Goodman ASAS-10ASC Скачать руководство пользователя страница 1

 

INSTALLATION, OPERATION AND 

SERVICE INSTRUCTIONS 

 

MODELS 

ASAS-10ASC, ASAS-11ASC, ASAS-12ASC, ASAS-18ASC 

GSAS-10ASC, GSAS-11ASC, GSAS-12ASC, GSAS-18ASC 

ELECTRONIC AIR CLEANERS 

 

IMPORTANT:  PLEASE READ MANUAL BEFORE OPERATING UNIT 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 Features

 

 

• 

Lifetime Filter System never needs replacing 

• 

Electronically removes dust, mites, pollen, pet dander, tobacco smoke, cooking smoke 
and grease, mold, fungi, bacteria, and more down to 0.01 micron 

• 

Light Weight Aluminum Collecting Cells are durable and easy to maintain 

• 

Cell Guides ensure proper placement of collecting cells 

• 

Activated Carbon Filters remove unpleasant odors 

• 

Galvanized Steel Cabinet for solid vertical or horizontal installation 

• 

Durable Scratch-Resistant powder coat paint finish resists corrosion 

• 

Electronic Air Proving Switch for quick wiring 

• 

Dual Indicator Lights show Air Cleaner is working properly at a glance 

 
 

FOR QUESTIONS REGARDING INSTALLATION, OPERATION & SERVICE, 

CALL THE AIR CLEANER HOTLINE TOLL-FREE 

1-800-267-8305 

 

Содержание ASAS-10ASC

Страница 1: ...eria and more down to 0 01 micron Light Weight Aluminum Collecting Cells are durable and easy to maintain Cell Guides ensure proper placement of collecting cells Activated Carbon Filters remove unplea...

Страница 2: ...precautions that may apply Follow all safety codes Wear safety glasses and work gloves WHAT THE ELECTRONIC AIR CLEANER DOES Your High Efficiency Electronic Air Cleaner has been designed to remove atmo...

Страница 3: ...ng Installation Location With Humidifier A humidifier should be installed in the furnace warm air duct However it may be installed in the return duct without causing problems to the Air Cleaner Care m...

Страница 4: ...air turbulence through Air Cleaner and to increase its efficiency There should not be more than 20 of expansion used on each side of transition fitting Do not reduce ductwork to a smaller Air Cleaner...

Страница 5: ...irflow through the ducts The Air Cleaner will not run if the system fan is off For proper operation follow these simple steps 1 Run heating cooling system fan continuously and on low speed if availabl...

Страница 6: ...low Replacement Carbon Filters A GSAS 10 A GSAS 11 Set of 3 Part 1156 3 A GSAS 12 A GSAS 18 Set of 3 Part 1856 3 SERVICE Testing Air Proving Switch APS The APS sensor must protrude through the plastic...

Страница 7: ...aner at the source 1 Remove the power box cover 2 Disconnect the performance light wiring connected to the LED terminals on the power board 3 Push the light out through the front of the power box 4 Pu...

Страница 8: ...se proximity to hydro towers or situated in remote farm land areas By adjusting the HV ADJ potentiometer the voltage can be set to optimum level A high voltage meter capable of measuring 10 000 VDC is...

Страница 9: ...t Look along the top of the cell with the short still in place If there is a small arc between the cell top and copper contact then that is the bad contact Pull cell out and gently pull copper contact...

Страница 10: ...4 Using needle nose pliers place spring hook in the hole of the ionizing bar near cell top 5 Place eyelet of wire over the S hook and place S hook into hole on ionizing bar on other side of cell Keep...

Страница 11: ...icle out of cell Replace wire if necessary Ducts were not cleaned prior to installation of air cleaner Clean ducts Cell plate s are bent Remove cells and adjust to original spacing using needle nose p...

Страница 12: ...BUT NOT LIMITED TO LOSSES TO PERSONS OR PROPERTY ARISING OUT OF THE FAILURE OF THIS EQUIPMENT TO OPERATE FOR ANY REASON WHATSOEVER ARE EXCLUDED THE EXPRESSED WARRANTIES MADE IN THIS WARRANTY ARE EXCLU...