SS-GPCC
www.goodmanmfg.com
3
P
RODUCT
S
PECIFICATIONS
S
PECIFICATIONS
PCC090-3A
PCC090-4A
PCC120-3A
PCC120-4A
Cooling Capacity
Total BTU/h
86,000
86,000
116,000
116,000
Sensible BTU/h ¹
63,600
63,600
85,000
85,000
EER ²
10.3
10.3
10.3
10.3
IPLV ³
10.7
10.7
10.7
10.7
Indoor Blowers (2)
Type
Belt
Belt
Belt
Belt
Wheel (D x W)
12” x 12”
12” x 12”
12” x 15”
12” x 15”
Indoor Nominal CFM
3,000
3,000
3,800
3,800
Horsepower
1½
1½
3
3
Evaporator Coil (1)
Face Area (ft²)
11.2
11.2
14
14
Rows Deep/ Fins per Inch
3/ 16
3/ 16
3/ 16
3/ 16
Tube Diameter - Material
⅜
” - Copper
⅜
” - Copper
⅜
” - Copper
⅜
” - Copper
Filter Size (ft²) / Quantity
––
––
16 x 25 x 2 / 3
16 x 25 x 2 / 3
25 x 25 x 2 / 3
25 x 25 x 2 / 3
20 x 25 x 2 / 3
20 x 25 x 2 / 3
Condenser Fans (2) / Coil (1)
Horsepower
½
½
½
½
Fan Diameter
24”
24”
24”
24”
Outdoor Nominal CFM
5,500
5,500
6,400
6,400
Face Area (ft²)
15.6
15.6
23.8
23.8
Rows Deep/ Fins per Inch
2/ 21
2/ 21
2/ 21
2/ 21
Tube Diameter - Material
⅜
” - Copper
⅜
” - Copper
⅜
” - Copper
⅜
” - Copper
Electrical Data
Voltage-Phase
208/230-3
460-3
208/230-3
460-3
Compressor RLA/ LRA
12.5/ 88
5.9/ 44
17.4/ 123
6.8/ 49.5
Indoor Blower FLA
4.2
2.0
8.4
4.2
Outdoor Blower FLA
2.6
1.3
2.6
1.3
Min. Circuit Ampacity
4
38.1
18.2
54.5
22.5
Max. Overcurrent Device
5
60 amps
30 amps
70 amps
35 amps
Operating Weight (lbs)
980
980
1,270
1,270
Ship Weight (lbs)
1,000
1,000
1,290
1,290
¹ Sensible capacity is gross, with no deduction for indoor motor heat
² BTU/Watt @ 80/ 67° F inside; 95° F outside air
³ IPLV = Integrated Part Load Valve
4
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
5
HACR breakers may be used in place of fuses up to 60 amps