26

IO-247A

     12/04

XIII. OPERATIONAL CHECKS

WARNING

T

O AVOID PERSONAL INJURY OR DEATH, DO NOT REMOVE ANY INTERNAL

COMPARTMENT COVERS OR ATTEMPT ANY ADJUSTMENT. 

E

LECTRICAL

COMPONENTS ARE CONTAINED IN BOTH COMPARTMENTS. 

T

O PREVENT

PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO EXPLOSION 

AND/OR FIRE, CONTACT A QUALIFIED SERVICE AGENT AT ONCE IF AN 

ABNORMAL FLAME APPEARS.

B

URNER

 F

LAME

The burner flames should be inspected with the burner
compartment door installed.  Flames should be stable, quiet,
soft, and blue (dust may cause orange tips but they must not be
yellow).  Flames should extend directly outward from the burners
without curling, floating, or lifting off.  Flames must not impinge on
the sides of the heat exchanger firing tubes.

Check the burner flames for: 
1. Good adjustment
2. Stable, soft and blue 
3. Not curling, floating, or lifting off. 

 Burner Flame

A

UXILIARY

 L

IMIT

 C

ONTROL

A uto reset limits are located on or near the blower. To access this
auxiliary limit, disconnect the electrical power and remove the blower
door. If the limit control opens, the air circulation blower will run
continuously. The diagnostic light will flash one time. The auxiliary
limit control is designed to prevent furnace operation in case of
main blower failure on horizontal and counterflow installations. It
may also open if the power supply is interrupted while the furnace
is firing. The auxiliary limit control is suitable for both horizontal
right and horizontal left installations. Regardless of airflow direction,
it does not need to be relocated.

P

RIMARY

 L

IMIT

The primary limit control guards against overheating resulting from
insufficient conditioned air passing over the heat exchanger.  If the
primary limit control does not function during this test, the cause
must be determined and corrected.  Function of this control should
be verified by gradually blocking the furnace return air after the
furnace has been operating (burners firing) for approximately ten
minutes.  Check the control as follows:

1. Allow the furnace to operate with burners firing continuously

for approximately ten minutes.

2. Gradually block the return air to furnace.  Remove airflow

blockage when limit control is activated and turns off burners.
Airflow blockage causes unit overheating and will produce
the following reactions:

• The gas valve to close and extinguish flame,
• The induced draft blower to be de-energized after a fifteen

second postpurge, and

• The circulator blower to remain energized continuously until

limit control resets.

3. Remove the return air blockage to clear overheating

condition.   After an acceptable temperature is reached
during the cool down period, the limit control will reset and
allow the furnace to resume normal operation.

WARNING

T

O PREVENT PREMATURE FAILURE OF HEAT EXCHANGER, PROPERTY DAMAGE,

PERSONAL INJURY OR DEATH, DO NOT ADJUST THE LIMIT CONTROL (FACTORY

SET).

XIII. SAFETY CIRCUIT DESCRIPTION

IMPORTANT NOTE:  This unit must not be used as a construction
heater during the finishing phases of construction of a new structure.
This type of use may result in premature failure due to extremely
low return air temperatures and exposure to corrosive or very dirty
atmospheres.

These checks establish that the primoary limit control is functioning
and will respond to a restriction in the return air, or a circulator
blower failure.  If the primary limit control does not function during
this test, the cause must be determined and corrected.

G

ENERAL

A number of safety circuits are employed to ensure safe and proper
furnace operation.  These circuits serve to control any potential
safety hazards and serve as inputs in the monitoring and diagnosis
of abnormal function.  These circuits are continuously monitored
during furnace operation by the integrated control module.

I

NTEGRATED

 C

ONTROL

 M

ODULE

The integrated control module is an electronic device which controls
all furnace operations.  Responding to the thermostat, the module
initiates and controls normal furnace operation, and monitors and
addresses all safety circuits.  If a potential safety concern is
detected, the module will take the necessary precautions and
provide diagnostic information through an LED.

P

RIMARY

 L

IMIT

The primary limit control is located on the partition panel and
monitors heat exchanger compartment temperatures.  It is an
automatic reset, temperature sensor.  The limit guards against the
overheating as a resulting of insufficient air passing over the heat
exchanger.

A

UXILIARY

 L

IMIT

The auxiliary limit control is located either on or near the circulator
blower and monitors heat exchanger compartment temperatures.
The control is a  temperature sensor.  It guards against overheating
resulting from insufficient air passing over the heat exchanger.

R

OLLOUT

 L

IMITS

The rollout limit controls are mounted on the burner/manifold
assembly and monitor the burner flame.  They are   manual-reset,
temperature sensors.  This limit guards against burner flames not
being properly drawn into the heat exchanger.

P

RESSURE

 S

WITCHES

The pressure switches are normally-open, negative air pressure-
activated switches.  They monitor the airflow (combustion air and
flue products) through the heat exchanger via pressure taps located
on the induced draft blower.  These switches guard against
insufficient airflow (combustion air and flue products) through the
heat exchanger.

F

LAME

 S

ENSOR

The flame sensor is a probe mounted to the burner/manifold
assembly which uses the principle of flame rectification to
determine the presence or absence of flame.

Содержание AMV8

Страница 1: ...than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of...

Страница 2: ...INSTALLATION 13 FIX 1 LINER TERMINATION 13 FIX 2 CHANGE VENTING ARRANGEMENTS 13 FIX 3 REBUILD THE CROWN 13 FIX 4 RELINING 13 VIII Electrical Connections 14 WIRING HARNESS 14 115 VOLT LINE CONNECTIONS...

Страница 3: ...7 ANNUAL INSPECTION 27 FILTERS 27 FILTER MAINTENANCE 27 FILTER REMOVAL 27 UPRIGHT FILTER REMOVAL 27 INDUCED DRAFT AND CIRCULATOR BLOWER MOTORS 28 FLAME SENSOR QUALIFIED SERVICER ONLY 28 IGNITER QUALIF...

Страница 4: ...mponent failures could result in heating system operational problems TO THE INSTALLER Before installing this unit please read this manual thoroughly to familiarize yourself with specific items which m...

Страница 5: ...uring grounding will be discharged 3 Service integrated control module or connecting wiring following the discharge process in step 2 Use caution not to recharge your body with static electricity i e...

Страница 6: ...s permitted when installed in the horizontal configuration Line contact is defined as the portion of the cabinet that is formed by the intersection of the top and side National Fire Protection Associa...

Страница 7: ...nting system are not in operation a Seal any unused openings in the venting system b Inspect the venting system for proper size and horizontal pitch as required by the National Fuel Gas Code ANSI Z223...

Страница 8: ...AM AGE PERSONAL INJURY OR DEATH SUFFICIENT FRESH AIR FO R PROPER COM BUSTION AND VENTILATION OF FLUE G ASES M UST BE SUPPLIED MO ST HOM ES REQ UIRE OUTSIDE AIR BE SUPPLIED INTO THE FURNACE AREA Improv...

Страница 9: ...input rating of all equipment in the enclosure Furnace Water Heater Chimney or Gas Vent NOTE The air duct openings must have a free area of not less than one square inch per 2000 BTU of the total inp...

Страница 10: ...W 70 4 Inch 90 4 Inch 115 N A 140 N A MODEL Under some conditions larger vents than those shown above may be required or allowed When an existing furnace is removed from a venting system serving other...

Страница 11: ...ter Water Heater Vent Connector Basement Floor F A F Vent Connector Figure 8 Typical Multiple Flue Clay Tile Chimney CHECKLIST SUMMARY This checklist serves as a summary of the items to be checked bef...

Страница 12: ...must be removed and replaced Fix 4 Next gently tap the inside of the liner with a Phillips screwdriver If the screwdriver perforates the liner or if the tapping does not sound like metal hitting metal...

Страница 13: ...acturer s instructions In some cases a shorter extension above the roof may be possible with a liner than would be required with a masonry chimney For further information on relining see Fix 4 FIX 2 C...

Страница 14: ...s that have the junction box located in the include indoor swimming pools and chlorine bleaches paint strippers adhesives paints varnishes sealers waxes which are not yet dried and solvents used durin...

Страница 15: ...switch 24 VOLT THERMOSTAT WIRING NOTE Wire routing must not interfere with circulator blower operation filter removal or routine maintenance As a two stage furnace the furnace integrated control modul...

Страница 16: ...furnace integrated control module 4 Secure the dehumidistat ground wire typically the green lead to the ground screw on the furnace junction box NOTE Ground wire may not be present on all dehumidista...

Страница 17: ...own on the rating plate Overfiring of the furnace can result in premature heat exchanger failure Gas pressures in excess of 13 inches water column can also cause permanent damage to the gas valve IMPO...

Страница 18: ...pressure switch kits PROPANE GAS CONVERSION WARNING POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH MAY OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED THE APPROPRIATE KITS MUST BE APPLIED TO...

Страница 19: ...h the left side of the furnace the installer must supply the following fittings starting from the gas valve Straight pipe to reach the exterior of the furnace A ground joint union drip leg and manual...

Страница 20: ...9 1 559 50 18 37 79 131 198 376 114 237 448 913 1 417 60 16 35 72 121 187 340 103 217 409 834 1 275 80 13 29 62 104 155 289 89 185 346 724 1 066 100 11 26 55 90 138 255 78 162 307 630 976 125 10 24 48...

Страница 21: ...waits call from thermostat NORMAL HEATING SEQUENCE R and W1 or R and W1 W2 thermostat contacts close initiating a call for heat Integrated control module performs safety circuit checks Induced draft b...

Страница 22: ...blower requires 30 seconds to ramp up to full speed Electronic air cleaner terminals are energized with circulator blower Furnace circulator blower and outdoor cooling unit run their appropriate spee...

Страница 23: ...Installation s gas heating HTG value 1 000 BTU ft3 Obtained from gas supplier Installation s seconds per cubic foot 34 sec ft3 Conversion Factor hours to seconds 3600 sec hr Input Htg value x 3600 sec...

Страница 24: ...r the cooling system Most cooling systems are designed to work with air flows between 350 and 450 CFM per ton Most manufacturers recommend an air flow of about 400 CFM per ton Example 2 5 tons X 400 C...

Страница 25: ...ormance to be optimized for the particular homeowner s needs O F F O F F 8 7 4 3 2 1 O F F O N 4 3 2 1 O N O F F 4 3 2 1 O N O N 4 3 2 1 Cooling Speed Tap A Cooling Speed Tap B Cooling Speed Tap C Coo...

Страница 26: ...ontrol will reset and allow the furnace to resume normal operation WARNING TO PREVENT PREMATURE FAILURE OF HEAT EXCHANGER PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT ADJUST THE LIMIT CONTROL FACTO...

Страница 27: ...n determining the cause XVI MAINTENANCE WARNING TO AVOID ELECTRICAL SHOCK INJURY OR DEATH DISCONNECT ELECTRICAL POWER BEFORE PERFORMING ANY MAINTENANCE IF YOU MUST HANDLE THE IGNITER HANDLE WITH CARE...

Страница 28: ...VENT PERSONAL INJURY OR DEATH DO NOT REMOVE ANY INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY ADJUSTMENT ELECTRICAL COMPONENTS ARE CONTAINED IN BOTH COMPARTMENTS CONTACT A QUALIFIED SERVICE AGENT AT ONCE...

Страница 29: ...circuit Inspect pressure switch hose Repair if necessary Inspect flue for blockage proper length elbows and termination Correct pressure switch setpoint or contact motion Tighten or correct wiring con...

Страница 30: ...spect for proper sensor alignment Check inlet air piping for blockage proper length elbows and termination Compare current gas pressure to rating plate info Adjust as needed Turn power OFF prior to re...

Страница 31: ...MIT CONTROL WIRING TO UNIT MUST BE PROPERLY ON S OME M O DE LS IN DU CTO R COI L P R ES SU R E SWI TC H LO W FIR E Y L RD BK WH IN D U CED B R GN D WH WH BK BR RD GN BU BR WH AU XI LIA RY LI M I T C O...

Страница 32: ...of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s...

Отзывы: