FIRST RESPONDER - USER HANDBOOK
B-8
Fig. B-7 50% LEL Display
10) Make sure that correct reading is displayed before
disconnecting the calibration gas then disconnect
tubing from instrument inlet and turn regulator valve
on calibration gas cylinder in a clockwise direction
to turn off gas flow.
11) Make sure that the regulator valve is in the fully
closed position (Off) then disconnect the regulator
from the gas cylinder (turn regulator body in a
counter clockwise direction).
12) Replace the cap on the calibration gas cylinder.
13) Repeat steps 1 to 12 for each range to be calibrated
otherwise quit FCM. See QUITTING FCM for further
details.
Quitting FCM
Quit and Save Changes
1) Press and hold Switch Two (
) to save CAL
data.
2) Double press Switch One (
) to exit FCM.