DC155
4 manual
Page 7
Gönnheimer Elektronic GmbH
phone.: +49 (6321) 49919-0, fax: -41
Email: [email protected]
2.3.2
Dosing control with a proportional (analog) valve
The DC155 can optionally get supplied with a
4...20 mA analog output
to control a proportional solenoid
valve. In this case, the analog output has to be configured as
"Ramp shape"
.
It is possible to set the maximum value of the analog output, the starting value and the ending value by using
the following three parameters (percentage values):
"Limit for analog output", "Start value of the rising
ramp"
and
"End value of the falling ramp".
The analog output can get configured as:
0...20 mA
: 0% = 0mA, 100% = 20mA
4...20 mA
: 0% = 4mA, 100% = 20mA
The dosing quantity is set with the parameter "setpoint". The rising ramp is determined by the parameter
"setpoint 1", the falling ramp by "setpoint 2". The ramp is determined by the filling quantity, not by the time.
This means that the analog output is at its maximum after the quantity "Setpoint 1" has been filled and not
after a given time.
The meaning of all these parameters is demonstrated with the following diagram.