If an air conditioning coil is installed with the furnace, a
common drain may be used.  An open tee must be
installed in the drain line, near the cooling coil, to relieve
positive air pressure from the coil’s plenum.  This is
necessary to prohibit any interference with the function of
the furnace’s drain trap.

NOTE:

 In vertical installations, air conditioning coil condensate may

drain into the furnace trap as long as there is a trap between the coil and
the furnace trap and the drain pipe is not terminating below the water
level of the furnace trap.

S

TANDARD

 R

IGHT

 

OR

 L

EFT

 S

IDE

 D

RAIN

 H

OSE

 C

ONNECTIONS

All installations positions require the use of the drain trap, hoses,  tubes,
and clamps. The following quantity of hoses, tubes, and hose clamps
are provided with the unit.

DRAIN TRAP
QTY: 1

GREEN
HOSE CLAMPS
QTY: 3

SILVER
HOSE CLAMP
QTY: 1

TUBE 2
QTY: 2

TUBE 1
QTY: 1

HOSE B
QTY: 1

HOSE A
QTY: 1

RED
HOSE CLAMP
QTY: 1

Hose and Tube Identification

In a upright installation drain hoses are connected to drain ports on the
rubber elbow and the recuperator coil front cover. The drain lines are
then routed through the right side panel and into the drain trap secured
to the outside of the cabinet.

NOTE:

Refer to 

Alternate Vent/Flue Hose Connections

 for upright

installations using an alternate vent/flue outlet.

1. Remove the rubber plug from the right side of the front cover

drain port.

2. Secure Hose A to front cover drain port with a red hose

clamp. Route hose to rear side panel grommet hole.

3. Cut and remove 1/4 inch from the end of the drain port on

the rubber elbow.

4. Insert Tube 1 into rubber elbow drain port and secure with

silver hose clamp.  Angle tube outward toward front of
furnace.

5.

Cut 17 3/4 inches from the long end of Hose B and discard.
Secure the remaining hose to Tube 1 with a green hose
clamp.  Route the other end of Hose B to  front right side
panel grommet hole.

For details concerning mounting of the drain trap, refer to 

Vertical

Drain Trap Mounting.

6. Insert short end of each of tube 2 through side panel

grommet holes. Secure tubes to hoses A and B with green
hose clamps. Ensure hoses and tubes maintain a
downward slope for proper drainage and that they are not
kinked or binding.

DRAIN
TRAP

FRONT

COVER

DRAIN PORT

TUBE(S) 2

GREEN

HOSE

CLAMPS

(3 PLACES)

RIGHT SIDE

PANEL

RUBBER ELBOW 

DRAIN PORT

TUBE 1

SIDE PANEL

GROMMET

HOLES

HOSE

B

HOSE

 A

RUBBER

ELBOW

RED HOSE

CLAMP

SILVER HOSE CLAMP

Upright “Standard” Connections -Right Side

(Upflow Shown, Counterflow Similar)

Содержание ACSH96

Страница 1: ...nking before acting Most dealers have a list of specific good safety practices follow them The precautions listed in this Installation Manual are intended as supplemental to existing practices However...

Страница 2: ...MENTS 16 STANDARD FURNACE CONNECTIONS 16 ALTERNATE FURNACE CONNECTIONS 17 NON DIRECT VENT SINGLE PIPE PIPING 18 DIRECT VENT DUAL PIPE PIPING 19 VENT INTAKE TERMINATIONS FOR INSTALLATION OF MULTIPLE DI...

Страница 3: ...OWER UP 37 HEATING MODE 37 MODE DIP SWITCH IS SET TO 1 STG POSITION 37 MODE DIP SWITCH IS SET TO 2 STG POSITION 38 COOLING MODE 38 FAN ONLY MODE 38 XVI Operational Checks 38 BURNER FLAME 38 XVII Safet...

Страница 4: ...ed throughout the structure if the furnace or air handler is operating in any mode CO can cause serious illness including permanent brain damage or death B10259 216 TO THE INSTALLER Before installing...

Страница 5: ...Electrical Connection Inlets Alternate 18 Coil Front Cover Pressure Tap 19 Coil Front Cover Drain Port 20 Drain Line Penetrations 21 Drain Trap 22 Blower Door Interlock Switch 23 Capacitor 24 Integra...

Страница 6: ...verted to operate on L P gas by using the appropriate L P conver sion kit listed in the PROPANE GAS HIGH ALTITUDE INSTALLA TIONS section of this manual Install this furnace only in a location and posi...

Страница 7: ...TO SHUT OFF TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY WARNING POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOK...

Страница 8: ...eaning solutions such as perchloroethylene printing inks paint removers varnishes hydrochloric acid cements and glues antistatic fabric softeners for clothes dryers and masonry acid washing materials...

Страница 9: ...latest edition of the National Fuel Gas Code NFPA 54 ANSI Z223 1 and or CSA B149 1 05 1 05 Installation Codes Seal off a non direct vent furnace if it is installed near an area frequently contaminated...

Страница 10: ...part of the unconfined space 5 3 3 Equipment Located in Confined Spaces a All Air from Inside the Building The confined space shall be pro vided with two permanent openings communicating directly wit...

Страница 11: ...Water Heater Outlet Air Chimney or Gas Vent NOTE The inlet and outlet air openings must each have a free area of not less than one square inch per 4000 BTU of the total input rating of all equipment i...

Страница 12: ...ions Refer to Recommended Installation Positions figure for appropriate in stallation positions ductwork connections and resulting airflow arrangements VII HORIZONTALAPPLICATIONS CONSIDERATIONS GENERA...

Страница 13: ...The indicated kits must be used to insure safe and proper furnace operation All conversions must be performed by a qualified installer or service agency AIR DISCHARGE AIR DISCHARGE AIR DISCHARGE Bott...

Страница 14: ...G Clearance to inside corner H Clearance to each side of center line extended above meter regulator assembly 3 ft 91 cm within a height 15 ft 4 5 m above the meter regulator assembly OTHER THAN DIRECT...

Страница 15: ...d Fittings must be DWV type fit tings meeting ASTM D2665 and ASTM D3311 Carefully follow the manufactures instructions for cutting cleaning and solvent cement ing of PVC In addition to PVC and ABS pip...

Страница 16: ...insulated and closed with a weather tight corrosion resistant flashing STANDARD FURNACE CONNECTIONS It is the responsibility of the installer to ensure that the piping con nections to the furnace are...

Страница 17: ...ELBOW NON DIRECT VENT 90 PVC ELBOW NON DIRECT VENT STANDARD CONNECTIONS OR OR UPFLOW COUNTERFLOW ALTERNATE FURNACE CONNECTIONS If the standard locations are undesirable for a specific installation al...

Страница 18: ...105 98 91 84 Not Applicable Not Applicable MH95 ACSH96 AMEH96 GCH95 GME95 Direct Vent 2 Pipe and Non Direct Vent 1 Pipe 6 Maximum Allowable Length of Vent Flue Pipe Combustion Air Pipe ft 1 2 Unit Inp...

Страница 19: ...ameter for construction of the vent flue and combustion air intake pipe systems of a direct vent dual pipe installation The number of elbows tabulated represents the number of elbows and or tees in ea...

Страница 20: ...e outside the structure and may be installed with the intake and exhaust pipes located side by side or with one pipe above the other This kit is NOT intended for use with single pipe indirect vent ins...

Страница 21: ...trap secured to the outside of the cabinet NOTE Refer to Alternate Vent Flue Hose Connections for upright installations using an alternate vent flue outlet 1 Remove the rubber plug from the right side...

Страница 22: ...ber elbow Discard cut portion 5 Insert Tube 1 into rubber elbow drain port and secure with a silver hose clamp Angle tube toward trap 6 Cut 17 3 4 inches from the long end of Hose B and discard 7 Secu...

Страница 23: ...mp Angle tube outward toward front of furnace 5 Cut X inches from the long end of Hose B and discard Refer to table for appropriate length to cut Secure remaining hose to Tube 1 with a green hose clam...

Страница 24: ...ked drain conditions Cut hose to appropriate length to minimize sagging Plug left unused pressure tap with plug removed from right side 2 Secure HoseA to front cover drain tap with a red hose clamp Ro...

Страница 25: ...a hose to the induced draft blower housing 6 Cut 5 1 2 inches straight length from the long end of each Tube 2 and discard radius ends 7 Insert approximately one inch of each Tube 2 through left side...

Страница 26: ...blower door For direct vent applica tions the cabinet opening to the junction box must be sealed air tight using either a UL approved bushing such as Heyco Liquid Tight or by applying a UL approved no...

Страница 27: ...ire routing must not to interfere with circulator blower operation filter removal or routine maintenance Refer to the follow ing figure for thermostat connections to the integrated control module term...

Страница 28: ...n specified on the furnace rating plate The combination of the lower air density and a lower manifold pressure will prohibit the burner orifice from drawing the proper amount of air into the burner Th...

Страница 29: ...m of three inches long Install a 1 8 NPT pipe plug fitting accessible for test gauge connection immediately upstream of the gas supply connection to the furnace Always use a back up wrench when making...

Страница 30: ...ch pipe fittings starting from the gas valve to reach the outside of the cabinet must be supplied 1 Close nipple 1 90 degree street elbow 1 2 1 2 pipe nipple 1 90 degree elbow Straight Pipe The straig...

Страница 31: ...vert to capacities at 5 psig settings multiply by 0 879 Propane Gas Piping Chart I Sizing Between Single or Second Stage Regulator and Appliance Maximum Propane Capacities Listed are Based on 1 2 W C...

Страница 32: ...s retaining the sheet metal over the duct opening Using tin snips cut the metal strips and remove the sheet metal to free the duct flanges Using the scribe line along the duct flange as a guide unfold...

Страница 33: ...e HORIZONTAL INSTALLATIONS Filters must be installed in either the central return register or in the return air duct work XIV STARTUP PROCEDURE ADJUSTMENT Furnace must have a 115 VAC power supply prop...

Страница 34: ...OR EQUIPMENT DAMAGE THE INLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING CAUTION The line pressure supplied to the gas va...

Страница 35: ...ach a hose and manometer to the outlet pressure barb fitting Honeywell valve or outlet pressure tap White Rodgers valve 5 Turn ON the gas supply 6 Turn on power and close thermostat R and W1 contacts...

Страница 36: ...hermometer readings to stabilize 4 Adjust temperature rise by adjusting the circulator blower speed Increase blower speed to reduce temperature rise Decrease blower speed to increase temperature rise...

Страница 37: ...to 12 minutes NOTE The ACSH AMH AMEH GCH GDH GMH and GME hybrid furnaces require a single stage thermostat These furnaces utilize a control board with single stage or two stage capability The second s...

Страница 38: ...ws R and Y thermostat contacts close initiating a call for cool Integrated control module performs safety circuit checks Outdoor fan and compressor are energized Circulator blower is energized on cool...

Страница 39: ...mly touch a clean unpainted metal surface of the furnaces near the control Any tools held in a person s hand during grounding will be discharged 3 Service integrated control module or connecting wirin...

Страница 40: ...emove 1 Turn OFF electrical power to furnace 2 Remove filter s from the central return register or ductwork 3 Replace filter s by reversing the procedure for removal 4 Turn ON electrical power to furn...

Страница 41: ...nal problem Perform the checks listed in Section XIV Startup Procedure andAdjustments to reduce the chances of repeated fouling XX BEFORE LEAVING AN INSTALLATION Cycle the furnace with the thermostat...

Страница 42: ...kage proper length elbows and termination Check drain system Correct as necessary Correct pressure switch setpoint or contact motion Tighten or correct wiring connection Pressure switch hose blocked p...

Страница 43: ...e and air inlet piping for blockage proper length elbows and termination Correct as necessary Check rollout limit Replace if necessary Check induced draft blower for proper performance Replace if nece...

Страница 44: ...4 793 MED HI MED LO 2 0 981 61 962 62 943 63 917 65 888 67 830 764 665 LOW 1 5 750 79 730 81 714 83 692 86 657 90 620 570 502 HIGH 4 0 2069 29 1965 30 1871 32 1756 34 1661 36 1549 1415 1275 MH950704CX...

Страница 45: ...9 534 HIGH 3 0 1431 42 1368 44 1296 47 1228 49 1150 53 1055 962 860 ACSH960703BX MED 2 5 1212 50 1182 51 1138 53 1091 55 1019 59 944 871 769 MED HI MED LO 2 0 1002 60 978 62 956 63 921 66 878 69 825 7...

Страница 46: ...039 34 998 35 959 37 923 882 839 T4 BLUE 3 0 1274 28 1239 28 1199 29 1166 30 1129 31 1096 1059 1021 T5 BLACK 3 0 1306 27 1261 28 1232 29 1195 29 1162 30 1132 1090 1057 T1 YELLOW 1 5 714 80 667 79 604...

Страница 47: ...682 619 534 HIGH 3 0 1431 42 1368 44 1296 47 1228 49 1150 53 1055 962 860 GCH950703BX MED 2 5 1212 50 1182 51 1138 53 1091 55 1019 59 944 871 769 MED HI MED LO 2 0 1002 60 978 62 956 63 921 66 878 69...

Страница 48: ...039 34 998 35 959 37 923 882 839 T4 BLUE 3 0 1274 28 1239 28 1199 29 1166 30 1129 31 1096 1059 1021 T5 BLACK 3 0 1306 27 1261 28 1232 29 1195 29 1162 30 1132 1090 1057 T1 YELLOW 1 5 714 80 667 79 604...

Страница 49: ...DOOR OPEN DOOR SWITCH WARNING DISCONNECT POWER BEFORE SERVICING WIRING TO UNIT MUST BE PROPERLY POLARIZED AND GROUNDED BK GND DISCONNECT L POWER SUPPLY WITH OVERCURRENT PROTECTION DEVICE WH JUNCTION B...

Страница 50: ...the unit for the most up to date wiring HIGH VOLTAGE D ISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT M ULTIPLE POWER SOURCES MAY BE PRESENT F AILURE TO DO SO MAY CAUSE PROPERTY DAMAGE...

Страница 51: ...the wiring diagram on the unit for the most up to date wiring HIGH VOLTAGE D ISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT M ULTIPLE POWER SOURCES MAY BE PRESENT F AILURE TO DO SO MAY C...

Страница 52: ...t vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL...

Страница 53: ...53 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 54: ...54 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 55: ...55 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 56: ...forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s No Better Quality Visit our web sites at www goodm...

Отзывы: