EXAMPLE FOR PROGRAMMING
Example: 4 Basement tanks for 15.000 litres fuel oil, litre display, linear steel tank
Inner height 220 cm, (fill level tank 1 = 125 cm)
SmartBox
®
4 BASIC PRO
with 4 standard probes 0 - 250 mbar
Menü-Schritt
Eingaben / Auswahl
Tank number:
1 (2,3,4)
1.Measure probe
250mbar
2.Liquid
Heat.oil
3.Tank shape
Linear
4.Tank volume
15.000L
(set with [+] / [-] keys)
5.Tank height
220.0cm
(set with [+] / [-] keys)
5b.Filling limit
95%=209cm
(set with [+] / [-] keys)
6.View tanks
Single/detailed
Collective
Percents: Yes
(
L
Σ
%
are displayed alternately)
7.Exit
press [Enter] to see the indication
8.500L 8.520L
Σ
34.120
8.540L 8.560L 57% 57% 57% 57%
For Tank 2-4 repeat the entry with the correct value in the same way as with tank1
Tanks with inner shell
For tanks with an inner shell (e.g. cylindrical horizontal or tanks welded together in the
basement) the data in steps "4.Tank volume" and "5.Internal tank height" must be corrected.
Examples:
Wall thickness of inner casing 0.5cm
reduce value for inner height by approx. 1cm,
reduce volume for 10m³ by 1.3%, for 20m³ by 1 %, for 50m³ by 0.8% and for 100m³
by 0.7 %.
Wall thickness of inner casing 2cm
reduce value for inner height by approx. 4cm,
reduce volume for 10m³ by 5%, for 20m³ by 4%, for 50m³ by 3% and for 100m³ by 2.5%.
NOTES ON PROGRAMMING
Menu
Setting
Description
9.Offset
probe
Adjusting:
Probe zero point, electric
Position / Distance from base
Unusable capacity that is not to be displayed
ESC
Exit the menu
Offset calibr.
New measurement of probe zero point (electric)
Lift
level probe
out of the liquid beforehand.
Probe bottom
gap
Distance: x cm
;
normal reference is x = 0 cm, max = 99 cm
Bottom
deadstock
Suction position: y cm
Normal reference is 0 cm = complete capacity.
y > 0 cm means corresponding unusable capacity.
Default values
Complete reset of all parameters of menu step 9 to
the
original delivery status
.