background image

4

Rooftop Installation (Figure 2)

1.

Before locating the unit on the roof, make sure that the
strength of the roof and beams is adequate to support the
weight involved. (See specification sheet for weight of
units.) This is very important and the installer’s
responsibility.

2.

Make proper consideration for the weather–tight integrity
of the roof and proper drainage of condensate.

3.

Consideration should also be given to shade, appearance
and noise.

36"

36"

24"

PL

EN

UM

UN

IT

PL

AT

FO

RM

CU

RB

DUCTING

DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT
RETURN DUCTWORK TO ANY OTHER HEAT PRODUCING
DEVICES SUCH AS FIREPLACE INSERT, STOVE, ETC. UN-
AUTHORIZED USE OF SUCH DEVICES MAY RESULT IN
PROPERTY DAMAGE, FIRE, CARBON MONOXIDE POISON-
ING, EXPLOSION, PERSONAL INJURY OR DEATH.

WARNING

Ducting work should be fabricated by the installing
contractor in accordance with local codes. Industry manuals
may be used as a guide when sizing and designing the
duct system- such as NESCA (National Environmental
Systems Contractors Association, 1501 Wilson Blvd.,
Arlington, Virginia 22209).

The unit should be placed as close as possible to the space
to be air-conditioned allowing clearance dimensions as
indicated. Ducts should run as directly as possible to supply
and return outlets. Use of non-flammable weatherproof
flexible connectors on both supply and return connections
at the unit to reduce noise transmission is recommended.

It is preferable to install the unit on the roof of the structure
if the registers or diffusers are located in the wall or ceiling.
A slab installation is recommended when the registers are
low on the wall or in the floor.

compressor compartment and controls. The top of the unit
should be completely unobstructed.  If units are to be located
under an overhang, there should be a minimum of 36”
clearance and provisions made to deflect the warm discharge
air out from the overhang.

Location

Consider the affect of outdoor fan noise on conditioned space
and any adjacent occupied space. It is recommended that
the unit be placed so that condenser air discharge does
not blow toward windows less than 25 feet away.

The unit should be set on a solid, level foundation - preferably
a concrete slab at least 4 inches thick. The slab should be
above ground level and surrounded by a graveled area for
good drainage. Any slab used as a unit’s foundation should
not adjoin the building as it is possible that sound and
vibration may be transmitted to the structure. For rooftop
installation, steel or treated wood beams should be used
as unit support for load distribution.

Heat pumps require special location consideration in areas
of heavy snow accumulation and/or areas with prolonged
continuous subfreezing temperatures. Heat pump unit bases
have holes under the outdoor coil to permit drainage of defrost
water accumulation. The unit must be situated to permit
free unobstructed drainage of the defrost water and ice. A
minimum 2" clearance under the outdoor coil is required in
the milder climates.

Outside Slab Installation (Figure 1)

1. The unit must be mounted on a solid, level foundation.

2. Select a location that will minimize the length of the supply

and return ducts.

3. Select a location where external water drainage cannot collect

around the unit.

4. Consideration should also be given to shade, appearance

and noise.

36"

36"

10"

UNIT

WALL

36"

FIGURE 1

FIGURE 2

Содержание GPC SERIES

Страница 1: ...on TX 77092 06 06 www goodmanmfg com www amana hac com 2005 2006 Goodman Manufacturing Company L P All information contained herein is subject to change without notice INSTALLATION OPERATING INSTRUCTI...

Страница 2: ...her shipping or concealed should be filed immediately with the shipping company Check the unit model number specifications electrical characteristics and accessories to determine if they are correct I...

Страница 3: ...ntinuous operating conditions independent of any installed system EPA Regulations IMPORTANT THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY EPA HAS ISSUED VARIOUS REGULATIONS REGARDING THE INTRODUCT...

Страница 4: ...gisters are low on the wall or in the floor compressor compartment and controls The top of the unit should be completely unobstructed If units are to be located under an overhang there should be a min...

Страница 5: ...ty use an insulation with a good K factor and a vapor barrier Industry practices should be followed Balancing dampers are recommended for each branch duct in the supply system Ductwork should be prope...

Страница 6: ...o 18AWG as follows LEAD THERMOSTAT Red R 24V Green G Fan Yellow Y Cool White W1 Heat Brown W2 Heat TABLE 2 b Heat Pumps Connect 24V wires from the thermostat to the corresponding wires in the control...

Страница 7: ...ht will come on 15 If checking the unit in the wintertime when the outdoor coil is cold enough to actuate the defrost control observe at least one defrost cycle to make sure the unit defrosts complete...

Страница 8: ...herefore all the charts and data for service that apply to summer air conditioning apply to the heat pump when it is on the cooling cycle and most apply on the heating cycle except that condenser beco...

Страница 9: ...the timing period the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 75 F the defrost cycle is terminated and the timing period is reset...

Страница 10: ...the proper amount All package units are charged to the superheat method at the compressor suction line these are fixed orifice devices For charging in the warmer months 10 F superheat at the compresso...

Страница 11: ...perly SERVICE THE FOLLOWING INFORMATION IS FOR USE BY QUALIFIED SERVICE AGENCY ONLY OTHERS SHOULD NOT ATTEMPT TO SERVICE THIS EQUIPMENT Common Causes of Unsatisfactory Operation of Heat Pump on the He...

Страница 12: ...nnection a Check for unit voltage at compressor check tighten all connections b Compressor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still...

Отзывы: