p
rodUCT
s
peCiFiCaTions
p
rodUCT
s
peCiFiCaTions
6 www.goodmanmfg.com
SS-CPG180-240
a
irFlow
d
aTa
—
15 T
ons
Standard Belt Drive ― Down Shot
ESP
(" H₂O)
Turns Open
0
1
2
3
4
5
6
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
0.2
0.00
6827
2.67
6394
2.28
5982
1.94
0.4
7079
3.20
6623
2.76
6161
2.34
5706
1.98
5271
1.66
0.6
6903
3.32
6405
2.83
5923
2.41
5434
2.02
4949
1.68
0.8
6717
3.42
6198
2.92
5668
2.45
5152
2.05
1.0
5975
2.99
5418
2.51
1.2
5147
2.55
High-Static Belt Drive ― Down Shot
ESP
(" H₂O)
Turns Open
0
1
2
3
4
5
6
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
1.0
6690
3.69
6008
3.02
5321
2.43
1.2
6653
3.95
5922
3.22
5182
2.58
1.4
6634
2.80
5857
3.44
5056
2.74
1.6
6638
4.55
5808
2.43
4948
2.91
1.8
6683
4.93
5784
3.95
4855
2.05
2.0
5803
4.27
4788
3.32
Notes
• Airflow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
• Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Application that exceed the above could require a
larger motor. Minimum rated SCFM is 350 per ton.
• High-static airflow requires installation of high kit (HSKT180G) or factory-built high-static model.
•
Unit factory shipped with the sheave set at 2.5 turns open.