background image

5

Connecting the Return and Supply Flexible Duct in
Manufactured or Modular Housing Application

The return and supply fittings are to be attached at the unit
to a suitable square to round duct converter.  Your distributor
has a factory designed square to round converter transition.
The model #’s of these kits are as follows: Small Chassis
25” SQRPCH101, Medium Chassis 27.5” SQRPCH102,
Large and Extra Large Chassis 32.5:” and 36” SQRPCH103
(See Specification Sheets for Dimension details).  The
SQRPCH101 has 14" duct collar on supply and 16" duct
collar (equivalent diameter, opening is oval) on the return.
The SQRPCH102 and SQRPCH103 have 14" duct collar on
supply and 18" duct collar (equivalent diameter, opening is
oval) on the return. The collars are to be slipped into the
openings, and the flanges bent around the converter. The
square to round converter is attached to the flanges of the
square duct openings.  The flexible duct is then clamped
on to the collars. Once the duct is affixed to the unit, 

seal

the collars and flanges with a proper waterproof sealant

(See Figure 3).

It is strongly encouraged to use appropriately sized ducts
based upon the CFM for your application (unit’s CFM).  If
duct sizing through industry manuals or air duct calculators
require larger ducts than converter openings, run larger duct
size up to unit converter openings and reduce with a reducer
duct fitting or transition right at the unit.

NOMINAL S IZE   (INCHE S )

NO MINA L A RE A      (SQ . FT.)

10x20

1.4

14x20

1.9

14x25

2.4

15x20

2.1

16x20

2.2

16x25

2.8

20x20

2.8

20x25

3.5

25x25

4.3

M INIM U M   FILTE R  S IZE

TABLE 1

OUTER FLANGE

STARTER FLANGE

BEAD

SQUARE TO ROUND
DUCT CONVERTER PANEL

FIGURE 3

 500      1000    1500     2000    2500    3000    3500

7

6

5

4

3

2

DIS

PO

SA

BL

E F

ILT

ER

PER

MAN

ENT

  FIL

TER

Airflow - SCFM

N

o

m

in

a

F

ilt

e

A

re

a

S

q

u

a

re

 F

e

e

t

FIGURE 4

Plenum Application

A suitable plenum or square duct must be constructed. The
duct cross-sectional area should be determined by industry
duct sizing manuals or air duct calculators.

On ductwork exposed to outside air conditions of
temperature and humidity, use an insulation with a good K
factor, and a vapor barrier. Industry practices should be
followed.  Balancing dampers are recommended for each
branch duct in the supply system. Ductwork should be
properly supported from the unit.

NOTE: Proper sealing of all duct work and air handling
compartments is extremely important to overall unit
efficiency.

Filters

Filters are not provided with unit, and must be supplied and
installed in the return duct system by the installer.  A field
installed filter grille is recommended for easy and convenient
access to the filters for periodic inspection and cleaning.
Filters must have adequate face area for the rated quantity
of the unit. See air delivery tables (Figure 4) for
recommended filter size.

PIPING

Condensate Drain

The condensate drain connection of the evaporator is a half
coupling of ¾” N.P.T.  A trap must be provided to have Proper
condensate drainage.

2" Minimum

3" Minimum

A Positive Liquid Seal
Is Required

Flexible
Tubing-Hose
Or Pipe

Drain
Connection

Unit

FIGURE 5

Install condensate drain trap as shown. Use ¾ “ drain
connection size or larger. Do not operate without trap.  Unit
must be level or slightly inclined toward drain.

WIRING

All wiring should be made in accordance with the
National Electrical Code.  

The local Power Company

should be consulted to determine the availability of sufficient
power to operate the unit. The voltage, frequency, and phase
at the power supply should be checked to make sure it
corresponds to the unit’s RATED VOLTAGE
REQUIREMENT.

Install a branch circuit fused disconnect near the unit, in
accordance with the N.E.C. or local codes. Wire sizes and
overcurrent protection should be determined from the unit
nameplate ampacity and in accordance with Table 4 (page
6) or the N.E.C.  Under no circumstances should wiring be
sized smaller than is recommended by either of these two
sources.

Fuses smaller than that recommended on the wiring diagrams
could result in unnecessary fuse failure or service calls.
The use of protective devices of larger size than indicated
could result in extensive damage to the equipment. The
manufacturer bears no responsibility for damage caused to
equipment as result of the use of larger than is recommended
size protective devices.

Содержание GPC SERIES

Страница 1: ...on TX 77092 06 06 www goodmanmfg com www amana hac com 2005 2006 Goodman Manufacturing Company L P All information contained herein is subject to change without notice INSTALLATION OPERATING INSTRUCTI...

Страница 2: ...her shipping or concealed should be filed immediately with the shipping company Check the unit model number specifications electrical characteristics and accessories to determine if they are correct I...

Страница 3: ...ntinuous operating conditions independent of any installed system EPA Regulations IMPORTANT THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY EPA HAS ISSUED VARIOUS REGULATIONS REGARDING THE INTRODUCT...

Страница 4: ...gisters are low on the wall or in the floor compressor compartment and controls The top of the unit should be completely unobstructed If units are to be located under an overhang there should be a min...

Страница 5: ...ty use an insulation with a good K factor and a vapor barrier Industry practices should be followed Balancing dampers are recommended for each branch duct in the supply system Ductwork should be prope...

Страница 6: ...o 18AWG as follows LEAD THERMOSTAT Red R 24V Green G Fan Yellow Y Cool White W1 Heat Brown W2 Heat TABLE 2 b Heat Pumps Connect 24V wires from the thermostat to the corresponding wires in the control...

Страница 7: ...ht will come on 15 If checking the unit in the wintertime when the outdoor coil is cold enough to actuate the defrost control observe at least one defrost cycle to make sure the unit defrosts complete...

Страница 8: ...herefore all the charts and data for service that apply to summer air conditioning apply to the heat pump when it is on the cooling cycle and most apply on the heating cycle except that condenser beco...

Страница 9: ...the timing period the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 75 F the defrost cycle is terminated and the timing period is reset...

Страница 10: ...the proper amount All package units are charged to the superheat method at the compressor suction line these are fixed orifice devices For charging in the warmer months 10 F superheat at the compresso...

Страница 11: ...perly SERVICE THE FOLLOWING INFORMATION IS FOR USE BY QUALIFIED SERVICE AGENCY ONLY OTHERS SHOULD NOT ATTEMPT TO SERVICE THIS EQUIPMENT Common Causes of Unsatisfactory Operation of Heat Pump on the He...

Страница 12: ...nnection a Check for unit voltage at compressor check tighten all connections b Compressor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still...

Отзывы: