con densing unit legs or frame and the roof mounting assembly to reduce noise vibration NOTE These units require special location consideration in areas of heavy...

Страница 3: ...tance Cond Unit Tons Suct Liq Suct Liq Suct Liq 1 1 2 5 8 1 4 3 4 3 8 3 4 3 8 2 5 8 1 4 3 4 3 8 3 4 3 8 2 1 2 5 8 1 4 3 4 3 8 7 8 3 8 3 3 4 3 8 7 8 3 8 1 1 8 3 8 3 1 2 7 8 3 8 1 1 8 3 8 1 1 8 3 8 4 7...

Страница 4: ...ented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size...

Страница 5: ...ch located near the unit do not install the switch on the unit Refer to the installa tion instructions supplied with the indoor furnace air handler for specific wiring connections and indoor unit conf...

Страница 6: ...f disabling this function is desired move the jumper from DLY to NORM on the defrost control Adequate refrigerant charge for the matching HSVTC evapora tor coil and 15 feet of lineset is supplied with...

Страница 7: ...Charge Adjustment The outdoor temperature must be 60 F or higher Set the room thermostat to COOL fan switch to AUTO and set the tem perature control well below room temperature Purge gauge lines Conne...

Страница 8: ...URATED SUCTION TEMPERATURE F LIQUID PRESSURE PSIG R 22 R 410A 200 101 70 210 105 73 220 108 76 225 110 78 235 113 80 245 116 83 255 119 85 265 121 88 275 124 90 285 127 92 295 130 95 305 133 97 325 13...

Страница 9: ...nit and refrigerant tubing sizes These adjustments should only be performed by qualified service personnel AdvancedAdjustmentRecommendations SUPERHEATFORMULA SUCTIONLINETEMPERA TURE SATURATEDSUCTIONTE...

Страница 10: ...t with Voltmeter Low Voltage Test Voltage Faulty Evap Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortag...

Страница 11: ...airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually c...

Страница 12: ...gh not required to get the protection of the standard warranty registering your product is a relatively short process and entitles you to additional warranty protection except that failure by Californ...

Отзывы: