22.Test
current
Test function for the current mA value of the
probe
:
ADC: 7400=11.40 mA
If
level probe
is not submerged, the value should
be close to 4 mA. Tolerance range is 3.7 ... 4.3 mA.
23.Test
relay
SmartBox 4
Furthermore, devices connected on the relay contact will also be switched
on and/or off!
•
Connected devices can be damaged (dry running).
•
Operating media may leak.
Disconnect the devices connected before
test relay
.
Only reconnect the devices again
after
test relay.
Relay 1 ON/OFF
Test function for the switch function of relay
24.Reset
ESC
Exit this function without executing it.
Restart
Initialisation. The device software restarts and
keeps all device settings.
Factory
settings
Complete reset of all parameters to the original
delivery status.
26.Exit
Press [Enter] to return to display mode
SmartBox
®
4 LAN-Activation of other indicators (and assignation of the respective tank
numbers)
Numbering the tanks (if applicable)
The level gauge SmartBox
®
4 LAN always has tank number 1.
If other level gauge SmartBox
®
1, 2 or 3 (display unit) are to be connected, they must be
assigned defined tank numbers. The tank numbers are simply assigned in the sequence in
which the display units log on for the first time.
First, activate display unit 2 for tank number 2 (switch on mains voltage), then for display unit
3, and so on.
Example: Activate tank 2
After connection the display unit of tank 2 as described under electrical installation –
Connecting the Interface to SmartBox
®
1, SmartBox
®
2 or SmartBox
®
3, switch on the
display unit of the tank in question (switch on the mains voltage).
In the display unit of SmartBox
®
4 LAN, the following will be indicated alternatingly: “Tank1:” -
“xx.xxxL“ – “Tank2:“ – “yy.yyyL“ (depending on the selection / adjustment in the menu step
6. Show tanks). Then, follow the same steps for the other display units.
The order of the displayed tanks can be changed subsequently under menu step
16.Sort. Tanks
SmartBox 4 LAN