Heater Model

HKCB20

HKCB30

HKCB40

Number of Stages

2

2

2

Output (MBH)

67.9

135.8

135.8

CFM

2,600

24.2

36.2

-

2,800

22.5

33.6

-

3,000

21.0

31.4

-

3,200

19.7

29.4

39.3

3,400

18.5

27.7

37.0

3,600

17.5

26.2

34.9

3,800

16.5

24.8

33.1

4,000

15.7

23.5

31.4

4,200

15.0

22.4

29.9

4,400

14.3

21.4

28.6

4,600

13.7

20.5

27.3

4,800

13.1

19.6

26.2

5,000

12.6

18.8

25.2

5,200

12.1

18.1

24.2

5,400

11.6

17.4

23.3

5,600

11.2

16.8

22.5

5,800

10.8

16.2

21.7

6,000

10.5

15.7

21.0

E

LECTRIC

 H

EAT

 A

IR

 T

EMPERATURE

 R

ISE

H

EAT

 K

IT

 A

VAILABILITY

Unit Size

HKCB20

HKCB30

HKCB40

X

X

X

10

X

X

X

X - Heat Kit Available
N/A - Heater Not Available

Notes

•  Maximum air temperature rise of 40° must not be exceeded.
•  See table for Electric Heat Kit Availability in various unit sizes.
•  Air temperature rise is for total heating capacity. Temperature rises at other conditions may be 

calculated by using the formula:

 

Temperature Rise = Output Capacity - BTU/h

  

 

 

1.08 x ft

3

/min. Air

fl

 ow

•  For altitudes over 2,000’, air temperature rise must be calculated using the formula:
 

Temperature Rise = Output Capacity - BTU/h              

   14.4 

ft

3

/Min.  Air

fl

 ow x Speci

fi

 c Weight of Air

•  Operation at less than nominal voltages must be derated by the following factors:  

460 volt-0.92; 230 volt-0.92; 208 volt-0.75.

Содержание 10.3 EER

Страница 1: ...grommets for vibration isolation Two independent condenser coils for two stage operation High and low pressure controls on all systems Mild ambient switch Centrifugal fan for quiet and efficient opera...

Страница 2: ...s liquid temperature or pressure decreases Caution If control is used below 50 F accumulators should be added to the equipment to avoid slugging of the compressors ROOF CURB PGC 5 Full perimeter curb...

Страница 3: ...Fan Diameter 24 24 24 24 Outdoor Nominal CFM 5 500 5 500 6 400 6 400 Face Area ft 15 6 15 6 23 8 23 8 Rows Deep Fins per Inch 2 21 2 21 2 21 2 21 Tube Diameter Material Copper Copper Copper Copper El...

Страница 4: ...4 www goodmanmfg com SS GPCC PRODUCT SPECIFICATIONS DIMENSIONS Unit Size A Height B Supply Air C Return Air PCC090 X 36 12 176 16 PCC120 X 52 20 2513 16 X Electrical Designation...

Страница 5: ...l A B PCC090 X 6 7 PCC120 X 22 23 X Electrical Designation DIMENSIONS ELECTRICAL CONNECTIONS 1 Main power entrance location 2 Control wiring entrance location 3 Optional field installed internal disco...

Страница 6: ...8 4 90 6 68 2 8 4 90 6 81 8 8 4 93 5 93 5 70 WB 8 4 96 4 44 8 8 4 96 4 58 5 8 4 96 4 73 1 8 4 96 4 87 7 73 WB 8 5 101 3 35 1 8 5 101 3 49 7 8 5 101 3 64 3 8 6 101 3 78 9 100 61 WB 8 5 78 9 70 1 8 6 8...

Страница 7: ...9 11 7 126 6 126 6 64 WB 11 6 115 9 84 9 11 6 115 9 105 1 11 6 119 9 119 9 11 7 126 6 126 6 67 WB 11 7 122 6 72 7 11 7 122 6 93 0 11 7 122 6 111 8 11 7 126 6 126 6 70 WB 11 8 130 7 60 6 11 8 130 7 80...

Страница 8: ...RISE HEAT KIT AVAILABILITY Unit Size HKCB20 HKCB30 HKCB40 7 X X X 10 X X X X Heat Kit Available N A Heater Not Available Notes Maximum air temperature rise of 40 must not be exceeded See table for El...

Страница 9: ...SS GPCC www goodmanmfg com 9 PRODUCT SPECIFICATIONS FAN PERFORMANCE DATA...

Страница 10: ...MER HEATER ACCESSORIES SEE HEATER W C GY GRAY BK 5 2 ELECTRIC START ELECTRIC W1 HIGH 230 TERMINAL TO 208 TERMINAL MODEL E COMP VT VIOLET FAN RELAY SWITCH WH WHITE Y COOLING TAP MED LOW HIGH HIGH HIGH...

Страница 11: ...ER MED PHCB05C1 RELAY GN CAP RELAY COM L1 HORIZ LOW VOLTAGE C ACCESSORY INSTALLATION INSTRUCTIONS OR ORANGE TAP HEAT 1 LOW 22303201 REV 1 230 VOLT 4 FUSE 208 VOLT INSTALLATION LEADS MAY BE USED WITH E...

Страница 12: ...LATION BLOWER ACB L1 208 230 VAC 1 FOR PROPER OPERATION ON 208 VOLT THE FOLLOWING CHANGE MUST BE MADE 208 VOLT INSTALLATION MOVE RD6 WIRE FROM TRANSFORMER 230 TERMINAL TO 208 TERMINAL VT 20 RD 10 CONT...

Отзывы: