SmartBox
®
4 BASIC PRO
12 / 16
Menu
Setting
Description
10.Trim
height
xxx.x cm
Entry option for the reference height for the 2-point
measurement, for other probe measurement range
or for an unknown density. Subtract 1.0 cm from
the actual measured level and enter this value.
Calibrate:No
Calibrate:Yes
If activated (Yes), the display in menu steps 1+2 is
then "by comparison".
If this is entered with an almost empty
tank, it is recommended that you make a correction
the next time it is filled.
11.Exit
Press [Enter] to return to display mode
12.Unit
L
default setting
m³
%
m
kg
IG
UG
t
mbar
kPa
liter:
cubic meters:
percent:
meter:
kilogram:
imperial Gallon:
US liquid gallon:
ton:
millibar:
kilopascals:
999900L
2.50m³
99.50%
2.50m
999900kg
219750IG
263900UG
2.50t
500mbar
50kPa
13.Rounding Automatically
Without
rounding
20L
50L
100L
200L
500L
1.000L
Default settings
minimal increments
Rounding increments in relation to the set volume
set with [+]/ [-] keys
14.Exit
Press [Enter] to return to display mode
15.Exit
Press [Enter] to return to display mode
16.Delete
tank
ESC
Exit the menu
Delete Tank n
Settings for tank n are deleted and reset to default
settings (tanks 2, 3, 4)
17.Input/
Output
Alarm-In
Sets the function of the alarm contact input
Closing
Closer alarm. Input closed
Alarm
Opening
Opener alarm. Input contact opens
Alarm
Deactiv
Sets the alarm input functionless
Data-Out
Defines the data output on the output adapter slot
Tank: 1
1-4
For data output a selection can be made between
•
Output single tank 1, 2, 3 or 4
for analogue
adapter
•
Output “1-4”
all tanks are output sequentially
via digital slot-in adapter – e.g. for PC set LAN