background image

7

Models

Nominal

Charge

 (oz.)

GSC13018

75

GSC13024

77

GSC13030

66

GSC13036

77

GSC13042

95

GSC13048

89

GSC13060

131

‡ Approximate charge shown for 15’ of 3/8” liquid line. System charge must be

adjusted per final charge adjustment (Page 7.)

2. Set thermostat to call for cooling.  Check indoor and out-

door fan operation and allow system to stabilize for 10
minutes for fixed orifices and 20 minutes for expansion
valves.

Charge Verification

REFRIGERANT UNDER PRESSURE!

 

• Do not overcharge system with refrigerant.
• Do not operate unit in a vacuum or at negative pres-
  sure.
Failure to follow proper procedures may cause 
property damage, personal injury or death.

WARNING

Use refrigerant certified 

 standards. Use of used 

refrigerant may cause compressor damage that is not
covered under warranty.  Most portable machines cannot 
clean used refrigerant to meet 

tandards.

to AHRI

AHRI s

CAUTION

NOTICE

Violation of EPA regulations may result in fines or other
penalties.

Operating the compressor with the suction valve closed 
may cause serious compressor damage.

CAUTION

Final Charge Adjustment

The outdoor temperature must be 60°F or higher. Set the room
thermostat to COOL, fan switch to AUTO, and set the tem-
perature control well below room temperature.

After system has stabilized per startup instructions, check
subcooling and superheat as detailed in the following section.

Fixed Orifice

CAUTION

To prevent personal injury, carefully connect and disconnect
manifold gauge hoses. Escaping liquid refrigerant can cause
burns. Do not vent refrigerant into the atmosphere. Recover
all refrigerant during system repair and before final unit
disposal.

1. Purge gauge lines. Connect service gauge manifold to

base-valve service ports. Run system at least 10 minutes
to allow pressure to stabilize.

2. Temporarily install thermometer on suction (large) line

near suction line service valve with adequate contact and
insulate for best possible reading.

3. Refer to the superheat table provided for proper system

superheat. Add charge to lower superheat or recover
charge to raise superheat.

4. Disconnect manifold set, installation is complete.

Superheat Formula = Suct. Line Temp. - Sat. Suct. Temp.

Expansion Valve System

1. Purge gauge lines. Connect service gauge manifold

tobase-valve service ports. Run system at least 10 min-
utes to allow pressure to stabilize.

2. Temporarily install thermometer on liquid (small) line near

liquid line service valve with adequate contact and insu-
late for best possible reading.

3. Check subcooling and superheat. Systems with TXV ap-

plication should have a subcooling of 7 ± 2 ºF and super-
heat of 8 ± 1 ºF.

a.

If subcooling and superheat are low, 

adjust

 TXV to

8 ± 1 ºF superheat, then check subcooling.

NOTE:

 To adjust superheat, turn the valve stem clock-

wise to increase and counter clockwise to decrease.

b.

If subcooling is low and superheat is high, 

add 

charge

to raise subcooling to 7 ± 2ºF then check super-
heat.

c.

If subcooling and superheat are high, 

adjust

 TXV

valve to 8 ± 1 ºF superheat, then check subcooling.

d.

If subcooling is high and superheat is low, 

adjust

TXV valve to 8 ± 1 ºF superheat and 

remove 

charge

to lower the subcooling to 7 ± 2ºF.

NOTE:

 Do 

NOT 

adjust the charge based on suction pres-

sure unless there is a gross undercharge.

4. Disconnect manifold set, installation is complete.

Subcooling Formula = Sat. Liquid Temp. - Liquid Line Temp.

NOTE

: Check the Schrader ports for leaks and tighten valve

cores if necessary. Install caps finger-tight.

Содержание GSC13018

Страница 1: ...ds It is the owner s and installer s responsibility to read and com ply with all safety information and instructions accompanying these symbols Failure to heed safety information increases the risk of...

Страница 2: ...t in a structure that is not complete either as part of new construction or renovation will void the warranty Installation Clearances Special consideration must be given to location of the con densing...

Страница 3: ...onger than necessary for installation CAUTION Use only refrigerant grade dehydrated and sealed copper tub ing to connect the condensing unit with the indoor evaporator After cutting the tubing install...

Страница 4: ...tion when using the heat trap compound Note Remove Schrader valves from service valves before brazing tubes to the valves Use a brazing alloy of 2 minimum silver content Do not use flux Torch heat req...

Страница 5: ...or less using suc tion and liquid service valves Using both valves is nec essary as some compressors create a mechanical seal separating the sides of the system 4 Close pump valve and hold vacuum for...

Страница 6: ...ow proper procedures may cause property damage personal injury or death WARNING 1 Add refrigerant amount shown in table below for the unit being installed Local codes often require a disconnect switch...

Страница 7: ...nit disposal 1 Purge gauge lines Connect service gauge manifold to base valve service ports Run system at least 10 minutes to allow pressure to stabilize 2 Temporarily install thermometer on suction l...

Страница 8: ...10 105 220 108 225 110 235 113 245 116 255 119 265 121 275 124 285 127 295 130 305 133 325 137 355 144 375 148 405 155 415 157 425 n a 435 n a 445 n a 475 n a 500 n a 525 n a 550 n a 575 n a 600 n a 6...

Страница 9: ...it Test Control Circuit with Voltmeter Low Voltage Test Voltage Faulty Evaporator Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resis...

Страница 10: ...10 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 11: ...11 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 12: ...ty standards regardless of size or effi ciency We have designed these units to significantly reduce the most frequent causes of product failure They are simple to service and forgiving to operate We u...

Отзывы: