Installation

Mounting

The GL-235 is designed for outdoor use.  Mount the box vertically with the knockouts facing
downward.  For safety, the GL-235 must be a minimum of 5 feet (horizontally) from the pool or
spa.

Power input

Turn off power at circuit breaker before wiring.  Remove the internal panel to expose the wiring
connections.  Either 115VAC or 240VAC can be used.  Refer to the input wiring diagram (Figure 1)
on next page.  

WARNING:  Applying 240VAC to the 120VAC input terminals will cause

permanent damage to the control.

Grounding

Refer to NEC and local codes for specific grounding requirements.  In general, a separate ground
conductor must be run to the ground terminal on the pool service panel.

Low Voltage (LV) output:  Solar Valve

The GL-235-LV and GL-235-LV-HV control a single valve.  In most applications this is the solar
valve, which diverts water through the collector panels or through the normal pool loop depending
on conditions.

Description

The GL-235-LV and GL-235-LV-HV are differential temperature controls for solar heating of pools,
spas, and hot tubs.  These models provide differential temperature control with an adjustable,
calibrated water temperature high limit.  Automatic nocturnal cooling (for pools that overheat in
hot climates) and recirculate freeze protection functions can be enabled/disabled via internal jumpers.

Input power can be either 115 or 240 VAC.  The output controls a 24VAC automatic valve actuator.
For older systems with 12VAC valves, an internal jumper can be moved to select 12 VAC output
operation.  The GL-235-LV-HV has one low voltage output for controlling a single valve and a second
high voltage output for controlling a filter pump or booster pump.

Specifications

Power

:

        105-130VAC, .5A 50/60Hz.

Or

        195-250VAC, .3A 50/60Hz

Output:

          Selectable low voltage 24VAC,
          20VA, .85A or 12VAC, 20VA,
        1.7A

GL-235-LV-HV only:

        SPST-NO isolated contact
        115VAC 1HP
        240VAC 2HP

Sensors:

        2 required  (thermistor,

                        10Kohm @  25C/77ºF).

Differential

:   on at 4ºF, off at 1.5ºF

Desired
P o o l
Temp.:

      70-104ºF calibrated scale or
      Solar Off, 75-104ºF  on
      some models

Recirculate
freeze

:

            On  at  <40ºF, off at > 42ºF

                      Enabled via jumper

Nocturnal
cooling:

       On when collector 8ºF less than
       pool and pool hotter than limit,
       off when collector 3ºF less than
      pool or pool cooler than high
       limit.  Enabled via jumper

2

Содержание GL-235-LV

Страница 1: ...3NF of the pool tem perature or the pool temperature is lowered below the set desired temperature SINGLE SETTING FOR DESIRED TEMPERATURE The GL 235 logic is set by a single dial adjustment with the d...

Страница 2: ...eplacement SEE WARRANTY STATEMENT FOR COMPLETE DETAILS Service You Can Count On Visit www goldlinecontrols com or call 800 343 0826 to speak with a qualified technical support representative Our techn...

Страница 3: ...GL 235 Solar Pool Controller Installation OperationManual for models GL 235 LV GL 235 LV HV www goldlinecontrols com 888 921 7665 North Kingstown RI USA LDLINE CONTROLS INC G...

Страница 4: ...s spas and hot tubs These models provide differential temperature control with an adjustable calibrated water temperature high limit Automatic nocturnal cooling for pools that overheat in hot climates...

Страница 5: ...ery important if recirculate freeze protection or nocturnal cooling functions are being used Also this function can be used on systems where the system should operate whenever solar heat is available...

Страница 6: ...protection starts early enough to protect the system The GL 235 is shipped from the factory with recirculate freeze protection disabled the jumper is present but installed on one pin only To activate...

Страница 7: ...n the MANUAL OFF position during cold weather Also note that the switch does NOT turn power off to the GL 235 Troubleshooting No Power Indicator Check main power circuit breakers Check fuse Fuse Repla...

Страница 8: ...SENSOR indicator blinking If the CHECK SENSOR indicator is blinking there may be a possible open circuit or short circuit with the solar sensor Using a voltmeter measure the voltage across the termina...

Страница 9: ...BasicInstallationofGL 235 LV Figure2 7...

Страница 10: ...GL 235 LV HVwithHighVoltageOutputusedforTimerOverride Figure3 8...

Страница 11: ...GL 235 LV HVwithHighVoltageOutputusedforBoosterPump Figure4 9...

Страница 12: ...10 Measuring Voltage of Pool Sensor Use the same method to measure the Solar Sensor Figure5...

Страница 13: ...29 51 19 377 3 30 91 7 164 2 09 131 2 987 1 15 12 58 774 4 27 52 18 870 3 27 92 6 999 2 06 132 2 926 1 13 13 57 014 4 25 53 18 377 3 24 93 6 839 2 03 133 2 867 1 11 14 55 313 4 23 54 17 899 3 21 94 6...

Страница 14: ...warrants its solar control products installed outside of the USA or Canada to be free from defects in material or workmanship under normal use and service for one year from date of the initial system...

Отзывы: