SmartBox
®
4 BASIC PRO
10 / 16
Menu
Input function
Input value
4.Tank
volume
Adjust the tank volume with [+] / [-] (100%). The default
setting is 0 L. The value must be set.
___________L
Please see a volume table for the highest value,
if available. For a 100 m³ cyl. buried tank, this
may for example be the value 100600 litres.
5.Tank
height
Enter inner tank height in millimetres: e. g.: 249 cm
(max. value = 999,9 cm) (height without dome)
_________mm
Please see a volume table for the highest value,
if available. For a 100 m³ cyl. buried tank, this
may for example be the value 288 cm.
5b.Filling
limit
Set the filling limit of the tank with [+]/ [-]:
With fuel oil tanks, that is the shut-off point of the limit
indicator. The default setting is 95%.
e.g. 95%=237cm. For tanks which can be filled to the
very top (e.g. water tanks), it is necessary to set the
highest value of 99%.
__________%
6.View
Tank
In the 1st line of the display, the tank name/medium and
contents are displayed (e.g. in litres).
The display in the 2nd line can be selected:
____________
View details
e.g.
Single/detailed
FiPercent
a)
FiLevel
b)
Level
c)
For fuel oil tanks in Germany, a free capacity display is
required according to TRwS 791-2. This is possible with
selection a) and b).
Single/Detailed
The tanks are displayed
cyclically one after the other, with L, % and, if
applicable, temperature. With display change.
Collective
The (eg. L) values of tanks 1 to 4 are displayed
(depending on the number of connected probes)
Without display change.
Percent
Yes
No
Select
Yes
display change
values (eg. in L) Tank 1 – 4
total capacity d percent values
7.+8.Exit
Press Enter to return to display mode
After performing entry steps 1 - 7, the programming process is completed.
After confirmation of step “8.Exit“, the device automatically returns to default display mode;
the current tank content is shown in the display.
Special functions are available under entry steps 9 to 24 (see page 13).
After the end of setup, do not forget to replace the housing cover!
After completing the ASSEMBLY and PROGRAMMING, carrying out a function check is
recommended (FUNCTION CHECK section).