background image

11

SUPERHEAT CAN BE DETERMINED AS FOLLOWS:

1.

Read suction pressure.  Determine Saturated Suction
Temperature from tables or pressure gauge saturated
temperature scale (R-22).

2.

Read suction line temperature.

3.

Use the following formula:

SUPERHEAT = SUCTION LINE TEMP - SAT. SUCTION TEMP

ELECTRIC HEAT INSTALLATION & ADJUSTMENT

This series of electric cooling and heat pump package
equipment is designed to accept a field installed electric
heat kit. The unit is equipped to easily install the HKR Series
Electric Heat Kit. Full Installation Instructions are included
in this kit. Please use this document for guidance in field
equipping the package unit with electric heat.

Choose the heat kit that fits the application for the specific
installation. Permanently mark the unit’s nameplate with
the model being installed. High and low voltage connections
are detailed in the heat kit instructions.

Indoor Blower motor speed tap selection may need to be
modified to accommodate normal continuous operation to
prevent a nuisance trip.  

See table below.

Unit Model Number

5

8

10

15

20

GPC/GPH1324H21A

M

(F)

M

(F)

M

(F)

H

na

GPC/GPH1330H21A

L

(F)

L

(F)

L

(F)

M

na

GPC/GPH1336H21A

M

(F)

M

(F)

M

(F)

H

na

GPC/GPH1342H21A

L

(F)

L

(F)

M

M

H

GPC/GPH1348H21A

M

(F)

M

(F)

M

(F)

M

(F)

H

GPC/GPH1360H21A

2

(F)

2

(F)

2

(F)

2

(F)

2

(F)

H / 3 - High; M / 2 - Medium;  L / 1 - Low

Speed Taps Description:  H/M/L - PSC: 3/2/1 - X-13

Electric Heat KW

MAINTENANCE

HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE INSTALLING OR
SERVICING. MULTIPLE POWER SOURCES MAY BE
PRESENT.  FAILURE TO DO SO MAY CAUSE PROPERTY
DAMAGE, PERSONAL INJURY OR DEATH.

WARNING

The Self Contained Package Air Conditioner and Heat Pump
should operate for many years without excessive service
calls if the unit is installed properly. However it is
recommended that the homeowner inspect the unit before
a seasonal start up.  The coils should be free of debris so
adequate airflow is achieved. The return and supply registers
should be free of any obstructions. The filters should be
cleaned or replaced. These few steps will help to keep the
product up time to a maximum.   The Troubleshooting Chart
(on page 11) should help in identifying problems if the unit
does not operate properly.

SERVICE

THE FOLLOWING INFORMATION IS FOR USE BY
QUALIFIED SERVICE AGENCY ONLY: OTHERS SHOULD
NOT ATTEMPT TO SERVICE THIS EQUIPMENT.

Common Causes of Unsatisfactory Operation of Heat Pump
on the Heating Cycle.

Inadequate Air Volume Through Indoor Coil

When a heat pump is in the heating cycle, the indoor coil is
functioning as a condenser.  The return air filter must always
be clean, and sufficient air volume must pass through the
indoor coil to prevent excessive discharge pressure, and
high pressure cut out.

Outside Air Into Return Duct

Do not introduce cold outside air into the return duct of a
heat pump installation.  Do not allow air entering the indoor
coil to drop below 65° F.  Air below this temperature will
cause low discharge pressure, thus low suction pressure,
and excessive defrost cycling resulting in low heating output.
It may also cause false defrosting.

Undercharge

An undercharged heat pump on the heating cycle will
cause low discharge pressure resulting in low suction
pressure and frost accumulation on the outdoor coil.

Poor “Terminating” Sensor Contact

The unit’s defrost terminating sensor must make good
thermal contact with the outdoor coil tubing.  Poor contact
may not terminate the unit’s defrost cycle quickly enough
to prevent the unit from cutting out on high discharge
pressure.

Malfunctioning Reversing Valve

This may be due to:

1.

Solenoid not energized

 - In order to determine if the

solenoid is energized, touch the nut that holds the solenoid
cover in place with a screwdriver. If the nut magnetically
holds the screwdriver, the solenoid is energized and the
unit is in the cooling cycle.

2.

No voltage at unit’s solenoid

 - Check unit voltage. If no

voltage, check wiring circuit.

3.

Valve will not shift

:

a .

Undercharged

 - check for leaks;

b.

Valve Body Damaged

 - Replace valve;

c.

Unit Properly Charged

 - If it is on the heating

cycle, raise the discharge pressure by restricting airflow
through the indoor coil. If the valve does not shift, tap it

lightly

 on both ends with a screwdriver handle. 

Do Not

Tap The Valve Body

. If the unit is on the cooling cycle,

raise the discharge pressure by restricting airflow through
the outdoor coil. If the valve does not shift after the above
attempts, cut the unit off and wait until the discharge
and suction pressure equalize, and repeat above steps.
If the valve does not shift, replace it.

Содержание GPC SERIES

Страница 1: ...on TX 77092 06 06 www goodmanmfg com www amana hac com 2005 2006 Goodman Manufacturing Company L P All information contained herein is subject to change without notice INSTALLATION OPERATING INSTRUCTI...

Страница 2: ...her shipping or concealed should be filed immediately with the shipping company Check the unit model number specifications electrical characteristics and accessories to determine if they are correct I...

Страница 3: ...ntinuous operating conditions independent of any installed system EPA Regulations IMPORTANT THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY EPA HAS ISSUED VARIOUS REGULATIONS REGARDING THE INTRODUCT...

Страница 4: ...gisters are low on the wall or in the floor compressor compartment and controls The top of the unit should be completely unobstructed If units are to be located under an overhang there should be a min...

Страница 5: ...ty use an insulation with a good K factor and a vapor barrier Industry practices should be followed Balancing dampers are recommended for each branch duct in the supply system Ductwork should be prope...

Страница 6: ...o 18AWG as follows LEAD THERMOSTAT Red R 24V Green G Fan Yellow Y Cool White W1 Heat Brown W2 Heat TABLE 2 b Heat Pumps Connect 24V wires from the thermostat to the corresponding wires in the control...

Страница 7: ...ht will come on 15 If checking the unit in the wintertime when the outdoor coil is cold enough to actuate the defrost control observe at least one defrost cycle to make sure the unit defrosts complete...

Страница 8: ...herefore all the charts and data for service that apply to summer air conditioning apply to the heat pump when it is on the cooling cycle and most apply on the heating cycle except that condenser beco...

Страница 9: ...the timing period the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 75 F the defrost cycle is terminated and the timing period is reset...

Страница 10: ...the proper amount All package units are charged to the superheat method at the compressor suction line these are fixed orifice devices For charging in the warmer months 10 F superheat at the compresso...

Страница 11: ...perly SERVICE THE FOLLOWING INFORMATION IS FOR USE BY QUALIFIED SERVICE AGENCY ONLY OTHERS SHOULD NOT ATTEMPT TO SERVICE THIS EQUIPMENT Common Causes of Unsatisfactory Operation of Heat Pump on the He...

Страница 12: ...nnection a Check for unit voltage at compressor check tighten all connections b Compressor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still...

Отзывы: