background image

SYSTEM OPERATION

11

heat. 

• 

Integrated control module performs safety circuit checks.

• 

Pressure Sensor Verification:

 The control operates 

the inducer in a manner to verify the pressure sensor 

null value and span operation are within specification. 

If the system is operating correctly, this test takes only 

a few seconds. If the system is not functioning properly, 

the control times out after a maximum 90 seconds and 

display the proper fault code.  

• 

Induced draft blower is energized for 30 second 

prepurge.

• 

Igniter warm up begins after 30 second prepurge expires.

• 

Gas valves open at end of igniter warm up period, 

delivering gas to burners and establishing flame. 

• 

Integrated control module monitors flame presence. Gas 

valve will remain open only if flame is detected. 

• 

Circulator blower is energized on high heat speed 

following a fixed 30 second blower on delay. Electronic 

air cleaner terminals are energized with circulator blower. 

• 

Furnace operates; integrated control module monitors 

safety circuits continuously. 

• 

R and W thermostat contacts open, completing the call 

for heat. 

• 

Gas valve closes, extinguishing flame. 

• 

Induced draft blower is de-energized following a thirty 

second post purge. 

• 

HUM terminal is de-energized. 

• 

Circulator blower continues running for selected heat off 

delay period factory set at 120 seconds. If required this 

can be changed in the field. 

• 

Electronic air cleaner is de-energized. 

• 

Furnace awaits the next call from thermostat. 

Cooling Mode 

The normal operational sequence in cooling mode is as 

follows: 
• 

R, Y and G thermostat contacts close, initiating a call 

for cool. 

• 

Integrated control module performs safety circuit checks. 

• 

Outdoor fan and compressor are energized. 

• 

Circulator blower is energized on cool speed following a 

fixed six second on delay. If required this can be changed 

in the field to 45 seconds. Electronic air cleaner terminals 

are energized with circulator blower. 

• 

Furnace circulator blower and outdoor cooling unit 

run, integrated control module monitors safety circuits 

continuously. 

• 

R, Y and G thermostat contacts open, completing the 

call for cool. 

• 

Outdoor fan and compressor are de-energized. 

• 

Circulator blower is de-energized following a fixed forty 

firve second cool off delay period. Electronic air cleaner 

terminals are de-energized. 

• 

Furnace awaits the next call from thermostat. 

Fan Only Mode 

The normal operational sequence in Fan Only Mode is as 

follows: 
• 

R and G thermostat contacts close, initiating a call for 

fan. 

• 

Integrated control module performs safety circuit checks. 

• 

Circulator blower is energized on low heat speed. 

Electronic air cleaner terminals are energized. 

• 

Circulator blower runs, integrated control module 

monitors safety circuits continuously. 

ID Plugs for ULN 80% Furnace

Each 80% ULN model has a unique ID Plug that needs to 

be installed into the board for your specific model number. 

The ID plug will populate the board with the correct operating 

parameters for each model and should be left in the board 

once installed.:
Please see the table below for reference. 

 

Part Number

Goodman / Amana

0130F00773

*MES800403AUAA 

0130F00765

*MES800603AUAA 

0130F00766

*MES800604BUAA 

0130F00767

*MES800804BUAA 

0130F00768

*MES800805CUAA 

ID Plug Installation

The following procedure will ensure the proper operating 

parameters are installed onto the board. Each model has a 

unique ID PLUG that needs to be installed into the board for 

your specific model number. Please see the instruction below.

1.  1. Select the appropriate ID plug for the installed 

model number from the table above.

2.  Attach the appropriate ID Plug for the installed model 

number to the control board into the blue connector 

as shown below. This will load the correct parame-

ters to the board. Failure to follow these instructions 

will result in the board not functioning.

Содержание Amana AMES80 U Series

Страница 1: ...erviced only by a qualified service technician who is familiar with the safety procedures required in the repair and who is equipped with the proper tools parts testing instruments and the appropriate...

Страница 2: ...arts testing in struments and the appropriate service manual REVIEWALL SERVICEINFORMATIONINTHEAPPROPRIATESERVICE MANUAL BEFORE BEGINNING REPAIRS OUTSIDE THE U S call 1 713 861 2500 Not a technical ass...

Страница 3: ...El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparato cuando se opera en cualquier mo...

Страница 4: ...oodman A Ini al Release V GMC B 1st Revision Con gura on M Up ow Horizontal Major Revision C Counter ow Horizontal A Ini al Release B 1st Revision S PSC Motor Nox E Constant Torque Motor Mul Speed ECM...

Страница 5: ...atural Gas S Single Speed X Low NOx U Ultra Low NOx Gas Valve M Modula ng Cabinet Width C 2 Stage A 14 S Single Stage B 17 5 C 21 AFUE D 24 5 97 97 AFUE 80 80 AFUE Maximum CFM 3 1200 CFM MBTU h 4 1600...

Страница 6: ...pplication This product is designed for NATURAL GAS ONLY This product is designed for use as a residential home gas fur nace It is not designed or certified for use in mobile home trailer or recreatio...

Страница 7: ...as piping supplying the furnace must be properly sized based on the gas flow required specific gravity of the gas and length of the run The gas line installation must comply with local codes or in the...

Страница 8: ...0 furnace with serial numbers 2003 and prior will need this ID plug to operate at High Altitude You will still need to adjust manifold pressures and CO2 as described above See the table below for the...

Страница 9: ...tified as HUM and EAC All field wiring must conform to applicable codes Connections should be made as shown below Accessory Wiring If it is necessary for the installer to supply additional line voltag...

Страница 10: ...ll cause reduced airflow For bottom return connection remove the bottom of the cabinet before setting the furnace on the raised platform or return air duct A closed return duct system must be used wit...

Страница 11: ...be changed in the field to 45 seconds Electronic air cleaner terminals are energized with circulator blower Furnace circulator blower and outdoor cooling unit run integrated control module monitors s...

Страница 12: ...RAFT AND CIRCULATION BLOWERS The bearings in the induced draft blower and circulator blower motors are permanently lubricated by the manufacturer No further lubrication is required Check motor winding...

Страница 13: ...2 164 327 655 1636 37 97 195 486 12 75 150 300 600 1500 38 23 47 95 189 474 13 69 138 277 555 1385 39 92 185 462 14 64 129 257 514 1286 40 22 45 90 180 450 15 60 120 240 480 1200 41 176 439 16 56 113...

Страница 14: ...t As the external static pressure goes up the temperature rise will also increase Consult the proper tables for tempera ture rise limitation BTU HR Calculation Example The unit being tested takes 40 s...

Страница 15: ...er Tubular Heat Exchanger Pressure Sensor Assembly Flue Pipe Connection Gas Valve Inducer Gas Manifold Assembly Grommet Burner Assembly Integrated Control Module Transformer Blower Door Interlock Swit...

Страница 16: ...tion of the same gauge or its equivalent THERMOSTAT AND WIRING DISCONNECT ALL POWER BEFORE SERVICING WARNING 1 Remove the blower compartment door to gain access to the thermostat low voltage wires loc...

Страница 17: ...eed Orange wire connected to FAN on the control board Medium Speed Black Low Speed and Brown Medium Low Speed wires connected to PARK on the control board The multi speed ECM motor requires a line vol...

Страница 18: ...Allow adequate time for thermometer readings to stabilize 4 Adjust temperature rise by adjusting the circulator blower speed Increase blower speed to reduce temperature rise Decrease blower speed to i...

Страница 19: ...ntinuity between each of the motor leads 4 Touch one probe of the ohmmeter to the motor frame ground and the other probe in turn to each lead If the windings do not test continuous or a reading is obt...

Страница 20: ...ernal to the furnace remove burner compartment door to gain access to the gas valve 2 Connect a calibrated water manometer or appropriate gas pressure gauge at either the gas valve inlet pressure tap...

Страница 21: ...es Any necessary major changes in gas flow rate should be made by changing the size of the burner orifice 5 White Rodgers 36G22 Valves a Back outlet pressure test screw inlet outlet pressure boss out...

Страница 22: ...eld until the LED is blinking in AMBER more than 10 seconds less than 15 seconds the control will execute a field test mode sequence to cycle through component operation Operation The control must be...

Страница 23: ...T MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 1 Disconnect the yellow flame sensor wire from the sensor 2 Connect a micro amp meter in ser...

Страница 24: ...TROUBLESHOOTING 24...

Страница 25: ...TROUBLESHOOTING 25...

Страница 26: ...lash the Fault Code History up to 5 fault codes from newest to oldest Fault Code Clear Function When the SW1 button is pressed and held for an extended period more than 5 seconds less than 10 seconds...

Страница 27: ...ROL INTERNAL TO 2 MANUFACTUR S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING 1 SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0 7 AMPS NOTES HI VOLTAGE FIELD HI VOLTAGE 120V LOW VOLTAGE FIELD LO...

Страница 28: ...ntact us Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page GOODMAN BRAN...

Отзывы: