background image

10

ADJUSTING SPEED TAP FOR INDOOR BLOWER
MOTOR

PSC Motor

Adjust the CFM for the unit by changing the speed tap of
the indoor blower motor at the EBTDR “com” connection
with one of the speed taps on “M1” or “M2”. (Black-High
Speed, Blue-Medium Speed, Red-Low Speed.)

X-13 Motor

The blower motor speed for the X-13 motor is controlled
by three 24V low voltage leads: green, yellow, and white.
The green lead sets the speed for fan-only mode. The
yellow lead sets the speed for cooling and heat pump
heating mode (if applicable).  The white lead sets the
speed for electric heat mode (emergency heat and second
stage heat, if applicable).

The leads are factory connected as follows: Green to T1,
Yellow to T2, and White to T3. T1 is the low speed setting
and is dedicated to fan-only mode.  T2 and T3 are medium
speed settings. T4 and T5 are high speed settings.  To
adjust the blower speed, move the yellow and/or white
wires to T4 and T5. 

NOTE: 

If more than one lead is

energized at the same time, the motor will use the higher
speed setting.

See Specification Sheet for GPC/GPH model series for
CFM vs ESP tables.

CHECKING CHARGE

After completing airflow measurements and adjustments,
the unit’s refrigerant charge must be checked.  The unit
comes factory charged, but this charge is based on 400
CFM per ton at minimum ESP per ARI test conditions
(generally between .15 - .25 ESP).  When air quantity or
ESP is different than above, charge must be adjusted to
the proper amount.  All package units are charged to the
superheat method at the compressor suction line (these
are fixed orifice devices).

For charging in the warmer months, 10

º

F superheat at the

compressor is required at conditions: 95

º

F outdoor ambient

(dry bulb temperature), 80

º

F dry bulb / 67

º

F wet bulb indoor

ambient, approximately 50% humidity.  This superheat
varies when conditions vary from the conditions described.

A superheat charge chart is available for other operating
conditions.  Use it to provide the correct superheat at the
conditions the unit is being charged at.

After superheat is adjusted it is recommended to check
unit sub-cooling at the condenser coil liquid line out.  In
most operating conditions 10 - 15

º

F of sub-cooling is

adequate.

Suction Pressure

Saturated Suction 

Temperature (°F)

50

26

53

28

55

30

58

32

61

34

63

36

66

38

69

40

72

42

75

44

78

46

81

48

84

50

87

52

TABLE  5

Suction Pressure Temperature (R-22)

DB

WB

63

301 - 332

73 - 83

115

75

67

306 - 335

77 - 78

71

311 - 342

82 - 92

63

268 - 299

72 - 82

105

75

67

273 - 304

77 - 87

71

278 - 309

80 - 90

63

233 - 264

67 - 77

95

75

67

238 - 269

72 - 82

71

243 - 274

77 - 87

63

198 - 229

62 - 72

85

75

67

203 - 234

67 - 77

71

208 - 239

71 - 81

63

172 - 203

57 - 67

75

75

67

175 - 206

61 - 71

71

180 - 211

66 - 76

63

144 - 175

52 - 62

65

75

67

149 - 180

56 - 66

71

155 - 186

60 - 70

INDOOR 

TEMP. °F

LIQUID 

PRESSURE 

PSIG

SUCTION 

PRESSURE 

PSIG

OUTDOOR 

TEMP. °F

TABLE  6

Operating Pressures

65

70

75

80

85

100

-

-

-

10

10

95

-

-

10

10

10

90

-

-

12

15

18

85

-

10

13

17

20

80

-

10

15

21

26

75

10

13

17

25

29

70

10

17

20

28

32

65

13

19

26

32

35

60

17

25

30

33

37

Ambient Condenser 

Inlet Temp (°F 

Drybulb)

Return Air Temp. (°F Drybulb)

TABLE 7

System Superheat

Содержание GPC SERIES

Страница 1: ...on TX 77092 06 06 www goodmanmfg com www amana hac com 2005 2006 Goodman Manufacturing Company L P All information contained herein is subject to change without notice INSTALLATION OPERATING INSTRUCTI...

Страница 2: ...her shipping or concealed should be filed immediately with the shipping company Check the unit model number specifications electrical characteristics and accessories to determine if they are correct I...

Страница 3: ...ntinuous operating conditions independent of any installed system EPA Regulations IMPORTANT THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY EPA HAS ISSUED VARIOUS REGULATIONS REGARDING THE INTRODUCT...

Страница 4: ...gisters are low on the wall or in the floor compressor compartment and controls The top of the unit should be completely unobstructed If units are to be located under an overhang there should be a min...

Страница 5: ...ty use an insulation with a good K factor and a vapor barrier Industry practices should be followed Balancing dampers are recommended for each branch duct in the supply system Ductwork should be prope...

Страница 6: ...o 18AWG as follows LEAD THERMOSTAT Red R 24V Green G Fan Yellow Y Cool White W1 Heat Brown W2 Heat TABLE 2 b Heat Pumps Connect 24V wires from the thermostat to the corresponding wires in the control...

Страница 7: ...ht will come on 15 If checking the unit in the wintertime when the outdoor coil is cold enough to actuate the defrost control observe at least one defrost cycle to make sure the unit defrosts complete...

Страница 8: ...herefore all the charts and data for service that apply to summer air conditioning apply to the heat pump when it is on the cooling cycle and most apply on the heating cycle except that condenser beco...

Страница 9: ...the timing period the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 75 F the defrost cycle is terminated and the timing period is reset...

Страница 10: ...the proper amount All package units are charged to the superheat method at the compressor suction line these are fixed orifice devices For charging in the warmer months 10 F superheat at the compresso...

Страница 11: ...perly SERVICE THE FOLLOWING INFORMATION IS FOR USE BY QUALIFIED SERVICE AGENCY ONLY OTHERS SHOULD NOT ATTEMPT TO SERVICE THIS EQUIPMENT Common Causes of Unsatisfactory Operation of Heat Pump on the He...

Страница 12: ...nnection a Check for unit voltage at compressor check tighten all connections b Compressor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still...

Отзывы: