29
If the combustion air intake pipe is to be installed above a finished
ceiling or other area where dripping of condensate will be objec-
tionable, insulation of the combustion air pipe may be required.
Use 1/2” thick closed cell foam insulation such as Armaflex™ or
Insultube™ where required.
V
ENT
/F
LUE
AND
C
OMBUSTION
A
IR
P
IPE
T
ERMINATIONS
The vent/flue and combustion air pipes may terminate vertically,
as through a roof, or horizontally, as through an outside wall.
Vertical pipe terminations should be as shown in the following
figure.
Refer to Vent/Flue Pipe and Combustion Pipe - Termina-
tion Locations
for details concerning location restrictions. The
penetrations through the roof must be sealed tight with proper
flashing such as is used with a plastic plumbing vent.
SCREEN
(OPTIONAL)
12" MIN. TO ROOF
OR HIGHEST ANTICIPATED
SNOW LEVEL
12" MIN.
VENT/FLUE
_____________________________________
VENT/FLUE
COMBUSTION
AIR INTAKE
SCREEN
(OPTIONAL)
12" MIN. TO ROOF
OR HIGHEST ANTICIPATED
SNOW LEVEL
12" MIN.
TEE (OPTIONAL)
Vertical Terminations (Dual Pipe)
Horizontal terminations should be as shown in the following fig-
ure. Refer to
Vent/Flue Pipe and Combustion Pipe - Termination
Location
for location restrictions. A 2 3/8” diameter wall penetra-
tion is required for 2” diameter pipe. A 3” diameter hole is required
for a 2 1/2” pipe and a 3 1/2” diameter hole is required for 3”
diameter pipe. The wall penetration should be sealed with caulk-
ing material.
90º OR 45°
ELBOW
SCREEN
(OPTIONAL)
12" MIN. TO GRADE OR
HIGHEST ANTICIPATED
SNOW LEVEL
6” MAX
10”- 24”
4” MIN
Standard Horizontal Terminations (Dual Pipe)
Vent & Combustion Air Intake Measurements for Stan-
dard Horizontal Terminations (Dual Pipe)
Center to center = 10” min / 24” max.
Vertical separation: 0” - 24”
Vent termination from wall = 8” min / 12” max.
Combustion air intake from wall = 6” max.
Vent and intake clearance to ground
or anticipated snow level = 12” min.
_____________________________________
SCREEN
(OPTIONAL)
AIR
INTAKE
90°
ELBOWS
12" MIN. ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
3” - 24”
Alternate Horizontal Vent Termination (Dual Pipe)
PRODUCT DESIGN