background image

10

calls for heat.  At the end of the timing period, the unit’s
defrost cycle will be initiated provided the sensor remains
closed. When the sensor opens (approximately 75° F), the
defrost cycle is terminated and the timing period is reset. If
the defrost cycle is not terminated due to the sensor
temperature, a ten minute override interrupts the unit’s
defrost period.

C

Y

W2

R

R DFT

TEST

DF1

DF2

JUMPER WIRE

90
60
30

A

FIGURE 7

SUGGESTED FIELD TESTING/TROUBLE SHOOTING

1.

Run unit in the heating mode (room thermostat calling for
heat).

2.

Check unit for proper charge. 

Note: Bands of frost on the

condenser coil indicate low refrigerant charge.

3.

Shut off power to unit.

4.

Disconnect outdoor fan by removing the purple lead from
“DF2” on defrost control.

5.

Restart unit and allow frost to accumulate.

6.

After a few minutes of operation, the unit’s defrost
thermostat should close. To verify this, check for 24 volts
between “DFT” and  “C” on board. If the temperature at the
thermostat is less than 28° F and the thermostat is open,
replace the unit’s defrost thermostat, as it is defective.

7.

When the unit’s defrost thermostat has closed, short the
test pins on the defrost board until the reversing valve shifts,
indicating defrost.  This should take up to 21 seconds
depending on what timing period the control is set on.  After
defrost initiation, the short must instantly be removed or the
unit’s defrost period will only last 2.3 seconds.

8.

After the unit’s defrost thermostat has terminated, check
the defrost thermostat for 24 volts between “DFT” and “C”.
The reading should indicate 0 volts (open sensor).

9.

Shut off power to unit.

10. Replace outdoor fan motor lead to terminal “DF2” on defrost

board and turn on power.

AIR FLOW MEASUREMENT AND ADJUSTMENT

After reviewing section on DUCTING, proceed with airflow
measurements and adjustments.  Unit’s blower curves (in
Specification Sheets) are based on external static pressure
(ESP, in. of W.C.).  The duct openings on the unit are
considered internal static pressure, so as long as ESP is
maintained, the unit will deliver the proper air up to the
maximum static pressure listed for the CFM required by the
application (i.e. home, building, etc.)

In general 400 CFM per ton of cooling capacity is a rule of
thumb.  Some applications depending on the sensible and
latent capacity requirements may need only 350 CFM or up
to 425 CFM per ton.  Check condition space load
requirements (from load calculations) and equipment
expanded ratings data to match CFM and capacity.

Notes:

•  Data shown is dry coil. Wet coil pressure drop is approximately 0.1" H2O, for two-row indoor coil; 0.2” H2O, for three-row indoor coil; and 0.3” H2O, for four-row indoor coil.

•  Data shown does not include filter pressure drop, approx. 0.08” H

2

O.

•  ALL MODELS SHOULD RUN NO LESS THAN 350 CFM/TON. 

•  Reduce airflow by 2% for 208-volt operation.

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM

1,180

1,125

1,075

1,020

955

875

655

-

WATTS

335

325

315

305

295

275

240

-

CFM

1,350

1,280

1,205

1,130

1,050

985

910

845

WATTS

435

420

405

385

375

350

330

310

CFM

1,450

1,370

1,290

1,205

1,130

1,040

960

885

WATTS

495

480

465

440

425

400

385

370

CFM

1,860

1,800

1,745

1,695

1,650

1,600

1,555

1,500

WATTS

410

425

440

455

470

480

495

500

CFM

1,990

1,945

1,885

1,835

1,785

1,740

1,695

1,645

WATTS

510

520

530

545

555

570

585

590

CFM

2,100

2,045

1,985

1,945

1,895

1,850

1,800

1,750

WATTS

595

610

620

630

645

660

670

680

230

230

230

230

230

230

Model

Speed

Volts

E.S.P (In. of H

2

O)

G

P

H

1

3

36H

2

1

*

G

P

C

1

3

36H

2

1

*

LOW

MED

HIGH

G

P

H

1

3

60H

2

1

*

G

P

C

1

3

60H

2

1

*

"T" 1 LOW

"T" 2 MED

"T" 3 HIGH

Содержание GPC 13 SEER H Series

Страница 1: ...o system charging and start up Prior to installation thoroughly familiarize yourself with this Installation Manual Observe all safety warnings During installation or repair caution is to be observed I...

Страница 2: ...PTING TO INSTALL OR REPAIR THIS UNIT WITHOUT SUCH BACKGROUND MAY RESULT IN PRODUCT DAMAGE PERSONAL INJURY OR DEATH AT A MINIMUM INTRODUCTION Checking Product Received Upon receiving the unit inspect i...

Страница 3: ...heat pumps are designed for OUTDOOR USE ONLY This series is available in cooling Capacities of 3 and 5 nominal tons of cooling Op tional field installed heat kits are available in 5 8 10 15 and 20 KW...

Страница 4: ...application minimizes exposed wiring Close to the wall application assures free unobstructed air to the other two sides In more confined application spaces such as corners provide a minimum 10 cleara...

Страница 5: ...the collars and flanges with a proper waterproof sealant See Figure 3 It is strongly encouraged to use appropriately sized ducts based upon the CFM for your application unit s CFM If duct sizing thro...

Страница 6: ...GE DISCONNECT SWITCH LOW VOLTAGE CONNECTORS R COMMON HEAT FAN COOL W Y G THERMOSTAT SUBBASE Y G R W FOR INTERNAL WIRING SEE WIRING LABEL ATTACHED TO UNIT HIGH VOLTAGE POWER WIRING 24 VOLT CONTROL WIRI...

Страница 7: ...now be operating Allow the unit to run 10 minutes make sure cool air is being supplied by the unit 7 Turn the temperature setting to the highest position stopping the unit The indoor blower will cont...

Страница 8: ...is recommended to serve as an indication that the unit will operate normally COMPONENTS 1 Contactor This control is activated closed by the room thermostat for both heating and cooling The contactor...

Страница 9: ...refrigerant circuit external to the compressor This is accomplished with a reversing valve Thus the hot discharge vapor from the compressor is directed to the indoor coil evaporator on the cooling cy...

Страница 10: ...inal DF2 on defrost board and turn on power AIR FLOW MEASUREMENT AND ADJUSTMENT After reviewing section on DUCTING proceed with airflow measurements and adjustments Unit s blower curves in Specificati...

Страница 11: ...e adjusted to the proper amount All package units should be charged to the superheat method at the compressor suction line these are fixed orifice devices For charging in the warmer months 10 F superh...

Страница 12: ...he Heating Cycle Inadequate Air Volume Through Indoor Coil When a heat pump is in the heating cycle the indoor coil is functioning as a condenser The return air filter must always be clean and suffici...

Страница 13: ...k tighten all connections b Compressor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection...

Страница 14: ...BTD R EM FC GND LVJB PLF RCCF SA TR BLOWER INTERLOCK RELAY CONTACTOR CRANKCASE HEATER CONDENSER MOTOR COMPRESSOR ELECTRONIC BLOWER TIME DELAY RELAY EVAPORATOR MOTOR FAN CAPACITOR EQUIPMENT GROUND LOW...

Страница 15: ...OVER CURRENT PROTECTION COMPONENT LEGEND C CM COMP EM GND LVJB PLF RCCF SA TR CONTACTOR CONDENSER MOTOR COMPRESSOR EVAPORATOR MOTOR EQUIPMENT GROUND LOW VOLTAGE JUNCTION BOX FEMALE PLUG CONNECTOR RUN...

Страница 16: ...LOWER INTERLOCK RELAY CONTACTOR CRANKCASE HEATER CONDENSER MOTOR COMPRESSOR DEFROST CONTROL DEFROST THERMOSTAT ELECTRONIC BLOWER TIME DELAY RELAY EVAPORATOR MOTOR FAN CAPACITOR EQUIPMENT GROUND HIGH V...

Страница 17: ...ROTECTION COMPONENT LEGEND C CM COMP DC DFT EM GND HVDR LPS LVDR LVJB PLF RVC RCCF SA TR CONTACTOR CONDENSER MOTOR COMPRESSOR DEFROST CONTROL DEFROST THERMOSTAT EVAPORATOR MOTOR EQUIPMENT GROUND HIGH...

Страница 18: ...18 THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 19: ...19 THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 20: ...ificantly reduce the most frequent causes of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leav...

Отзывы: