PACKAGE COOLING SPECIFICATIONS
31
GPC1342H41AB
GPC1349H41AA
GPC1360H41BB
GPC1342H41AB
GPC1349H41AA
GPC1360H41BB
C OOLING
COOLING CAPACITY, BTUH
41,000
45,500
57,500
C APACITY
SEER
13.0
13.0
13.0
U NIT
VOLTAGE (NAMEPLATE)
208-230/1/60
208-230/1/60
208-230/1/60
ELECTRICAL
AMPS (TOTAL)
22.17
24.17
33.6
SPECIFICATION
MINIMUM CIRC UIT AMPACITY
26.6
29.2
40.2
MAXIMUM OVERCURRENT PROTECTION
(1)
40
45
60
C OM PRESSOR
TYPE
SCROLL
SCROLL
SCROLL
RATED LOAD AMPS
17.9
19.9
26.4
LOCKED ROTOR AMPS
112
109
134
C ON DEN SER
HORSEPOWER
1/4
1/4
1/4
FAN MOTOR
RPM
1075
1075
1075
FULL LOAD AMPS
1.4
1.4
1.4
LOCKED ROTOR AMPS
2.9
2.9
2.9
C ON DEN SER FAN
BLADE DIAMETER (INCHES) /# OF BLADES
22 / 4
22 / 4
22 / 4
C ON DEN SER
FACE AREA - SQ. FT.
16.0
16.0
19.5
C OIL
NUMBER OF ROWS
1
1
1
FINS PER INC H
28
28
28
EVAPORATOR
HORSEPOWER - N O. OF SPEEDS
1/2 - 3
1/2 - 3
3/4 - 3
B LOWER
FULL LOAD AMPS
2.87
2.87
5.8
MOTOR
LOCKED ROTOR AMPS
4.9
4.9
NA
MOTOR SPEED TAP - COOLING
LOW
MED IUM
T2
RPM
1075
1075
1075
EVAPORATOR
DIAMETER X WIDTH (INCHES)
10 x 8
10 x 8
11 x 8
B LOWER
RATED SCFM COOLING
1,410
1,585
1,850
MAX EXTERNAL STATIC PRESS ("w .c.)
0.5
0.5
0.5
EVAPORATOR
FACE AREA - SQ. FT.
6.2
6.2
7.0
C OIL
NUMBER OF ROWS
4
4
4
FINS PER INC H
14
14
14
GENERAL
FILTER SIZE - SQ. FT. *
(2) 20 x 20 x 1
(2) 20 x 20 x 1
(2) 20 x 25 x 1
INFORMATION
DRAIN SIZE (INCHES)
3/4"
3/4"
3/4"
EXPANSION DEVICE
ORIFICE (0.072)
ORRIFIC E (0.078)
ORIFICE (0.088)
REFRIGERANT CHARGE R-410A (Oz.)
88
80
93
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.)
3/4, 1, 1-1/4
3/4, 1, 1-1/4
3/4, 1, 1-1/4
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)
1/2
1/2
1/2
SHIPPING WEIGHT LBS.
370
400
400
OPERATING WEIGHT LBS.
360
390
390
IMPORTANT:
While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
(1)
Maximum Overcurrent Protection Device:
MUST
use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
*
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice.
ALWAYS
refer to the units serial plate for the most up-to-date general and electrical information.