Goodman GCH9 Скачать руководство пользователя страница 30

30

Orange

High

Common/Neutral

Medium Low

Circulator Blower Speeds

Low

Red

Medium Blue

Black

White

XV

XV

XV

XV

XV. NO

. NO

. NO

. NO

. NORM

RM

RM

RM

RMAL SEQUEN

AL SEQUEN

AL SEQUEN

AL SEQUEN

AL SEQUENCE O

CE O

CE O

CE O

CE OF OPERA

F OPERA

F OPERA

F OPERA

F OPERATI

TI

TI

TI

TIO

O

O

O

ON

N

N

N

N

P

OWER

 U

P

The normal power up sequence is as follows:

115 VAC power applied to furnace.

Integrated control module performs internal checks.

Integrated control module LED will light.

Integrated control module monitors safety circuits
continuously.

Furnace awaits call from thermostat.

H

EATING

 M

ODE

(M

ODE

 DIP 

SWITCH

 

IS

 

SET

 

TO

 “1 STG” 

POSITION

)

The normal operational sequence in heating mode is as follows:

R and W thermostat contacts close, initiating a call for heat.

Integrated control module performs safety circuit checks.

Induced draft blower is energized for 15 second pre-purge
period causing pressure switch contacts to close.

Igniter warm up begins after 15 second prepurge expires.

Low and high stage gas valves open at end of igniter warm
up period, delivering gas to burners and establishing flame.

Integrated control module monitors flame presence. Gas
valve will remain open only if flame is detected.

Circulator blower is energized on high heat speed following
a fixed thirty second blower on delay. Electronic air cleaner
terminals are energized with circulator blower.

Furnace operates; integrated control module monitors
safety circuits continuously.

R and W thermostat contacts open, completing the call for
heat.

Gas valve closes, extinguishing flame.

Induced draft blower is de-energized following a fifteen
second post purge.

The circulator blower remains at high heat speed for thirty
seconds. The circulator blower then switches to low heat
speed for the remainder of the selected heat off delay period.
For example, the selected heat off delay period is 150
seconds. The circulator blower operates at high heat for 30
seconds and at low speed for 150 - 30 = 120 seconds.

(M

ODE

 DIP S

WITCH

 

IS

 

SET

 

TO

 “2 STG” 

POSITION

)

The normal operational sequence in sequence is as follows:

R and W thermostat contacts close, initiating a call for heat.

Integrated control module performs safety circuit checks.

Induced draft blower is energized for 15 second prepurge
period causing pressure switch contacts to close.

Igniter warm up begins after 15 second prepurge expires.

Low and high-stage gas valves open at end of igniter warm
up period, delivering gas to burners and establishing flame.

High-stage gas valve closes after five seconds; low-stage
gas valve remains open.

Integrated control module monitors flame presence. Gas
valve will remain open only if flame is detected.

Circulator blower is energized on low heat speed following
a fixed thirty second blower on delay. Electronic air cleaner
terminals are energized with circulator blower.

Furnace is now operating in low-stage heating mode.

Furnace operates; integrated control module monitors
safety circuits continuously.

If low-stage delay period expires, control will shift operation
from low-stage heating mode operation to high-stage
heating mode operation. Control will energize circulator
blower high heat speed and high stage gas valve.

Furnace is now operating in high-stage heating mode.

R and W thermostat contacts open, completing the call for
heat.

Induced draft blower is de-energized following a fifteen
second post purge.

Circulator blower is de-energized following a heat off delay
period (selectable 100 or 150 seconds; factory set at 150
seconds).
If the furnace is operating in the low-stage heating mode
when thermostat contacts open, circulator remains at low
heat speed for the selected delay off period.
If the furnace is operating in high-stage heating mode when
the thermostat contacts open, the circulator blower remains
at high heat speed for thirty seconds. The circulator blower
then switches to low heat speed for the remainder of the
selected heat off delay period. For example, the selected
heat off delay period is 150 seconds. The circulator blower
operates at high heat for 30 seconds and at low speed for
150 - 30 = 120 seconds.

Furnace awaits the next call from thermostat.

Содержание GCH9

Страница 1: ...tall the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of common sense a matter of thinking before acting Most dealers have a list of s...

Страница 2: ...ER VENT FLUE AND COMBUSTION AIR PIPING PRACTICES 13 TERMINATION LOCATIONS 13 CANADIAN VENTING REQUIREMENTS 14 STANDARD FURNACE CONNECTIONS 14 ALTERNATE FURNACE CONNECTIONS 14 NON DIRECT VENT SINGLE PI...

Страница 3: ...XVIII Troubleshooting 32 ELECTROSTATIC DISCHARGE ESD PRECAUTIONS 32 DIAGNOSTIC CHART 32 FAULT RECALL 32 RESETTING FROM LOCKOUT 32 XIX Maintenance 32 ANNUAL INSPECTION 32 FILTERS 32 BURNERS 33 INDUCED...

Страница 4: ...warranty certificate is also supplied with the unit Read the warranty carefully and note what is covered Keep the warranty cer tificate in a safe location for future reference If additional informatio...

Страница 5: ...e Pipe Connection Alternate 15 Rubber Elbow 16 Induced Draft Blower 17 Electrical Connection Inlets Alternate 18 Coil Front Cover Pressure Tap 19 Coil Front Cover Drain Port 20 Drain Line Penetrations...

Страница 6: ...The input rate and temperature rise are set per the furnace rating plate 100 outside air is provided for combustion air requirements during construction Temporary ducting can be used II SAFETY II SAF...

Страница 7: ...ly air opening and the combustible floor Exposure to contaminated combustion air will result in safety and performance related problems Do not install the furnace where the combustion air is exposed t...

Страница 8: ...tions of use g If improper venting is observed during any of the above tests the common venting system must be corrected halogen type refrigerants cleaning solutions such as perchloroethylene printing...

Страница 9: ...ipping heavily insulated caulked vapor barrier etc addi tional air may need to be provided using the methods described in 5 3 3 b or 5 3 4 Space Unconfined For purposes of this Code a space whose volu...

Страница 10: ...directly with an additional room s of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space The total input of all gas utilization equipment installed...

Страница 11: ...ropriate in stallation positions ductwork connections and resulting airflow arrangements VII HO VII HO VII HO VII HO VII HORIZO RIZO RIZO RIZO RIZONT NT NT NT NTAL APPLI AL APPLI AL APPLI AL APPLI AL...

Страница 12: ...s require an orifice change to compensate for the energy content difference between natural and propane gas High altitude installations may require both a pressure switch and an orifice change These c...

Страница 13: ...nt flue pipe and a combustion air intake pipe Refer to the appropriate section for details concerning piping size length number of elbows furnace connections and terminations MATERIALS AND JOINING MET...

Страница 14: ...rd against inadvertent blockage COMBUSTION AIR PIPE DIRECT VENT INSTALLATIONS On upflow units secure the combustion air intake pipe directly to the air intake coupling On counterflow units secure the...

Страница 15: ...LT IN LEAKS CAUSING BODILY INJURY OR DEATH DUE TO EXPOSURE TO FLUE GASES INCLUDING CARBON MONOXIDE 7 Upflow and Counterflow units For upright installations externally mount the rubber elbow to the ven...

Страница 16: ...r of elbows in the piping system Pipe Size 4 inc 2 3 4 5 6 7 8 045_3 2 68 65 62 59 56 53 50 070_3 2 68 65 62 59 56 53 50 070_4 2 46 43 40 2 16 13 10 3 68 65 62 59 56 53 50 090_5 3 68 65 62 59 56 53 50...

Страница 17: ...ter pipe can be used in place of 2 diameter pipe 4 Increased Clearance Configurations using 2 45 deg Long Sweep elbows should be considered equivalent to one 90 deg elbow VENT FLUE AND COMBUSTION AIR...

Страница 18: ...furnace NOTE If the alternate vent flue outlet is utilized in an upright installation the drain trap and drain connections must be located on the same side as the alternate vent flue outlet In horizon...

Страница 19: ...Hose B with green hose clamps Ensure hoses and tubes maintain a downward slope for proper drainage and that they are not kinked or binding For details concerning mounting of the drain trap refer to S...

Страница 20: ...ht down side panel grommet holes Secure tubes to Hose A and Hose B using green hose clamps Ensure hoses and tubes maintain a downward slope for proper drainage and are not kinked or bound For details...

Страница 21: ...must be sized in accordance with the maximum overcurrent pro tection specified on the unit rating plate An electrical disconnect must be provided at the furnace location NOTE Line polarity must be ob...

Страница 22: ...Blower pressure switch is powered anytime the pressure switch is closed and provides 24 VAC humidifier control Remove the yellow wire and connect the supplied brown jumper wire to the pressure switch...

Страница 23: ...plying the furnace must be properly sized based on the gas flow required specific gravity of the gas and length of the run The gas line installation must comply with local codes or in their absence wi...

Страница 24: ...ctors and semi rigid tubing against physical and thermal damage when installed Ensure aluminum alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry...

Страница 25: ...ne gas leak Rust can reduce the level of odorant in propane gas Do not rely on your sense of smell Contact a local propane gas supplier about installing a gas detecting warning system If the presence...

Страница 26: ...uipped with means to prevent operation of either unit unless the damper is in the full heat or cool position When the furnace is installed without a cooling coil it is recom mended that a removable ac...

Страница 27: ...bility of flue gases escaping through the drain system FURNACE OPERATION Purge gas lines of air prior to startup Be sure not to purge lines into an enclosed burner compartment Check for leaks using an...

Страница 28: ...NT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATOR...

Страница 29: ...rtially open position 2 Place thermometers in the return and supply ducts as close to the furnace as possible Thermometers must not be influenced by radiant heat by being able to see the heat exchange...

Страница 30: ...MODE DIP SWITCH IS SET TO 2 STG POSITION The normal operational sequence in sequence is as follows R and W thermostat contacts close initiating a call for heat Integrated control module performs safet...

Страница 31: ...Y CIRCUIT DESCRIPTION XVII SAFETY CIRCUIT DESCRIPTION XVII SAFETY CIRCUIT DESCRIPTION XVII SAFETY CIRCUIT DESCRIPTION GENERAL A number of safety circuits are employed to ensure safe and proper furnace...

Страница 32: ...e least recent fault RESETTING FROM LOCKOUT Furnace lockout results when a furnace is unable to achieve igni tion after three attempts during a single call for heat It is character ized by a non funct...

Страница 33: ...AME SENSOR QUALIFIED SERVICER ONLY Under some conditions the fuel or air supply can create a nearly invisible coating on the flame sensor This coating acts as an insulator causing a drop in the flame...

Страница 34: ...E LEA RE LEA RE LEAVIN VIN VIN VIN VING AN INST G AN INST G AN INST G AN INST G AN INSTALL ALL ALL ALL ALLA A A A ATI TI TI TI TIO O O O ON N N N N Cycle the furnace with the thermostat at least three...

Страница 35: ...kage proper length elbows and termination Check drain system Correct as necessary Correct pressure switch setpoint or contact motion Tighten or correct wiring connection Pressure switch hose blocked p...

Страница 36: ...e due to improper gas pressure or combustion air Induced draft blower and circulator blower runs continuously No furnace operation Integrated control module diagnostic LED is flashing FIVE 5 flashes F...

Страница 37: ...NT COVER PRESSURE SWITCH N O C GY BK PLUG CONNECTION FIELD SPLICE SWITCH TEMP OR 24V THERMOSTAT CONNECTIONS GR GND 115 VAC 24 VAC BLOWER COMPARTMENT DOOR SWITCH OPEN WHEN DOOR OPEN DOOR SWITCH BK GND...

Отзывы: