4.0 Heating Operation

On heat pump units, when the room thermostat set to the
heating mode, the reversing valve is not energized.  As long
as the thermostat is set for heating, the reversing valve will be
in the de-energized position for heating except during a
defrost cycle.  Some installations may use one or more
outdoor thermostats to restrict the amount of electric heat
that is available above a preset ambient temperature.  Use of
optional controls such as these can change the operation of
the electric heaters during the heating mode.  This sequence
of operation does not cover those applications.

4.1

 On a demand for first stage heat with heat pump units, the

room thermostat energizes “G” and “Y” and 24Vac is
supplied to “Y” at the heat pump unit and the “G” terminal
on the EBTDR board.  The heat pump is turned on in the
heating mode and the blower motor starts after a 7 second
on delay.

4.2

 If the first stage heat demand cannot be satisfied by the

heat pump, the temperature indoors will continue to drop.
The room thermostat will then energize terminal “W2’ for
second stage heat and 24Vac will be supplied to heat
sequencer HR1 on the heater assembly.

4.3

 HR1 contacts M1 and M2 will close will close within 10

to 20 seconds and turn on heater element #1.  At the
same time, if the heater assembly contains a second
heater element, HR1 will contain a second set of con-
tacts, M3 and M4, which will close and turn on heater
element #2.  The blower motor is already on as a result
of terminal “G” on the EBTDR board being energized for
the first stage heat demand.

Note:

 If more than two heater elements are on the heater

assembly, it will contain a second heat sequencer, HR2,
which will control the 3

rd

 and 4

th

 heater elements if available.

If the second stage heat demand, “W2” cannot be satisfied by
the heat pump, the temperature indoors will continue to drop.
The room thermostat will then energize “W3” and 24Vac will
be supplied to HR2 on the heater assembly.  When the “W3”
demand is satisfied, the room thermostat will remove the
24Vac from HR2.  The contacts on HR2 will open between 30
to 70 seconds and heater elements #3 and #4 will be turned
off.  

On most digital/electronic thermostats, “W3” will

remain energized until the first stage heat demand “Y”
is satisfied and then the “G”, “Y”, “W2” and “W3”
demands will be removed.

4.4

 As the temperature indoors increase, it will reach a point

where the second stage heat demand, “W2”, is satisfied.
When this happens, the room thermostat will remove the
24Vac from the coil of HR1.  The contacts on HR1 will
open between 30 to 70 seconds and turn off both heater
element(s).  The heat pump remains on along with the
blower motor because the “Y” demand for first stage heat
will still be present.

4.5 

When the first stage heat demand “Y” is satisfied, the

room thermostat will remove the 24Vac from “G” and “Y”.
The heat pump is turned off and the blower motor turns off
after a 65 second off delay.

5.0 Defrost Operation

On heat pump units, when the room thermostat is set to the
heating mode, the reversing valve is not energized.  As long
as the thermostat is set for heating, the reversing valve will be
in the de-energized position for heating except during a
defrost cycle.

5.1

 The heat pump will be on and operating in the heating

mode as described the Heating Operation in section 4.

 5.2 The defrost control in the heat pump unit checks to see

if a defrost is needed every 30, 60 or 90 minutes of heat
pump operation depending on the selectable setting by
monitoring the state of the defrost thermostat attached to
the outdoor coil.

5.3 If the temperature of the outdoor coil is low enough to

cause the defrost thermostat to be closed when the
defrost board checks it, the board will initiate a defrost
cycle.

5.4 When a defrost cycle is initiated, the contacts of the

HVDR relay on the defrost board open and turns off the
outdoor fan.  The contacts of the LVDR relay on the
defrost board closes and supplies 24Vac to “O” and “W2”.
The reversing valve is energized and the contacts on HR1
close and turns on the electric heater(s).  The unit will
continue to run in this mode until the defrost cycle is
completed.

5.5 When the temperature of the outdoor coil rises high

enough to causes the defrost thermostat to open, the
defrost cycle will be terminated.  If at the end of the
programmed 10 minute override time the defrost thermo-
stat is still closed, the defrost board will automatically
terminate the defrost cycle.

5.6 When the defrost cycle is terminated, the contacts of the

HVDR relay will close to start the outdoor fan and the
contacts of the LVDR relay will open and turn off the
reversing valve and electric heater(s).  The unit will now be
back in a normal heating mode with a heat pump demand
for heating as described in the Heating Operation in
section 4.

S-41 AEP* & MBE WITH SINGLE STAGE CON-

DENSERS

 

AEP* & MBE ELECTRONIC BLOWER TIME DELAY RELAY

SEQUENCE OF OPERATION

This document covers the basic sequence of operation for a
typical application with a mercury bulb thermostat.  When a
digital/electronic thermostat is used, the on/off staging of the
auxiliary heat will vary.  Refer to the installation instructions
and wiring diagrams provided with the MBE for specific wiring
connections, dip switch settings and system configuration.

Содержание ACNF****16AA

Страница 1: ...ity for property damage or personal injury due to improper service procedures or services performed by an unqualified person Split System Air Conditioners Split System Heat Pumps with R 22 Refrigerant...

Страница 2: ...ou assume responsibility for any personal injury or property damage which may result WARNING This unit should not be connected to or used in conjunction with any devices that are not design certified...

Страница 3: ...e vaporous and liquid contents of the compressor housing and system Aventingcompressorterminalnormallypresentsnodanger toanyone providingtheterminalprotectivecoverisproperly in place If however the te...

Страница 4: ...or 0131M00061 GSC130481AG Goodman Brand Split Condenser 13 Seer condensing units Introduces new models with Bristol compressors GSC130181BA Goodman Brand Split Condenser 13 Seer condensing units Conve...

Страница 5: ...ls using 3 8 diameter tube coils to 5 mm coils Model Description ASC130 1AA Amana Brand Split Condenser 13 Seer condensing units Initial release new models of Amana Brand Deluxe 13 Seer AC R 22 condit...

Страница 6: ...duces models that contain the broad ocean motor GSH13018 301BA Goodman Brand Split Heat Pump 13 Seer heat pump units Reduction in chassis size from medium to small GSH130421AE Goodman Brand Split Heat...

Страница 7: ...s New revisions have screw locations moved in the top panel base pans louvers and control box covers ASH130 1AC Amana Brand Split Heat Pump 13 Seer heat pump units New revisions have horizontal style...

Страница 8: ...or Painted Flowrater Revision replaces the current spot welded blower housing with the same cinched or crimped design used on the 80 furnace line ARPF486016AB A Single Piece R Multi Position PSC Motor...

Страница 9: ...wavy fin with louver enhanced fin on coil AWUF 1AA A Single Piece Air Handler Wall Mount Unpainted Flowrator Introduces 13 SEER Dayton wall mount air handlers AWUF 16AA A Single Piece Air Handler Wall...

Страница 10: ...AUF36 CA C Indoor Coil A Upflow Downflow Painted or Uncased Flowrator Revision redesigns for performance improvement from 2 row to 3 row CHPF 6AA C Indoor Coil Horizontal A Coil Painted Flowrator Rele...

Страница 11: ...ons 030 2 5 Tons 070 5 Tons 036 3 Tons 090 7 5 Tons 042 3 5 Tons 120 10 Tons G S C 14 036 1 A A UNIT TYPE C Condenser R 22 H Heat Pump R 22 PRODUCT CATEGORY S Split System SEER 10 10 SEER 13 13 SEER 1...

Страница 12: ...5 Tons 048 4 Tons 024 2 Tons 060 5 Tons 030 2 5 Tons 070 5 Tons 036 3 Tons 090 7 5 Tons 042 3 5 Tons 120 10 Tons C KL 036 2 A PRODUCT CATEGORY C Split System UNIT TYPE E Commercial Air Conditioner K A...

Страница 13: ...Cooling 5 kw Electric Heat 2405 Nominal Cooling Capacity Electric Heat kw 2 Tons Cooling 5 kw Electric Heat 3608 Nominal Cooling Capacity Electric Heat kw 3 Tons Cooling 8 kw Electric Heat Major Revi...

Страница 14: ...2 3 1 2 Tons 10 SEER 1729 1 1 2 2 1 2 Tons for export systems Ceiling Mount Wall Mount Applications Nominal Cooling Capacity Electric Heat kW 1805 1 1 2 Tons Cooling 5 kW Electric Heat 2405 2 Tons Coo...

Страница 15: ...t Breaker DESIGN SERIES A First Series C A P F 1824 A 6 A PRODUCT TYPE C Indoor Coil CABINET FINISH U Unpainted P Painted N Unpainted Case EXPANSION DEVICE F Flowrater NOMINAL CAPACITY RANGE 13 SEER 1...

Страница 16: ...X X X X X CSR U 1 Hard Start Kit X X X X CSR U 2 Hard Start Kit X X X X CSR U 3 Hard Start Kit X X Model Description ASC13018 ASC13024 ASC13030 ASC13036 ASC13042 ASC13048 ASC13060 OT18 60A Outdoor The...

Страница 17: ...Kit x x OT18 60A Outdoor Lockout Stat OT EHR18 60 Emergency Heat relay kit CSR U 1 Hard Start Kit x x CSR U 2 Hard Start Kit x x x CSR U 3 Hard Start Kit x x Model Description CKL18 CKL24 CKL30 CKL36...

Страница 18: ...ORATOR COIL 1 4 FLARE CONNECTION BULB SUCTION LINE EXPANSION VALVE REMOVE BEFORE INSTALLING EXPANSION VALVE SEAL SUPPLIED W KIT SEAL SUPPLIED W KIT BULB TO BE LOCATED AT 10 OR 2 O CLOCK TAILPIECE 3 8...

Страница 19: ...HERMOSTAT WIRE SHORT CYCLE PROTECTOR YELLOW 1 BLACK 1 Y1 Y2 R1 R2 Y C UNIT TERMINAL BOARD CONTACTOR ASC01A ANTI SHORT CYCLECONTROLKIT Install Line Thermostat Here Install Line Thermostat Here Wire Nut...

Страница 20: ...RIES ELECTRIC HEAT KITS ELECTRICHEATKITAPPLICATIONS MBR MBE NO HEAT HKR 03 HKR05 C HKR 06 HKR 08 C HKR 10 C HKR 15 C HKR 20 C HKR 21 C HKR3 15 HKR3 20A MBR0800AA 1AA X X X X X MBR1200AA 1AA X X X X X...

Страница 21: ...the scroll A scrollisaninvolutespiralwhich whenmatchedwithamating scroll form generates a series of crescent shaped gas pockets between the members see following illustration Duringcompression onescr...

Страница 22: ...eavailable ARPF B 2 to 5 ton air handlers are dedicated for downflow operation and are approved for modular homes Flowrater transformerandblowertimedelayareonallstandard ARPF units Both the ARUF and A...

Страница 23: ...d itcontinuestogiveup heat which subcools the liquid and it is ready to repeat the cycle HEATING The heating portion of the refrigeration cycle is similar to the coolingcycle Byenergizingthereversingv...

Страница 24: ...door Coil Accumulator Bi Flow Filter Dryer Outdoor Coil Thermostatic Expansion Valve Check Valve Reversing Valve De Energized Indoor Coil Accumulator Bi Flow Filter Dryer Outdoor Coil Thermostatic Exp...

Страница 25: ...ng mode the orifice moves back off its seat allowingrefrigeranttoflowunmeteredaround the outside of the orifice EXPANSIONVALVE CHECKVALVEASSEMBLY INCOOLINGOPERATION EXPANSIONVALVE CHECKVALVEASSEMBLY I...

Страница 26: ...ndoor Coil Outdoor Coil Thermostatic Expansion Valve COOLING CYCLE CONDENSING UNIT In the cooling mode the orifice is pushed into its seat forcing refrigerant to flow through the metered hole in the c...

Страница 27: ...When used in this manner the Y heat demand is switched to the W1 input to the furnace by the outdoor thermostat and the furnace is used to satisfy the first stage Y heat demand On some controls ifthe...

Страница 28: ...est Motor Windings S 16 Improper Cooling Anticipator Check Resistance of Anticipator S 3B Shortage of Refrigerant Test For Leaks Add Refrigerant S 101 103 Restricted Liquid Line Remove Restriction Rep...

Страница 29: ...ressorWindings 43 S 17A Resistance Test 43 S 17B GroundTest 43 S 17D OperationTest 44 S 18 Testing Crankcase Heater optional item 44 S 21 CheckingReversingValveSolenoid 44 S 24 TestingDefrostControl 4...

Страница 30: ...nsofundersized wirecancauselowvoltage Ifwiresizeisadequate notify the local power company in regard to either low or high voltage REMOTE CONDENSING UNITS BLOWER COILS VOLTAGE MIN MAX 208 230 198 253 1...

Страница 31: ...TS OPTIONS Troubleshooting Encoded Two Stage Cooling Thermostats Options TEST FUNCTION SIGNAL OUT SIGNAL FAN S T E T S1 S1 S1 S2 S2 S2 S3 S3 S3 R COM LOW SPEED COOL LO SPEED COOL HI SPEED COOL LO SPEE...

Страница 32: ...pproximatelythree minutes before resetting 1 Remove wire from Y1 terminal 2 Wait for approximately four 4 minutes if machine was running With power ON WARNING Line Voltage nowpresent 1 Apply 24 VAC to...

Страница 33: ...relay or contactor S 8 CHECKING CONTACTOR CONTACTS DISCONNECTELECTRICALPOWERSUPPLY WARNING Disconnect Electrical Power Supply 1 Disconnectthewireleadsfromtheterminal T sideofthe contactor 2 With powe...

Страница 34: ...electrical box of any residential condensing unit that has a Copeland Scroll compressor inside Once attached Comfort Alert provides around the clock monitoring for common electrical problems compress...

Страница 35: ...formation Yellow ALERT Locked Rotor 1 Run capacitor has failed Flash Code 4 2 Low line voltage contact utility if voltage at disconnect is low 3 Excessive liquid refrigerant in compressor 4 Compressor...

Страница 36: ...or windings so that the motor will give two phase operation when connected to a single phase circuit The capacitor also reduces the line current to the motor by improvingthepowerfactor The line side o...

Страница 37: ...tion variable speed low noise and programmable air flow Be cause of the sophisticated electronics within the ECM motor some technicians are intimated by the ECM motor however these fears are unfounded...

Страница 38: ...ntinuityisindicated thethermallimit overload devicemaybeopen Allowmotortocooland retest 16 pin connector 5 pin connector 3 pin motor connector S 16D ECM CFM ADJUSTMENTS MBE MOTOR Thissectionreferences...

Страница 39: ...R G Turn power OFF prior to repair Wait 5 minutes after disconnecting power before opening motor Handle electronic motor control with care Motor rocks but won t start Loose motor mount Blower wheel n...

Страница 40: ...wer OFF prior to repair Wait 5 minutes after disconnecting power before opening motor Handle electronic motor control with care Blower won t shut off Current leakage from controls into G Y or W Check...

Страница 41: ...0 ON OFF OFF OFF 890 935 5 OFF ON OFF OFF 700 770 AEPF3036 3137 4260 Heating Element kw 1 2 7 8 UP TO 20 OFF OFF OFF OFF 2050 2150 UP TO 20 ON OFF OFF OFF 1750 1835 UP TO 15 OFF ON OFF OFF 1600 1680 U...

Страница 42: ...erminal may be expelled venting the vapor and liquid contents of the compressor housing and system IfthecompressorterminalPROTECTIVECOVERandgasket if required are not properly in place and secured the...

Страница 43: ...or other suitable instrument which puts out a voltage between 300 and 1500 volts check for a ground separately between each of the three leads and ground such as an unpainted tube on the compressor D...

Страница 44: ...tered at the coil tap the valve body lightly whileswitchingthesystemfromHEATINGtoCOOLING etc If this fails to cause the valve to switch positions remove the coil connector cap and test the continuity...

Страница 45: ...econd on delay the relay on the EBTDR board is energized and the blower motor starts 1 3 When the cooling demand Y is satisfied the room thermostat removes the 24Vac from G and Y 1 4Thecompressorandco...

Страница 46: ...on HR1 will open between 30 to 70 seconds and turn off both heater element s The heat pump remains on along with the blowermotorbecausethe Y demandforfirststageheat will still be present 4 5 When the...

Страница 47: ...eedona W1 onlydemand Ifthe first stage heat demand W1 cannot be satisfied by the heatpump thetemperatureindoorswillcontinuetodrop The room thermostat will then energize W2 and 24Vac will be supplied t...

Страница 48: ...roomthermostatwillremovethe 24Vacfrom E W1 oftheMBE ThecontactsonHR1will open between 30 to 70 seconds and turn off both heater element s The heat pump remains on along with the blowermotorbecausethe...

Страница 49: ...NOTE The temperature rise table is for sea level installa tions The temperature rise at a particular KW and CFM will begreaterathighaltitudes whiletheexternalstaticpressure at a particular CFM will b...

Страница 50: ...ng 1 Never open a system that is under vacuum Air and moisture will be drawn in 2 Plug or cap all openings 3 Remove all burrs and clean the brazing surfaces of the tubingwithsandclothorpaper Brazingma...

Страница 51: ...the suction line of the comprssor closed or severely restricted WARNING 1 Connect the vacuum pump vacuum tight manifold set with high vacuum hoses thermocouple vacuum gauge and charging cylinder as sh...

Страница 52: ...used When charging a remote condensing unit with a non match ing evaporator coil or a system where the charge quantity is unknown alternate charging methods must be used These systems must be charged...

Страница 53: ...AWB24 AWUF24 059 G VSH130251A 061 All other ARI Matches 061 G VSH130301A 068 G VSC130301A D GSH130301B 070 GSC130303A G VSH130311A 065 AC36 ACNF30 065 G VSH130361A 073 AWB36 AWUF36 068 GSH1303613A 1B...

Страница 54: ...or a restricted liquid line or drier A restriction will be indicated by a temperature drop across the drier 2 Checktheoperationofthepowerelementofthevalveas describedinS 110CheckingExpansionValveOpera...

Страница 55: ...ccurate thermometer or preferably a thermo couple type temperature tester to the liquid line as it leaves the condensing unit 2 Installahighsidepressuregaugeonthehighside liquid service valve at the f...

Страница 56: ...noticedatthepointofrestriction Inseverecases frostwillformattherestrictionandextenddownthelineinthe direction of the flow Discharge and suction pressures will be low giving the appearance of an underc...

Страница 57: ...system capacity proper oil return to compressor pumpingrateofcompressorandcoolingperformanceofthe evaporator This long line set application guideline applies to all AHRI listed R22 air conditioner and...

Страница 58: ...8 3 8 3 1 2 3 4 3 8 7 8 3 8 1 1 8 3 8 4 7 8 3 8 1 1 8 3 8 1 1 8 3 8 5 7 8 3 8 1 1 8 3 8 1 1 8 3 8 Line Diameter In OD REFRIGERANT LINE LENGTH Ft 0 24 25 49 50 74 Table9 7 8 required for full ratings 1...

Страница 59: ...superheatandsub coolinglevels especially on a system with a TXV installed in the indoor unit Heat pumps should be checked in both heating and cooling mode for proper charge level This guideline is mea...

Страница 60: ...or quantity of air If external static pressure is being measured on a furnace to determine airflow supply static must be taken between the A coil and the furnace Air Flow TOTAL EXTERNAL STATIC S 204 C...

Страница 61: ...P2 4 K1 OT NO Y P2 9 CALL FOR 2ND STAGE COMPRESSOR Y2 1 0K G FURN P2 1 C OT C C SECOND STAGE COMPRESSOR OUTPUT G CALL FOR EMERGENCY HEAT W1 FURN W2 HP F1 3A OT NC 24VAC 2ND STAGE COMPRESSOR DEMAND OUT...

Страница 62: ...age Electric Heat RED EMERGENCY HEAT RELAY 1 4 2 BLUE WHITE BLACK BROWN THERMOSTAT OT EHR18 60 2 1 From Air Handler C G W2 R C R W2 O Y From Outdoor Unit C G W2 E R O Y Indoor Thermostat W3 B L U E G...

Страница 63: ...or Unit C G W2 E R O Y Indoor Thermostat W3 W3 B L U E G R E E N W H I T E R E D B R O W N B L U E R E D W H I T E O R A N G E Y E L L O W 15kw and Above with Two OT EHR18 60 s Two Stage Electric Heat...

Страница 64: ...ATOR MOTOR ELECTRONIC BLOWER TIME RUN CAPACITOR SR EM EBTDR RC BK RD BL YL BLUE BLACK RED YELLOW COMPONENT CODE BROWN PURPLE GREEN PU BR GR FEMALE PLUG CONNECTOR MALE PLUG CONNECTOR NOTE 2 TRANSFORMER...

Страница 65: ...G NO K1 USE COPPER OR ALUMINUM WIRE EQUIPMENT GROUND 3 5 2 1 4 TR PC PU L1 L2 BL W BR SR PK G W BR BL PU R BK R R R BK BL BL R 208 240 24V BL R M6 M5 RS2 W BR BL BL L1 L2 BK BK R R Y Y Y M8 M7 BL BL B...

Страница 66: ...ATIONS CONNECT THERMOSTAT TO Y Y2 ONLY TAPE OR REMOVE Y1 CONNECTION CONNECT CONDENSING UNIT TO YCON C 6 RED WIRES TO BE ON TRANSFORMER TERMINAL 3 FOR 240 VOLTS AND ON TERMINAL 2 FOR 208 VOLTS 1 FOR HE...

Страница 67: ...DENSER COM W2 O ED W1 OUTDOOR HEATPUMP W W2 R W BL OTC OT1 C OT2 O E W1 BR BL Y BL Y YCON TO CONDENSER C PL2 3 1 2 BR Y W BL BR R PK G Y1 C W2 R TO Y Y2 G EM BK R G BL 4 5 6 7 8 9 W R R BL COM BL 5 TR...

Страница 68: ...for 240 volts and on terminal 2 for 208 volts 2 See composite wiring diagrams in installationinstructions for proper low voltage wiring connections Notes DELAY RELAY RELAY EVAPORATOR MOTOR ELECTRONIC...

Страница 69: ...T MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH Typical Wiring Schematic ASPF 16B with Electric Heat This wiring diagram is for reference on...

Отзывы: