PACKAGE COOLING SPECIFICATIONS
32
GPC1324H41B*
GPC1324H41C*
APC1324H41C*
*PC1330H41B*/C*
COOLING CAPACITY, BTUH
24,000
24,000
22,800
28,600
SEER
13.0
13.0
13.0
13.0
VOLTAGE (NAMEPLATE)
208-230/1/60
208-230/1/60
208-230/1/60
208-230/1/60
AMPS (TOTAL)
10.5
10.3
16.1
15.76
MINIMUM CIRCUIT AMPACITY
12.5
12.2
19.5
19
MAXIMUM OVERCURRENT PROTECTION
(1)
20
15
30
30
TYPE
RECIP
ROTARY
SCROLL
SCROLL
RATED LOAD AMPS
7.9
7.7
13.5
12.8
LOCKED ROTOR AMPS
41
37
58.3
64
HORSEPOWER
1/6
1/6
1/6
1/6
RPM
815
815
815
815
FULL LOAD AMPS
1.1
1.1
1.1
1.1
LOCKED ROTOR AMPS
1.7
1.7
1.7
1.7
CONDENSER FAN
BLADE DIAMETER (INCHES) / # OF BLADES
22 / 3
22 / 2
22 / 2
22 / 2
FACE AREA - SQ. FT.
13.4
12.3
12.3
12.3
NUMBER OF ROWS
1
1
1
1
FINS PER INCH
24
26
27
27
HORSEPOWER - NO. OF SPEEDS
1/4 - 3
1/4 - 3
1/4 - 3
1/3 - 3
FULL LOAD AMPS
1.5
1.5
1.5
1.86
LOCKED ROTOR AMPS
2.2
2.2
2.2
3.2
MOTOR SPEED TAP - COOLING
MEDIUM
MEDIUM
MEDIUM
LOW
RPM
1075
1075
1075
1075
DIAMETER X WIDTH (INCHES)
9 x 6
9 x 6
9 x 6
9 x 6
RATED SCFM COOLING
815
815
850
1,050
MAX EXTERNAL STATIC PRESS ("w.c.)
0.5
0.5
0.5
0.5
FACE AREA - SQ. FT.
4.6
4.66
4.66
4.66
NUMBER OF ROWS
3
3
3
3
FINS PER INCH
14
14
14
14
FILTER SIZE - SQ. FT. *
20 x 20 x 1
20 x 20 x 1
20 x 20 x 1
20x 25 x 1
DRAIN SIZE (INCHES)
3/4"
3/4"
3/4"
3/4"
EXPANSION DEVICE
ORIFICE (0.059)
ORIFICE (0.057)
ORIFICE (0.057)
ORRIFICE (0.062)
REFRIGERANT CHARGE R-410A (Oz.)
80
63
63
62
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.)
3/4, 1, 1-1/4
3/4, 1, 1-1/4
3/4, 1, 1-1/4
3/4, 1, 1-1/4
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)
1/2
1/2
1/2
1/2
SHIPPING WEIGHT LBS.
310
305
305
305
OPERATING WEIGHT LBS.
300
300
300
300
EVAPORATOR
BLOWER
EVAPORATOR COIL
GENERAL
INFORMATION
COOLING
CAPACITY
UNIT ELECTRICAL
SPECIFICATION
COMPRESSOR
CONDENSER FAN
MOTOR
CONDENSER COIL
EVAPORATOR
BLOWER MOTOR
*PC13[24-30]H41B*/C*
IMPORTANT:
While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
(1)
Maximum Overcurrent Protection Device:
MUST
use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
*
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice.
ALWAYS
refer to the units serial plate for the most up-to-date general and electrical information.