Goodman *CSS9* Скачать руководство пользователя страница 44

44

A

IRFLOW

1.

CFM in chart is without filter(s). Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires two return filters, this chart

assumes both filters are installed.

2.

All furnaces ship as high speed cooling and medium-speed heating. Installer must adjust blower cooling & heating speed as needed.

3.

For most jobs, about 400 CFM per ton when cooling is desirable.

4.

INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.

5.

The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. The shaded area indicates

ranges in excess of maximum external static pressure allowed when heating. The data for 0.6" w.c. to 0.8" w.c. is shown for air conditioning purposes only.

6.

At higher altitudes, a properly derated unit will have approximately the same temperature rise at a particular CFM, while the ESP at that CFM will be lower.

*MSS96*** & *CSS96***A*

0.6

0.7

0.8

AC

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

CFM

CFM

CFM

HIGH

3.0

1478

N/A

1418

25

1354

26

1290

28

1208

29

1129

1040

930

MED

2.5

1299

27

1265

28

1225

29

1167

30

1112

32

1033

949

841

MED-LO

2.0

1081

33

1064

33

1039

34

997

36

945

38

886

819

722

LOW

1.5

966

37

951

37

925

38

892

40

861

41

808

750

666

HIGH

3.0

1432

37

1374

39

1319

40

1237

43

1157

46

1063

958

854

MED

2.5

1289

41

1250

43

1204

44

1142

47

1066

50

981

897

789

MED-LO

2.0

1080

49

1057

50

1022

52

980

54

926

58

861

785

700

LOW

1.5

967

55

945

56

919

58

879

61

844

63

789

712

632

HIGH

3.0

1620

44

1561

46

1478

48

1401

51

1322

54

1239

1150

1052

MED

2.5

1538

46

1476

48

1401

51

1332

53

1250

57

1166

1083

992

MED-LO

2.0

1446

49

1388

51

1333

53

1258

57

1197

59

1112

1037

937

LOW

1.5

1246

57

1217

58

1165

61

1128

63

1067

N/A

994

938

840

HIGH

4.0

1746

41

1671

43

1589

45

1516

47

1447

49

1371

1295

1160

MED

2.5

1190

60

1179

60

1151

62

1138

62

1090

65

1042

970

879

MED-LO

2.0

894

N/A

877

N/A

867

N/A

870

N/A

863

N/A

831

764

671

LOW

1.5

624

N/A

595

N/A

620

N/A

620

N/A

610

N/A

604

571

519

HIGH

5.0

2233

32

2159

33

2086

34

2024

35

1941

37

1850

1753

1651

MED

4.0

1820

39

1778

40

1742

41

1695

42

1638

43

1551

1485

1384

MED-LO

3.5

1571

45

1535

46

1497

48

1446

49

1402

51

1338

1280

1204

LOW

3.0

1361

52

1333

53

1290

55

1255

N/A

1208

N/A

1171

1104

1051

HIGH

5.0

2157

41

2087

43

2028

44

1953

46

1858

48

1775

1661

1558

MED

4.0

1907

47

1852

48

1800

49

1738

51

1675

53

1605

1514

1410

MED-LO

3.5

1608

55

1580

56

1493

60

1501

59

1440

62

1367

1296

1219

LOW

3.0

1390

N/A

1344

N/A

1326

N/A

1268

N/A

1227

N/A

1194

1132

1071

HIGH

5.0

2204

48

2144

50

2080

51

1991

54

1914

56

1817

1724

1595

MED

4.0

1938

55

1914

56

1849

58

1778

60

1713

62

1645

1548

1454

MED-LO

3.5

1651

65

1624

66

1574

68

1529

70

1475

72

1409

1331

1236

LOW

3.0

1427

75

1382

N/A

1345

N/A

1311

N/A

1272

N/A

1215

1159

1066

HIGH

3.0

1425

25

1345

26

1271

28

1198

30

1138

31

1051

945

864

MED

2.5

1254

28

1218

29

1155

31

1107

32

1040

34

952

869

761

MED-LO

2.0

1082

33

1051

34

1007

35

965

37

910

39

841

770

660

LOW

1.5

889

40

872

41

829

43

815

44

765

46

711

659

585

HIGH

3.0

1348

40

1283

42

1217

44

1151

46

1086

49

1014

931

844

MED

2.5

1188

45

1139

47

1098

49

1039

51

986

54

916

834

758

MED-LO

2.0

1015

53

985

54

945

56

909

59

858

62

804

733

655

LOW

1.5

821

65

814

N/A

788

N/A

765

N/A

720

N/A

677

640

564

HIGH

4.0

1736

41

1613

44

1578

45

1498

47

1409

50

1314

1226

1119

MED

3.5

1657

43

1583

45

1501

47

1441

49

1366

52

1282

1173

1077

MED-LO

3.0

1581

45

1510

47

1443

49

1371

52

1280

56

1199

1110

990

LOW

2.5

1369

52

1313

54

1278

56

1225

58

1147

62

1071

990

888

HIGH

5.0

2018

44

1953

46

1877

47

1788

50

1735

51

1659

1556

1448

MED

4.0

1826

49

1749

51

1660

54

1566

57

1496

59

1415

1335

1220

MED-LO

3.5

1618

55

1539

58

1476

60

1406

63

1340

66

1275

1194

1093

LOW

3.0

1402

63

1354

66

1296

69

1242

N/A

1173

N/A

1108

1042

965

HIGH

5.0

2123

50

2053

52

2000

53

1916

56

1832

58

1739

1646

1561

MED

4.0

1912

56

1844

58

1770

60

1708

62

1619

66

1543

1436

1349

MED-LO

3.5

1684

63

1622

66

1578

68

1503

71

1442

74

1374

1302

1204

LOW

3.0

1493

71

1436

74

1371

N/A

1319

N/A

1264

N/A

1208

1153

1061

0.3

0.4

0.5

0.1

0.2

*CSS960402BN

*CSS960603BN

*CSS960804CN

*CSS961005CN

*CSS961205DN

*MSS960603BN

*MSS960803BN

*MSS960804CN

*MSS960805CN

*MSS961005CN

*MSS961205DN

*MSS960402BN

Содержание *CSS9*

Страница 1: ...OF CONTENTS SAFETY CONSIDERATIONS 3 SHIPPING INSPECTION 4 ELECTROSTATIC DISCHARGE ESD PRECAUTIONS 4 TO THE INSTALLER 5 PRODUCT APPLICATION 5 LOCATION REQUIREMENTS CONSIDERATIONS 6 CLEARANCES AND ACCES...

Страница 2: ...EASUREMENT NATURAL GAS ONLY 34 TEMPERATURE RISE 34 CIRCULATOR BLOWER SPEEDS 35 BLOWER HEAT OFF DELAY TIMINGS 35 NORMAL SEQUENCE OF OPERATION 35 POWER UP 35 HEATING MODE 35 COOLING MODE 36 FAN ONLY MOD...

Страница 3: ...tion GOODMAN WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU INSTALL OR PERFORM SERVICE ON THIS UNIT YOU ASSUME RESPONSIBILITY FOR...

Страница 4: ...nente muerte DANGER PELIGRO POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOKE SOOT CONDENSATION ELECTRICAL SHOCK OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION RE...

Страница 5: ...d appliance and is appropriate for use with natural or propane gas NOTE If using propane a propane conversion kit is required Dual certification means that the combustion air inlet pipe is optional an...

Страница 6: ...urnace is heating Provide provisions for venting combustion products outdoors through a proper venting system Special consideration should begiventovent fluepiperoutingandcombustionairintakepipewhenap...

Страница 7: ...lationoveracombustiblefloorbecomesnecessary useanaccessory subbase seeSpecificationSheetapplicableforyourmodelfordetails Aspecialaccessorysubbasemustbeusedforupright counterflow unit installations ove...

Страница 8: ...any unused openings in the venting system 2 Inspect the venting system for proper size and horizontal pitch as required by the National Fuel Gas Code ANSI Z223 1 or the Natural Gas and Propane Install...

Страница 9: ...back drafting or improper combustion of gas fired appliances thereby exposing building occupants to gas combustion products that could include carbon monoxide If this furnace is to be installed in th...

Страница 10: ...cesidepanel suspendingitbelowthefurnace Aminimum clearance of 5 5 below the furnace must be provided for the drain trap Additionally the appropriate downward piping slope must be maintained from the d...

Страница 11: ...all vent flue piping and connectorsarecompatiblewithfurnaceflueproducts Additionally itistheresponsibilityoftheinstallertoensurethatallpipingand connections possess adequate structural integrity and s...

Страница 12: ...in a horizontal section of pipe as this may create a water trap PREFERRED TRANSITION NO LESS THAN 45 DEGREES TO HORIZONTAL PLANE TO AVOID CREATING A WATER TRAP IN VENT PIPING ACCEPTABLE NO TRANSITION...

Страница 13: ...e responsibility of the installer to ensure that the piping connections to the furnace are secure airtight and adequately supported Vent FluePipe The vent pipe outlet is sized to accept 2 pipe Secure...

Страница 14: ...AN RESULT IN LEAKS CAUSING BODILY INJURY OR DEATH DUE TO EXPOSURE TO FLUE GASES INCLUDING CARBON MONOXIDE WARNING ALTERNATE COMBUSTION AIR PROVISION Upflow Horizontal models only When using the altern...

Страница 15: ...ollowing figure Refer to Vent Flue Pipe and Combustion Air Pipe To secure the pipe passing through the wall and pro hibit damage to piping connections a coupling should be in stalled on either side of...

Страница 16: ...anufacturer s specifications to prevent separation and flue gas leaks Figure 11 COMBUSTION AIR INTAKE OPTIONAL Not required for single pipe installation TEE OPTIONAL 96 MAX 3 MIN ROOF LINE INTAKE SCRE...

Страница 17: ...es used in the terminations must be included when de termining the number of elbows in the piping systems If the combustion air intake pipe is to be installed above a finished ceiling or other area wh...

Страница 18: ...the Side Wall Vent Kit p n0170K00000S or 0170K000001S forinstallationspeci fications CONDENSATE DRAIN LINES DRAIN TRAP A condensing gas furnace achieves its high level of efficiency by extracting hea...

Страница 19: ...he furnace trap GENERAL DRAIN INFORMATION All furnace models come with a factory installed drain trap For vertical installations the trap will remain in the factory position except for a counterflow w...

Страница 20: ...re with 1 clamp 5 Refer to Field Supplied Drain section for instructions on field supplied installed drain on outlet of furnace trap UPFLOW MODEL INSTALLED HORIZONTALLY WITH RIGHT SIDE DOWN Minimum 5...

Страница 21: ...11 Draining the Collector Box Install the non grommet end of hose 11 from outside the cabinet in the bottom drain hole Install on collector box and secure with a silver clamp 12 Use two silver clamps...

Страница 22: ...rap 3 Draining the Collector Box From outside the cabinet insert the non grommet end hose 8 into the back drain hole 4 Secure to collector box drain port using a silver clamp 5 Draining the Vent Elbow...

Страница 23: ...NEC Class 1 and must comply with all applicable codes The furnace must be electrically grounded in accordance with local codes or in their absence with the latest edition ofThe National Electric Code...

Страница 24: ...ctrical panel NOTE Do not use gas piping as an electrical ground To confirm proper unit grounding turn off the electrical power and perform the following check 1 Measure resistance between the neutral...

Страница 25: ...areas the gas supplier may artificially derate the gas in an effort to compensate for the effects of altitude If the gas is artificially derated the appropriate orifice size must be determined based...

Страница 26: ...ld must be maintained as shipped from the factory Maximum torque for the gas valve connection is 375 in lbs excessive over tightening may damage the gas valve Install a manual shutoff valve between th...

Страница 27: ...lug in Alternate Gas Line Hole Gas Valve Burners Manual Shut Off Valve upstream from ground joint pipe union Drip Leg Grommet in Standard Gas Line Hole Ground Joint Pipe Union Ground Joint Pipe Union...

Страница 28: ...oldwithallgasappliancesinoperation Main taining proper gas pressure depends on three main factors 1 Vaporization rate depending on temperature of the liquid and wetted surface area of the container or...

Страница 29: ...ws 1 With clean filters in the furnace use a draft gauge inclined manometer to measure the static pressure of the return duct at the inlet of the furnace Negative Pressure 2 Measure the static pressur...

Страница 30: ...o avoid condensation in the heating element With a parallelflowarrangement thedampersorothermeansusedtocontrol the flow of air must be adequate to prevent chilled air from entering the furnace and if...

Страница 31: ...ter Locations Figure 37 Based on 300 ft min filter face velocity Change filters before occupants take ownership of a new home Model Minimum Filter Size MSS960402BNA 14 X 30 MSS960603BNA 20 X 25 MSS960...

Страница 32: ...n smell for gas Be sure check near the floor as some types of gas are heavier than air 7 If you smell gas after five minutes immediately follow the Safety Instructions on page 3 of this manual If you...

Страница 33: ...made by adjusting the gas valve pressure regulator The manifold pressure must be measured with the burners operating To measure and adjust the manifold pressure use the following proce dure 1 Turn OFF...

Страница 34: ...ells us that at this rate it would take 46 seconds to consume one cu ft of gas 3600 46 78 This tells us that in one hour the furnace would consume 78 cu ft of gas The typical value range for 1 cu ft o...

Страница 35: ...l terminals 4 Connect all unused blower motor leads to the PARK terminals on the integrated control module Any leads not connected to the PARK terminals must be taped 5 Turn ON power to furnace 6 Veri...

Страница 36: ...an and compressor are de energized Circulator blower continues running during a cool off delay period of 45 seconds Furnace awaits next call from thermostat FAN ONLY MODE The normal operational sequen...

Страница 37: ...ungrounded furnaces 1 Disconnectallpowertothefurnace Donottouchtheintegratedcontrolmoduleoranywireconnectedtothecontrolprior to discharging your body s electrostatic charge to ground 2 Firmly touch a...

Страница 38: ...ipesystem Checkforblockageand orleakage Check theoutsideterminationandtheconnectionsatandinternal to the furnace Heat exchanger Check for corrosion and or buildup within the heat exchanger passageways...

Страница 39: ...e burners without curling floating or lifting off Flames must not impinge on the sides of the heat exchanger firing tubes INDUCED DRAFT AND CIRCULATOR BLOWERS The bearings in the induced draft blower...

Страница 40: ...e ordered by description Parts are available from your distributor Functional Parts List Gas Valve BlowerMotor Gas Manifold BlowerWheel Natural Gas Orifice BlowerMountingBracket Propane Gas Orifice Bl...

Страница 41: ...Loose or improperly connected wiring Pressure switch circuit not closed Induced draft blower is operat ing Induced draft blower runs continuously with no further furnace operation Integrated control m...

Страница 42: ...ir Induced draft blower and circulation blower runs continuously No furnace operation Integrated control module diagnostic LED is flashing FIVE 5 flashes Flame sensed with no call for heat Correct sho...

Страница 43: ...5 1084 1005 HIGH 5 0 2284 30 2231 31 2170 31 2103 32 2037 33 1945 1836 1750 MED 4 0 1865 37 1869 36 1775 38 1732 39 1684 40 1619 1548 1480 MED LO 3 5 1594 43 1571 43 1530 45 1492 46 1454 47 1414 1355...

Страница 44: ...N A 610 N A 604 571 519 HIGH 5 0 2233 32 2159 33 2086 34 2024 35 1941 37 1850 1753 1651 MED 4 0 1820 39 1778 40 1742 41 1695 42 1638 43 1551 1485 1384 MED LO 3 5 1571 45 1535 46 1497 48 1446 49 1402...

Страница 45: ...45 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 46: ...servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death Wiring is subject to change Always refer to the wiring diag...

Страница 47: ...gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or loc...

Страница 48: ...n on Products Parts Warranties Contractor Programs and Training Customer Services Financing Options 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com www amana hac com 2014 Goodman Manufac...

Отзывы: