SS-CPG180-240

r

oof

 c

urb

 i

nStallation

 — r

igging

Provisions for forks have been included in the unit base frame. No other 
fork locations are approved.
• 

Unit must be lifted by the four lifting holes located at the base frame 
corners.

•  Lifting cables should be attached to the unit with shackles.
•  The distance between the crane hook and the top of the unit must not 

be less than 60”.

•  Two spreader bars must span over the unit to prevent damage to the 

cabinet by the lift cables. Spreader bars must be of sufficient length 
so that cables do not come in contact with the unit during transport. 
Remove wood struts mounted beneath unit base frame before setting 

unit on roof curb. These struts are intended to protect unit base frame 

from fork lift damage. To remove the struts, extract the sheet metal re

-

tainers and pull the struts through the base of the unit. Refer to rigging 
label on the unit.

Important:

 If using bottom discharge with roof curb, duct-work should be 

attached to the curb prior to installing the unit. Duct-work dimensions are 
shown in Roof Curb Installation Instructions Manual.
Refer  to  the  Roof  Curb  Installation  Instructions  for 
proper curb installation. Curbing must be installed 
in compliance with the National Roofing Contractors 

Association Manual.

Lower unit carefully onto roof mounting curb. While 
rigging the unit, the center of gravity will cause the 
condenser end to be lower than  the supply air end.
Bring condenser end of unit into alignment with the 
curb. With condenser end of the unit resting on curb 
member and using curb as a fulcrum, lower opposite 

end of the unit until entire unit is seated on the curb. 

When a rectangular cantilever curb is used, take care 
to center the unit. Check for proper alignment and 
orientation of supply and return openings with duct.

To assist in determining rigging requirements, unit weights are shown to the right.

Note:

 These weights are calculated without installed accessories.

Corner & Center-of-Gravity Locations

40”

Compressor 1

R

etu

Rn

e

vapo

Ra

to

R

 C

oil

S

uppl

y

Compressor 2

58”

15-Ton Weights

20-Ton Weights

Gas

Cooler 

Gas

Cooler 

Weight A

582

590

Weight A

645

644

Weight B

475

582

Weight B

527

525

Weight C

565

492

Weight C

589

504

Weight D

461

401

Weight D

481

412

Shipping Weight

2198

2080

Shipping Weight

2357

2202

Operating Weight

2083

1965

Operating Weight

2242

2085

Содержание CPG1803503B***B Series

Страница 1: ...Three Phase Packaged Gas Electric Units Contents Nomenclature 2 Product Features 3 Product Specifications 4 Airflow Data 6 Expanded Cooling Data 8 Dimensions 12 Wiring Diagrams 16 Accessories 20 Compl...

Страница 2: ...led Op7ons 400 400 000 BTU h 025 25 kW 075 75 kW X No OpCons A Down ow Economizer Voltage Supply Fan Drive Type Motors 1 208 230 1 60 4 460 3 60 B Belt Drive 3 208 230 3 60 7 575 3 60 D Direct Drive H...

Страница 3: ...es High capacity steel cased filter dryer Built in filter rack with standard 2 filters convertible to 4 filters 24 volt terminal strip Contactor with lugs Easy to service Bottom utility entry Complies...

Страница 4: ...h 4 16 4 16 4 16 Belt Drive Evap Fan Data of Wheels D x W 2 15 x 12 2 15 x 12 2 15 x 12 Motor Sheave 1VP50 x 1 1VP50 x 1 1VP50 x 1 Blower Sheave Belt BK90 x 1 BX42 BK90 x 1 BX42 BK90 x 1 BX42 Condense...

Страница 5: ...ows Deep Fins per Inch 4 16 4 16 4 16 Belt Drive Evap Fan Data of Wheels D x W 2 15 x 15 2 15 x 15 2 15 x 15 Motor Sheave 1VP60 x 1 1VP60 x 1 1VP60 x 1 Blower Sheave Belt BK100 x BX46 BK100 x BX46 BK1...

Страница 6: ...P CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 1 0 6690 3 69 6008 3 02 5321 2 43 1 2 6653 3 95 5922 3 22 5182 2 58 1 4 6634 2 80 5857 3 44 5056 2 74 1 6 6638 4 55 5808 2 43 4948 2 91 1 8 6683 4 93...

Страница 7: ...BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 1 0 9001 6 83 8394 6 01 7797 4 78 7227 4 28 1 2 8891 6 83 8262 6 15 7632 5 35 7012 4 20 1 4 8811 6 86 8148 6 15 7495 5 48 6841 4 71 1 6 8065 6 19 7...

Страница 8: ...95 3 209 6 171 0 176 1 190 6 204 6 166 9 171 8 186 0 199 6 158 5 163 2 176 7 189 6 146 8 151 2 163 6 175 6 S T 0 81 0 72 0 55 0 35 0 84 0 75 0 57 0 37 0 86 0 77 0 58 0 37 0 89 0 79 0 60 0 39 0 92 0 82...

Страница 9: ...333 358 378 395 375 403 426 444 414 445 470 490 LO PR 100 107 116 124 106 113 123 131 110 117 128 136 116 123 134 143 121 129 141 150 125 133 146 155 85 6075 MBh 185 8 189 3 198 3 211 6 181 4 184 9 1...

Страница 10: ...60 3 279 4 228 0 234 8 254 1 272 8 222 5 229 1 247 9 266 1 211 4 217 6 235 5 252 8 195 8 201 6 218 2 234 2 S T 0 81 0 72 0 55 0 35 0 84 0 75 0 57 0 37 0 86 0 77 0 58 0 37 0 89 0 79 0 60 0 39 0 92 0 82...

Страница 11: ...98 382 412 435 453 430 463 489 510 475 512 540 563 LO PR 97 103 113 120 103 109 119 127 107 113 124 132 112 119 130 138 117 125 136 145 121 129 141 150 85 7875 MBh 247 7 252 5 264 4 282 1 241 9 246 6...

Страница 12: ...Product Specifications 12 www goodmanmfg com SS CPG180 240 Dimensions 133 88 50 5 Gas Inlet Location NPT 46 9 Flue Vent Vertical Discharge Top of Unit Supply Return 22 48 22 7 2 x 21 2 x 60...

Страница 13: ...control panel side of the unit for possible removal of fan shaft coil electric heat and gas furnace Leave a clearance of 48 on all other sides of the unit for possible compres sor removal or service a...

Страница 14: ...of Curb Installation Instructions Manual Refer to the Roof Curb Installation Instructions for proper curb installation Curbing must be installed in compliance with the National Roofing Contractors Ass...

Страница 15: ...locating and mounting the curb and package unit Duct work must be constructed using industry guidelines The duct work must be placed into the roof curb before mounting the package unit Our full perime...

Страница 16: ...WH WH WH GR GR GR RD RD RD BR BR BL BL BL PU PU PU PU PU PU PU GR BL BL BL PK BR BR BR BR BR YL YL YL YL YL YL RD RD RD RD BL BL BL BL WH WH WH WH 0140L00954 REV A OR OR OR OR 3 1 VMR 4 6 RD BK BK BK...

Страница 17: ...24V TB1 TB1 2 NOTE PLF 1 L SUPPLY VOLTAGE 208 240 3 60 2 L 3 L 1 3 1 3 1 F C C R 1 C C 3 T 1 P M O C 2 T F 1 M C M E 1 C C 1 T C 1 C C C B 2 T C B C B 3 F C C R 2 C C 3 T 1 T 2 P M O C 2 T F 3 M C 2 C...

Страница 18: ...PPROPRIATE INPUT VOLTAGE 1 24V 3 1 L2 UNUSED COOL HEAT DI FS L1 4 5 6 2 3 1 ECON 11 8 12 9 7 10 IIC LS 3 2 1 9 6 8 7 4 5 R GV W1 C Y1 Y2 G ALS PS RS GRND FS IGN W2 LPS1 LPS2 HPS1 HPS2 VMR S1 S2 TB1 TO...

Страница 19: ...IRING 0140L00957 REV A COMPONENT LEGEND Y1 Y Y2 2 F C C R F 2 M C C 2 T 1 T 3 T 3 T 1 T1 T TERMINAL BLOCK L1 TB2 4 6 S2 S1 N O I T C E T O R P T N E R R U C R E V O F O E Z I S D N A E P Y T R O F E T...

Страница 20: ...20 tons Convenience Outlet Powered All Models Convenience Outlet Non Powered All Models DNECONGS180240 Downflow Economizer 15 20 tons Electric Heat Kits HAKT36300 High Altitude Kit All Models HSKT180...

Отзывы: