SmartBox
®
4 BASIC PRO
13 / 16
Menu
Setting
Description
18.Language Language:
German,English,French
,Spain
[+] / [-] / [Enter]
Names:
ESC
[+] / [-] / [Enter]
Name Tank 1
: Suggested name
Letters can be changed with [+] / [-] / [Enter]
19.Exit
[Enter] back to display mode
20.LCD
display
Contrast:
90
Set the contrast of the LCD display
21.Device
info
Displays information about:
Software-version:
V6.00 (z. B.)
Serial-number
: Tank 1: SN=1234 (z. B.)
Gain:
X0=4.05mA B=1268
(for Tank 1)
22.Test
current
Test function for the current mA value of the
probe
:
ADC: 7400=11.40 mA
If
level probe
is not submerged, the value should
be close to 4 mA. Tolerance range is 3.7 ... 4.3 mA.
For larger deviations, see menu item 9.
23.Exit
[Enter] back to display mode
24.Reset
ESC
Reset the device software:
Exit this function without executing it.
Restart
Initialisation. The device software restarts and
keeps all device settings.
Factory
settings
Complete reset of all parameters to the original
delivery status.
26.Exit
Back to display mode
OPERATION
The product requires no operation while it is running.
FUNCTION CHECK
We recommend that you check the displayed litre values once per year to make sure that
they are correct.
For a simple check, pull the level probe up by its cable so that it hangs
above the liquid. In this status the display device should show 0 litres (+ tolerance).
The probe signal can be checked with menu step "22. Test Current"
At 0 cm fill level
approx. 3.7 – 4.3 mA.
In the event of a considerable deviation, we recommend a replacement.
New probe.
New probe/ replacement of the operating medium
If the installation of a new probe is required and/or a change in the operating medium takes
place, then firstly, all of the “standard values” under menu step “9th zero point probe“ must be
reset to the
factory setting
!
It is also necessary to check, and if required, correct all further set values.
17b.
H protocol
Data output:
Deactiv
Data: Litres
Data: Level
Data output to H Box (only with DTM-2):
•
Deactivated
•
Output in litres
•
Output in level