background image

24

IO-247A

     12/04

5. Turn ON gas and relight appliances turned off in step 1.

Ensure all the appliances are functioning properly and that
all pilot burners are operating.

T

EMPERATURE

 R

ISE

Air temperature rise is the temperature difference between supply
and return air.  The proper amount of temperature rise is usually
obtained when the unit is operated at the rated input with the “as
shipped” blower speed.  If the correct amount of temperature rise
is not obtained, it may be necessary to change the blower speed.

An incorrect temperature rise can cause condensing in or
overheating of the heat exchanger.  Determine and adjust the
temperature rise as follows.  The temperature rise must be within
the range specified on the rating plate or Product Data Book
applicable to your model*.

R IS E   = 

SUPPL Y
    AIR

RETUR N
    AIR 

HEAT EXCH ANGER

RADIATION  "LIN E OF SIG HT"

T

R E T U R N

T

S U P P LY

 

T

S U P P LY

 

T

R E T U R N

Temperature Rise Measurement

1. Operate furnace with burners firing approximately 15

minutes.  Ensure all registers are open and all duct dampers
are in their final (fully or partially open) position.

2. Place thermometers in the return and supply ducts as close

to the furnace as possible.  Thermometers must not be
influenced by radiant heat by being able to “see” the heat
exchanger.

3. Subtract the return air temperature from the supply air

temperature to determine the air temperature rise.  Allow
adequate time for thermometer readings to stabilize.

4. Adjust temperature rise by adjusting the circulator blower

speed. Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise.  Refer
to the following section for speed changing details.

C

IRCULATOR

 B

LOWER

 S

PEED

 A

DJUSTMENT

WARNING

T

O AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, TURN

OFF

 POWER TO THE FURNACE BEFORE CHANGING SPEED TAPS.

All furnaces are shipped with heating speed set at “B” and cooling
speed set at “D”. Use the following procedure to select the heating
and cooling speed needed for your unit.

Use the CFM LED (green), adjacent to the integrated control
module fuse to verify airflow quantity.  The green CFM LED

blinks once for each 100 CFM of airflow.

1. Determine the tonnage of the cooling system installed with

the furnace. If the cooling capacity is in BTU/hr divide it by
12,000 to convert capacity to TONs.

Example:

Cooling Capacity of 30,000 BTU/hr.
30,000/12,000 = 2.5 Tons

2. Determine the proper air flow for the cooling system.  Most

cooling systems are designed to work with air flows between
350 and 450 CFM per ton. Most manufacturers recommend
an air flow of about 400 CFM per ton.

Example:

 2.5 tons X 400 CFM per ton = 1000 CFM

The cooling system manufacturer’s instructions must be checked
for required air flow.  Any electronic air cleaners or other devices
may require specific air flows, consult installation instructions of
those devices for requirements.

3. Knowing the furnace model, locate the high stage cooling

air flow charts in the Product Data Book applicable to your
model* .  Look up the cooling air flow determined in step 2
and find the required cooling speed and adjustment setting.

Example:

A 70 kBtu furnace is to be installed with a 2.5
ton air conditioning system.  The air flow
needed is 1000 CFM. Using the cooling speed
chart for the 70 kBtu furnace, find the airflow
closest to 1000 CFM.  A cooling airflow of 990
CFM can be attained by setting the cooling
speed to “C” and the adjustment to “-” (minus).

NOTE:

  Continuous Fan Speed will be 56% of

high stage cooling.

4. Locate the blower speed selection DIP switches on the

integrated control module.  Select the desired “cooling”
speed tap by positioning switches 1 and 2 appropriately.
Select the desired “adjust” tap by positioning switches 3
and 4 appropriately.  Refer to the following figure for switch
positions and their corresponding taps.  Turn off power to
furnace for a minimum of 10 seconds, allowing motor to
reset and recognize new speed selection.  Turn on power
to furnace.  Verify CFM by counting the number of times the
green CFM LED blinks.

5. The multi-speed circulator blower also offers several custom

ON/OFF ramping profiles.  These ramping profiles may be
used to enhance cooling performance and increase comfort
level.  The ramping profiles are selected using DIP switches
5 and 6.  Refer to the following figure for switch positions
and their corresponding taps.  Refer to the bullet points below
for a description of each ramping profile.  Turn off power to
furnace for a minimum of 10 seconds, allowing motor to
reset and recognize the new profile selection.  Turn on power
to the furnace.  Verify profile selection by counting the green
CFM LED blinks and timing each step of the ramping profile

Profile A provides only an OFF delay of 1 minute at 100% of
the cooling demand airflow.

100% CFM  

1 min  

100% CFM  

Cooling 

Demand 

OFF OFF 

• Profile B ramps up to full cooling demand airflow by first

stepping up to 50% of the full demand for 30 seconds.  The
motor then ramps to 100% of the required airflow.  A 1 minute
OFF delay at 100% of the cooling airflow.

Содержание AMV8

Страница 1: ...than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of...

Страница 2: ...INSTALLATION 13 FIX 1 LINER TERMINATION 13 FIX 2 CHANGE VENTING ARRANGEMENTS 13 FIX 3 REBUILD THE CROWN 13 FIX 4 RELINING 13 VIII Electrical Connections 14 WIRING HARNESS 14 115 VOLT LINE CONNECTIONS...

Страница 3: ...7 ANNUAL INSPECTION 27 FILTERS 27 FILTER MAINTENANCE 27 FILTER REMOVAL 27 UPRIGHT FILTER REMOVAL 27 INDUCED DRAFT AND CIRCULATOR BLOWER MOTORS 28 FLAME SENSOR QUALIFIED SERVICER ONLY 28 IGNITER QUALIF...

Страница 4: ...mponent failures could result in heating system operational problems TO THE INSTALLER Before installing this unit please read this manual thoroughly to familiarize yourself with specific items which m...

Страница 5: ...uring grounding will be discharged 3 Service integrated control module or connecting wiring following the discharge process in step 2 Use caution not to recharge your body with static electricity i e...

Страница 6: ...s permitted when installed in the horizontal configuration Line contact is defined as the portion of the cabinet that is formed by the intersection of the top and side National Fire Protection Associa...

Страница 7: ...nting system are not in operation a Seal any unused openings in the venting system b Inspect the venting system for proper size and horizontal pitch as required by the National Fuel Gas Code ANSI Z223...

Страница 8: ...AM AGE PERSONAL INJURY OR DEATH SUFFICIENT FRESH AIR FO R PROPER COM BUSTION AND VENTILATION OF FLUE G ASES M UST BE SUPPLIED MO ST HOM ES REQ UIRE OUTSIDE AIR BE SUPPLIED INTO THE FURNACE AREA Improv...

Страница 9: ...input rating of all equipment in the enclosure Furnace Water Heater Chimney or Gas Vent NOTE The air duct openings must have a free area of not less than one square inch per 2000 BTU of the total inp...

Страница 10: ...W 70 4 Inch 90 4 Inch 115 N A 140 N A MODEL Under some conditions larger vents than those shown above may be required or allowed When an existing furnace is removed from a venting system serving other...

Страница 11: ...ter Water Heater Vent Connector Basement Floor F A F Vent Connector Figure 8 Typical Multiple Flue Clay Tile Chimney CHECKLIST SUMMARY This checklist serves as a summary of the items to be checked bef...

Страница 12: ...must be removed and replaced Fix 4 Next gently tap the inside of the liner with a Phillips screwdriver If the screwdriver perforates the liner or if the tapping does not sound like metal hitting metal...

Страница 13: ...acturer s instructions In some cases a shorter extension above the roof may be possible with a liner than would be required with a masonry chimney For further information on relining see Fix 4 FIX 2 C...

Страница 14: ...s that have the junction box located in the include indoor swimming pools and chlorine bleaches paint strippers adhesives paints varnishes sealers waxes which are not yet dried and solvents used durin...

Страница 15: ...switch 24 VOLT THERMOSTAT WIRING NOTE Wire routing must not interfere with circulator blower operation filter removal or routine maintenance As a two stage furnace the furnace integrated control modul...

Страница 16: ...furnace integrated control module 4 Secure the dehumidistat ground wire typically the green lead to the ground screw on the furnace junction box NOTE Ground wire may not be present on all dehumidista...

Страница 17: ...own on the rating plate Overfiring of the furnace can result in premature heat exchanger failure Gas pressures in excess of 13 inches water column can also cause permanent damage to the gas valve IMPO...

Страница 18: ...pressure switch kits PROPANE GAS CONVERSION WARNING POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH MAY OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED THE APPROPRIATE KITS MUST BE APPLIED TO...

Страница 19: ...h the left side of the furnace the installer must supply the following fittings starting from the gas valve Straight pipe to reach the exterior of the furnace A ground joint union drip leg and manual...

Страница 20: ...9 1 559 50 18 37 79 131 198 376 114 237 448 913 1 417 60 16 35 72 121 187 340 103 217 409 834 1 275 80 13 29 62 104 155 289 89 185 346 724 1 066 100 11 26 55 90 138 255 78 162 307 630 976 125 10 24 48...

Страница 21: ...waits call from thermostat NORMAL HEATING SEQUENCE R and W1 or R and W1 W2 thermostat contacts close initiating a call for heat Integrated control module performs safety circuit checks Induced draft b...

Страница 22: ...blower requires 30 seconds to ramp up to full speed Electronic air cleaner terminals are energized with circulator blower Furnace circulator blower and outdoor cooling unit run their appropriate spee...

Страница 23: ...Installation s gas heating HTG value 1 000 BTU ft3 Obtained from gas supplier Installation s seconds per cubic foot 34 sec ft3 Conversion Factor hours to seconds 3600 sec hr Input Htg value x 3600 sec...

Страница 24: ...r the cooling system Most cooling systems are designed to work with air flows between 350 and 450 CFM per ton Most manufacturers recommend an air flow of about 400 CFM per ton Example 2 5 tons X 400 C...

Страница 25: ...ormance to be optimized for the particular homeowner s needs O F F O F F 8 7 4 3 2 1 O F F O N 4 3 2 1 O N O F F 4 3 2 1 O N O N 4 3 2 1 Cooling Speed Tap A Cooling Speed Tap B Cooling Speed Tap C Coo...

Страница 26: ...ontrol will reset and allow the furnace to resume normal operation WARNING TO PREVENT PREMATURE FAILURE OF HEAT EXCHANGER PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT ADJUST THE LIMIT CONTROL FACTO...

Страница 27: ...n determining the cause XVI MAINTENANCE WARNING TO AVOID ELECTRICAL SHOCK INJURY OR DEATH DISCONNECT ELECTRICAL POWER BEFORE PERFORMING ANY MAINTENANCE IF YOU MUST HANDLE THE IGNITER HANDLE WITH CARE...

Страница 28: ...VENT PERSONAL INJURY OR DEATH DO NOT REMOVE ANY INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY ADJUSTMENT ELECTRICAL COMPONENTS ARE CONTAINED IN BOTH COMPARTMENTS CONTACT A QUALIFIED SERVICE AGENT AT ONCE...

Страница 29: ...circuit Inspect pressure switch hose Repair if necessary Inspect flue for blockage proper length elbows and termination Correct pressure switch setpoint or contact motion Tighten or correct wiring con...

Страница 30: ...spect for proper sensor alignment Check inlet air piping for blockage proper length elbows and termination Compare current gas pressure to rating plate info Adjust as needed Turn power OFF prior to re...

Страница 31: ...MIT CONTROL WIRING TO UNIT MUST BE PROPERLY ON S OME M O DE LS IN DU CTO R COI L P R ES SU R E SWI TC H LO W FIR E Y L RD BK WH IN D U CED B R GN D WH WH BK BR RD GN BU BR WH AU XI LIA RY LI M I T C O...

Страница 32: ...of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s...

Отзывы: