background image

SERVICING

40

If delayed ignition should occur, the following should be 

checked.  Furnace design makes this extremely unlikely 

unless safety controls have been by-passed or tampered 

with.  Never by-pass or alter furnace controls.

1.  Improper gas pressure - adjust to proper pressure.
2.  Improper burner positioning - burners should be in 

locating slots, level front to rear and left to right.

3.  Carry over (lighter tube or cross lighter) obstructed - 

clean.

4. 

Main burner orifice(s) deformed, or out of alignment to 

burner - replace.

CHECKING INTEGRATED IGNITION  CONTROL 

BOARDS

NOTE: Failure to earth ground the furnace, 

reversing the neutral and hot wire connection 

to the line (polarity), or a high resistance 

connection in the neutral line may cause the 

control to lockout due to failure to sense flame.

WARNING

To avoid the risk of electrical shock, wiring 

to the unit must be properly polarized and 

grounded. Disconnect power before performing 

service listed below. 

The ground wire must run from the furnace all the way back 

to the electrical panel. Proper grounding can be confirmed 

by disconnecting the electrical power and measuring 

resistance between the neutral (white) connection and the 

burner closest to the flame sensor. Resistance should be 

less than 2 ohms.

The ignition control is a combination electronic and 

electromechanical device and is not field repairable. 

Complete unit must be replaced.

WARNING

Line voltage now present 

These tests must be completed within a given time frame 

due to the operation of the ignition control. The trial for 

ignition period is 4 seconds.

The ignition control is capable of diagnosing many furnace 

failures to help in troubleshooting.  The control utilizes a 

dual, 7-segment LED display to indicate diagnostic codes.

When the control is powered up normally the light will be on 

continuously.  The display wil indicate “ON” when powered 

and in standby mode.  This can be used to test for 120 

volts and 24 volts to the control since both must be present 

for the light to be on. If this step fails, check for 120 volts 

to the control and check the transformer and its associated 

wiring. If this step is successful give the control a call for 

heat and wait five (5) seconds or until the furnace goes 

into lockout.  If the control detects a failure it will now be 

shown on the diagnostic indicator light/display. Refer to the 

Abnormal Operation section in the Sequence of Operation 

section of this manual for more detail on failure codes. 

1.  Check for 120 volts from Line 1 (Hot) to Line 2 (Neutral) 

at the ignition control. No voltage, check the door switch 

connections and wire harness for continuity.

2.  With the thermostat calling for heat, check for 24 volts 

from W to C terminal on the ignition control. No voltage. 

Check transformer, room thermostat, and wiring.  

If  you  have  24  volts  coming  off  the  transformer  but 

receive approximately 13 volts on the terminal board 

between (C) and (R), check for blown fuse.

3.  Check for 120 volts to the induced draft blower 

(low-stage) by measuring voltage between Pin 3 

and Pin 4 (on the 5-pin connector) located on circuit 

board. No voltage, check for loose connection 

in the 5-pin connector or replace ignition control. 

Check for 120 volts to the induced draft blower (high-

stage) by measuring voltage between Pin 2 and Pin 4 (on 

the 5-pin connector) located on circuit board. No voltage, 

check for loose connection in the 5-pin connector, no call 

for high stage heat or replace ignition control.

4.  If voltage is present in Steps 1 through 3 and the induced 

draft blower is operating, check for 120 volts to the ignitor 

during the preheat cycle. Measure voltage between Pin 

1 and Pin 5 (on the 5-pin connector) located on ignition 

control. No voltage, check low stage and high stage 

pressure switches or  replace the ignition control board. 

5.  After the ignitor warm-up time, begin checking for 24 

volts to the gas valve. Voltage will be present for seven 

seconds only if proof of flame has been established. 

6. 

If proof of flame was established voltage will be provided 

to the air circulation blower following the heat on delay 

period. 
a.  BEFORE replacing the ECM motor assembly or 

the end bell, first check the motor with a Goodman 

#UTT-01 UltraCheck-EZTM diaganostic tool .  If 

the motor runs with the diagnostic tool, the motor 

is good. To check the end bell, see the previous 

variable speed testing section of this manual before 

replacing the end bell. 

b.  The two-stage variable speed furnaces should have 

120 Volts at the motor at all times, even without a 

call for cooling or heating. These motors receive their 

operational signals through the 4-pin wiring harness, 

connected between the motor and integrated  control 

board.

Содержание ACVC8 CA Series AMVC8 CA Series

Страница 1: ...is possible however that during its lifetime a product may require service Products should be serviced only by a qualified service technician who is familiar with the safety procedures required in th...

Страница 2: ...s necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device continues to operate in the enclosed area Carbon monoxide emissions can be re circulated throughou...

Страница 3: ...nez pas a rejoindre votre fournisseur de gaz C N utiliser que votre main pour pousser ou tourner le commande du gaz N utilisez jamais d outils Si vous ne parvenez pas a pousser ou a tourner la command...

Страница 4: ...tion M Upflow Horizontal Major Revision C Downflow Horizontal A Initial Release K Dedicated Upflow B 1st Revision D Dedicated Downflow Nox Motor N Natural Gas V Variable Speed X Low NOx E High Efficie...

Страница 5: ...ht Induced Draft Nidec multi speed ECM motor Aluminized Steel tubular heat exchanger 115 volt silicon nitride igniter Left or right gas entry GMVC80 X GMVC800603BX AA GMVC800604BX AA GMVC800803BX AA G...

Страница 6: ...wer door For direct vent applications the cabinet opening to the junction box must be sealed air tight using either an UL approved bushing such as Heyco Liquid Tight or by applying non reactive UL app...

Страница 7: ...call Y or Y G this initial cooling call after the power is turned on will run the outdoor unit at full capacity until the call is removed Use this mode for charging If system is running low stage coo...

Страница 8: ...the algorithm records a strike against the gas furnace this strike is important when looking at the Under Target Threshold 4 Under Target Threshold 7 segment menu Utt If the furnace is able to satisfy...

Страница 9: ...920 3 6 1440 4 9 1960 1 1 440 2 4 960 3 7 1480 5 2000 1 2 480 2 5 1000 3 8 1520 5 1 2040 1 3 520 2 6 1040 3 9 1560 5 2 2080 1 4 560 2 7 1080 4 1600 5 3 2120 1 5 600 2 8 1120 4 1 1640 5 4 2160 1 6 640...

Страница 10: ...h either the right or left side panel of the furnace Thermostat wiring entrance holes are located in the blower compartment Thermostat Condensate Switch Main Control Board For gas heat only operations...

Страница 11: ...NS R C G Y 24 VAC Thermostat 1 2 C Heat Pump Optional R C Y This is the only case where setting the thermostat to heat pump mode is acceptable Non communicating Single Stage Heat Pump R C G Y Optional...

Страница 12: ...ket Use Y W G signals Thermostat has a Dehum or Configurable terminal with Dehum option Yes No Does your thermostat have a whole house Dehumidifier setting Install Dehumidistat in living space or retu...

Страница 13: ...heat or to transition back to the heat pump 115 Volt Line Connection of Electronic Air Cleaner WARNING High Voltage To avoid personal injury or death due to electrical shock disconnect electrical pow...

Страница 14: ...r connection will be required for account setup Connecting Phone Application to Furnace When in close proximity to the furnace the phone application will detect the Bluetooth Network being broadcasted...

Страница 15: ...lection the left and right switches are used to browse the main menu and option menus When the center switch is pressed in the main menu the furnace control will go to the option menu and display the...

Страница 16: ...as A06 1150 to 1249 CFM display as A12 Alarm Display If an active alarm is present the alarm code shall be reported in Status Menu starting with E and following with the appropriate two digit alarm co...

Страница 17: ...low tipping In some areas the gas supplier may artificially derate the gas in an effort to compensate for the effects of altitude If the gas is artificially derated the appropriate orifice size must b...

Страница 18: ...eturn duct at the inlet of the furnace Negative Pressure 2 Measure the static pressure of the supply duct Positive Pressure 3 The difference between the two numbers is 4 w c Example 1 0 1 2 3 Differen...

Страница 19: ...re less frequent replacement intervals Avoid using highly restrictive 1 filters which produce static pressure loss greater than 25 W C In some installations the minimum filter size required will not l...

Страница 20: ...ure tap 5 Turn ON the gas supply Follow this procedure to test the gas valve pressure at 100 firing rate Run High Fire It is recommended that the CoolCloud phone application be used for all functional...

Страница 21: ...by adjusting the circulator blower speed Increase blower speed to reduce temperature rise Decrease blower speed to increase temperature rise Refer to Startup Procedure and Adjustment Circulator Blower...

Страница 22: ...ir circulating motor will run on the high heating speed for thirty 30 seconds and then switch to the low heating speed for the remainder of the heat off delay period Circulator blower and electronic a...

Страница 23: ...shuffle your feet do not touch ungrounded objects etc If you come in contact with an ungrounded object repeat step 2 before touching control or wires 4 Discharge your body to ground before removing a...

Страница 24: ...ted by the manufacturer No further lubrication is required Check motor windings for accumulation of dust which may cause overheating Clean as necessary Flame Sensor Qualified Servicer Only Under some...

Страница 25: ...2 164 327 655 1636 37 97 195 486 12 75 150 300 600 1500 38 23 47 95 189 474 13 69 138 277 555 1385 39 92 185 462 14 64 129 257 514 1286 40 22 45 90 180 450 15 60 120 240 480 1200 41 176 439 16 56 113...

Страница 26: ...e gas valve turn downward clockwise to increase pressure and input and upward counterclockwise to decrease pressure and input A properly operating unit must have the BTU per hour input and CFM of air...

Страница 27: ...rked Transformers TRANSFORMER SECONDARY PRIMARY GND C R LINE VOLTAGE L1 HOT LINE VOLTAGE NEUTRAL METER READS 24 VOLTS METER READS 120 VOLTS GND C R N L1 GND C R N L1 READS 96 VOLTS IN PHASE READS 144...

Страница 28: ...d ignition control 6 With the blower motor in operation the voltage should be 115 volts 10 percent 7 If the reading falls below the minimum voltage check the line wire size Long runs of undersized wir...

Страница 29: ...r open door interlock switch 5 Check transformer primary voltage at incoming line voltage connections fuse splices and blower door interlock switch 6 If line voltage is available to the primary side o...

Страница 30: ...ore servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death To use the diagnostic tool perform the following steps 1...

Страница 31: ...ed from Plug End 5 Measure voltage between pins 4 and 3 Voltage should be approximately zero 6 Measure voltage between pins 5 and 3 Voltage should be the same as the supply voltage to the furnace 7 If...

Страница 32: ...inutes after removing power to allow capacitors to discharge 2 Disassemble motor as described in steps 2 through 4 above 3 Locate the 3 circuit harness from the motor Using an ohmmeter measure the res...

Страница 33: ...supply duct 3 w c total external static pressure on this system 4 w c NOTE Both readings may be taken simultaneously and read directly on the manometer if so desired If an air conditioner coil or Elec...

Страница 34: ...o so may cause property damage personal injury or death 1 Remove burner compartment door to gain access to the primary limit 2 Remove low voltage wires at limit control terminals 3 With an ohmmeter te...

Страница 35: ...Auxiliary Limit Control WARNING To avoid possible fire only reset the auxiliary limit control once If it should open a second time a qualified servicer must determine why the auxiliary limit opened be...

Страница 36: ...ls during the trial for ignition If you have 115V and the motor does not run replace the induced draft motor 6 After completing check and or replacement of induced draft motor reinstall burner compart...

Страница 37: ...s should be checked and adjusted in accordance to the type of fuel being consumed The line pressure supplied to the gas valve must be within the range specified below The supply pressure can be measur...

Страница 38: ...ltage Disconnect ALL electrical power and shut off gas supply before servicing or installing Manifold Gas Pressure Gas Rate Range Nominal Natural Gas High Stage 3 2 to 3 8 w c 3 5 w c Low Stage 1 6 to...

Страница 39: ...mpare the negative pressure to the closing point specified for the particular switch Either the switch is defective or the inducer venting system is inadequate OPEN TO ATMOSPHERE HOSE TO INDUCED DRAFT...

Страница 40: ...out If the control detects a failure it will now be shown on the diagnostic indicator light display Refer to the Abnormal Operation section in the Sequence of Operation section of this manual for more...

Страница 41: ...nd the sensor terminal 3 Be sure the positive side of the meter is to the flame sensor wire and the negative side of the meter is to sensor terminal WARNING Line voltage now present 4 Place the unit i...

Страница 42: ...ment 2 Segment 3 Idle I d L Constant Fan Compressor Cooling Low Stage I Compressor Cooling High Stage Compressor Cooling Single Stage Compressor Heat Low Stage I Compressor Heat High Stage Compressor...

Страница 43: ...Switch Open E d Condensate Switch Open E Grounding Fault E 0 Rollout Switch Open E Redundant Relay Open E Redundant Relay Stuck Closed E d d d d d Status Seven Segment Display Alarm Code Definition Ta...

Страница 44: ...s Heat Name 7 Segment Display Cloud Phone App Idle IdL Idle Constant Fan Constant Fan Compressor Cooling Low Stage Compressor Cooling Low Stage Compressor Cooling High Stage Compressor Cooling High St...

Страница 45: ...humidifier enabling options in different operation modes Ventilation On Time Adjustable between 0 60 minutes The default is 0 minute Off Adjusts the ventilation on time and turn it on off DeHum Logic...

Страница 46: ...12 15 Trims the cooling airflow by the selected amount Cool Trim Factor Low L 15 12 9 6 3 0 3 6 9 12 15 Trims the cooling airflow by the selected amount Cool Airflow Profile A B C D Select cooling air...

Страница 47: ...shorts in 115 circuit Repair as necessary Replace non functional integrated control module Turn pow er OFF prior to repair Read precautions in Electrostatic Discharge section of manual Replace control...

Страница 48: ...if necessary Turn pow er OFF prior to repair Replace igniter w ith correct replacement part Replace control w ith correct replacement part Replace high stage pressure sw itch Repair short in w iring...

Страница 49: ...orrect burner alignment Check correct restriction Turn pow er off prior to service Furnace fails to operate Integrated control module LED display provides error code Data not yet on netw ork o t r o i...

Страница 50: ...ared data set is correct for the specifc model Re populate data using correct memory card if required Turn pow er OFF prior to repair Replace motor w ith correct replacement part Use memory card for t...

Страница 51: ...ol module LED display provides error code Airflow is low er than demanded Blocked filters Restrictive ductw ork Undersized ductw ork Check integrated control module Verify control is populated w ith c...

Страница 52: ...UST BE PERMANENTLY GROUNDED AND CONFORM TO N E C AND LOCAL CODES COLOR CODES 1 SWITCH PRESSURE LOW FIRE SENSOR FLAME GN GREEN GR PRESSURE SWITCH FRONT COVER C VAC TO UNIT MUST BE 1 BL RD AND GROUNDED...

Страница 53: ...ntact us Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page GOODMAN BRAN...

Отзывы: