Goodman ASAS-10ASC Скачать руководство пользователя страница 8

Replacing The 24 V Transformer 
(A/ GSAS-12 and A/ GSAS-18 only) 

Before replacing 24 V transformer, turn off power 

to the Air Cleaner at the source. 
1.  Remove power box cover. 
2. Disconnect the secondary leads from the 

transformer to the 24 V terminals on the power 
board. See Fig. 6. 

3.  Cut the primary leads (to the APS) close to the 

transformer. 

4.  Remove the 2 hex head nuts from the transformer 

studs. 

5. Remove 

transformer. 

6.  Place new transformer over studs and re-install 2 

hex head nuts to lock into place. 

7.  Connect secondary leads (white) to the 24 V 

terminals on the power board. 

8.  Wire nut primary leads from APS (cut in Step 3) to 

primary leads from transformer. 

9.  Replace power box cover. 
10.  Turn on power to the Air Cleaner and test. 

Testing Voltage Of Power Board 

Voltage on the power board may drop below 

required level when installation area is too damp, too 
cold, or if there is a leakage of water from a humidifier. 
Voltage on power board may be too high when 
installation area is too dry or too hot, or home is in 
close proximity to hydro towers or situated in remote 
farm land areas. By adjusting the HV ADJ 
potentiometer, the voltage can be set to optimum level. 
A high voltage meter capable of measuring 10,000 
VDC is required. To test and adjust voltage level, 
perform the following procedure: 
1.  Turn the Air Cleaner 

OFF

2.  Remove the power box cover. 
3.  Connect the ground of the high voltage meter to an 

unpainted surface in the power box. 

4. Turn 

ON

 the Air Cleaner and wait 5 minutes before 

checking voltages to allow voltages on cells to 
stabilize. 

5.  Measure the voltages at HV1 and HV2 (where 

applicable) on the power board.  See Fig. 8 

6.  Adjust the HV ADJ potentiometer until the voltage 

reading matches the voltage in Table 2. 

7. Turn 

OFF

 the Air Cleaner. 

8.  Remove the high voltage meter. 
9.  Replace the power box cover. 
10.Turn 

ON

 the Air Cleaner. 

 

 

Table 2 — Power Board Voltage Settings 

Model 

Maximum Voltages on 
Plates (K VDC) 

Maximum Voltage on 
Ionizer (K VDC) 

ASAS-10ASC, ASAS-11ASC 
GSAS-10ASC, GSAS-11ASC 

6.2 - 6.5 (HV1) 

6.2 - 6.5 (HV1) 

ASAS-12ASC, ASAS-18ASC 
GSAS-12ASC, GSAS-18ASC 

4.8 - 5.2 (HV1) 

7.2 - 7.8 (HV2) 

Fig. 8 — Testing Voltage At Power Board 

Fig. 9 — Testing Voltage At Cell 

High Voltage Probe 

Probe 

Safety Interlock 

Grounded 
Area 

Probe 

Screwdriver 

Содержание ASAS-10ASC

Страница 1: ...eria and more down to 0 01 micron Light Weight Aluminum Collecting Cells are durable and easy to maintain Cell Guides ensure proper placement of collecting cells Activated Carbon Filters remove unplea...

Страница 2: ...precautions that may apply Follow all safety codes Wear safety glasses and work gloves WHAT THE ELECTRONIC AIR CLEANER DOES Your High Efficiency Electronic Air Cleaner has been designed to remove atmo...

Страница 3: ...ng Installation Location With Humidifier A humidifier should be installed in the furnace warm air duct However it may be installed in the return duct without causing problems to the Air Cleaner Care m...

Страница 4: ...air turbulence through Air Cleaner and to increase its efficiency There should not be more than 20 of expansion used on each side of transition fitting Do not reduce ductwork to a smaller Air Cleaner...

Страница 5: ...irflow through the ducts The Air Cleaner will not run if the system fan is off For proper operation follow these simple steps 1 Run heating cooling system fan continuously and on low speed if availabl...

Страница 6: ...low Replacement Carbon Filters A GSAS 10 A GSAS 11 Set of 3 Part 1156 3 A GSAS 12 A GSAS 18 Set of 3 Part 1856 3 SERVICE Testing Air Proving Switch APS The APS sensor must protrude through the plastic...

Страница 7: ...aner at the source 1 Remove the power box cover 2 Disconnect the performance light wiring connected to the LED terminals on the power board 3 Push the light out through the front of the power box 4 Pu...

Страница 8: ...se proximity to hydro towers or situated in remote farm land areas By adjusting the HV ADJ potentiometer the voltage can be set to optimum level A high voltage meter capable of measuring 10 000 VDC is...

Страница 9: ...t Look along the top of the cell with the short still in place If there is a small arc between the cell top and copper contact then that is the bad contact Pull cell out and gently pull copper contact...

Страница 10: ...4 Using needle nose pliers place spring hook in the hole of the ionizing bar near cell top 5 Place eyelet of wire over the S hook and place S hook into hole on ionizing bar on other side of cell Keep...

Страница 11: ...icle out of cell Replace wire if necessary Ducts were not cleaned prior to installation of air cleaner Clean ducts Cell plate s are bent Remove cells and adjust to original spacing using needle nose p...

Страница 12: ...BUT NOT LIMITED TO LOSSES TO PERSONS OR PROPERTY ARISING OUT OF THE FAILURE OF THIS EQUIPMENT TO OPERATE FOR ANY REASON WHATSOEVER ARE EXCLUDED THE EXPRESSED WARRANTIES MADE IN THIS WARRANTY ARE EXCLU...

Отзывы: