background image

3

Refrigerants are heavier than air. They can "push out"
the oxygen in your lungs or in any enclosed space.To
avoid possible difficulty in breathing or death:

•  

Never purge refrigerant into an enclosed room or

   space. By law, all refrigerants must be reclaimed.

•  

If an indoor leak is suspected, throughly ventilate the

   area before beginning work.
•  Liquid refrigerant can be very cold. To avoid possible
   frostbite or blindness, avoid contact and wear gloves
   and goggles.  If liquid refrigerant does contact your
   skin or eyes, seek medical help immediately.
•  Always follow EPA regulations. Never burn refrig-
   erant, as poisonous gas will be produced.

WARNING

To avoid possible explosion:
  Never apply flame or steam to a refrigerant cylinder.
    If you must heat a cylinder for faster charging,
    partially immerse it in warm water.

Never fill a cylinder more than 80% full of liquid re-

    frigerant.
•   Never add anything other than R-22 to an R-22 cy-
    linder . The service equipment used must be listed
    or certified for the type of refrigerant used.
•   Store cylinders in a cool, dry place. Never use a cy-
    linder as a platform or a roller.

•  

•   

To avoid possible explosion, use only returnable (not
disposable) service cylinders when removing refrig-
erant from a system.
 •  Ensure the cylinder is free of damage which could
    lead to a leak or explosion.
•   Ensure the hydrostatic test date does not exceed
    5 years.
•   Ensure the pressure rating meets or exceeds 400
    lbs.

When in doubt, do not use cylinder.

WARNING

Refrigerant Lines

The compressor mineral oil for R-22 units is susceptible to
moisture absorption and could cause compressor failure. 
Do not leave system open to atmosphere any longer than 
necessary for installation. 

CAUTION

Use only refrigerant grade (dehydrated and sealed) copper tub-
ing to connect the condensing unit with the indoor evaporator.
After cutting the tubing, install plugs to keep refrigerant tubing
clean and dry prior to and during installation.  Tubing should
always be cut square keeping ends round and free from burrs.
Clean the tubing to prevent contamination.

Do NOT let refrigerant lines come in direct contact with plumb-
ing, ductwork, floor joists, wall studs, floors, and walls.  When
running refrigerant lines through a foundation or wall, openings
should allow for sound and vibration absorbing material to be
placed or installed between tubing and foundation. Any gap
between foundation or wall and refrigerant lines should be filled
with a pliable silicon-based caulk, RTV or a vibration damping
material. Avoid suspending refrigerant tubing from joists and
studs with rigid wire or straps that would come in contact with
the tubing. Use an insulated or suspension type hanger. Keep
both lines separate and always insulate the suction line.

These sizes are recommended for line lengths of 79 feet or
less. For other line sizing option or runs of more than fifty feet,
refer to Remote Cooling Service Manual, or TP-106 Long Line
Set Application R-22, or contact your distributor for assistance.

Cond

Unit

Tons

Suct

Liq

Suct

Liq

Suct

Liq

1 1/2

5/8

1/4

3/4

3/8

3/4

3/8

2

5/8

1/4

3/4

3/8

3/4

3/8

2 1/2

5/8

1/4

3/4

3/8

7/8

3/8

3

3/4

3/8

7/8

3/8

1 1/8

3/8

3 1/2

7/8

3/8

1 1/8

3/8

1 1/8

3/8

4

7/8

3/8

1 1/8

3/8

1 1/8

3/8

5

7/8

3/8

1 1/8

3/8

1 1/8

3/8

Line Diameter (In. OD)

RECOMMENDED INTERCONNECTING TUBING (Ft)

0-24

25-49

    50-79*

* Lines greater than 79 feet in length or vertical elevation 
changes more than 50 feet 

refer to the Rem ote Cooling 

Service Manual or contact your distributor for assistance.

Содержание GSC13018

Страница 1: ...ds It is the owner s and installer s responsibility to read and com ply with all safety information and instructions accompanying these symbols Failure to heed safety information increases the risk of...

Страница 2: ...t in a structure that is not complete either as part of new construction or renovation will void the warranty Installation Clearances Special consideration must be given to location of the con densing...

Страница 3: ...onger than necessary for installation CAUTION Use only refrigerant grade dehydrated and sealed copper tub ing to connect the condensing unit with the indoor evaporator After cutting the tubing install...

Страница 4: ...tion when using the heat trap compound Note Remove Schrader valves from service valves before brazing tubes to the valves Use a brazing alloy of 2 minimum silver content Do not use flux Torch heat req...

Страница 5: ...or less using suc tion and liquid service valves Using both valves is nec essary as some compressors create a mechanical seal separating the sides of the system 4 Close pump valve and hold vacuum for...

Страница 6: ...ow proper procedures may cause property damage personal injury or death WARNING 1 Add refrigerant amount shown in table below for the unit being installed Local codes often require a disconnect switch...

Страница 7: ...nit disposal 1 Purge gauge lines Connect service gauge manifold to base valve service ports Run system at least 10 minutes to allow pressure to stabilize 2 Temporarily install thermometer on suction l...

Страница 8: ...10 105 220 108 225 110 235 113 245 116 255 119 265 121 275 124 285 127 295 130 305 133 325 137 355 144 375 148 405 155 415 157 425 n a 435 n a 445 n a 475 n a 500 n a 525 n a 550 n a 575 n a 600 n a 6...

Страница 9: ...it Test Control Circuit with Voltmeter Low Voltage Test Voltage Faulty Evaporator Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resis...

Страница 10: ...10 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 11: ...11 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 12: ...ty standards regardless of size or effi ciency We have designed these units to significantly reduce the most frequent causes of product failure They are simple to service and forgiving to operate We u...

Отзывы: