D6031 

- SIL 3 Switch/Proximity Detector Repeater Open Collector Output 

G.M. International ISM0214-2 

D6031 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards. 
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided. 

 

Warning 

Operation 

 D6031 module is a unit suitable for applications requiring SIL 3 level (according to IEC 61508) in safety related systems for high risk industries. 
The unit can be configured for switch or proximity detector (EN60947-5-6, NAMUR), NO or NC and for NO or NC optocoupled open collector transistor output. 
Each channel enables a load to be controlled by a switch, or a proximity detector. 
Fault detection circuit (DIP switch configurable) is available for both proximity sensor and switch equipped with end of line resistors. In case of fault, when enabled it de-energizes 
the corresponding output transistor and turns the fault LED on; when disabled the corresponding output transistor repeats the input line open or closed status as configured. 
D6031D is programmable via dip switches as single input and two independent outputs. Out 2 can be programmed for output duplicating Out 1 or Fault detection Out. 
In case of duplication, transistor driving can be independently configured for each output. 
In case of fault output, transistor driving can be programmed as normally close or normally open. 
Presence of supply power and status of output (energized or de-energized), as well as integrity or fault condition of sensor and connecting line are displayed by signaling LEDs 
(green for power, yellow for status and red for fault condition). 
 

Note:

 use of voltage free electrical contacts with fault detection enabled (control equipment) requires, near the switch at the end of the line a R1=1 K

 typical (470 

 to 2 K

 range) 

resistor in series and a R2=10 k

 typical (5 K

 to 15 K

 range) resistor in parallel to the contacts in order to allow the fault detection circuit to distinguish between a condition of 

contact close/open and a line open/short circuit fault. 

Installation 

 D6031 series are Switch/Proximity Detector Interface housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or 
on customized Termination Board. 
D6031 unit can be mounted with any orientation over the entire ambient temperature range. 
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without 
suffering or causing any damage. 
The wiring cables have to be proportionate in base to the current and the length of the cable. 
On the section “Function Diagram” and enclosure side a block diagram identifies all connections. 
Identify the number of channels of the specific card (e.g. D6031S is a single channel model and D6031D is a dual channel model), the function and location of each connection terminal 
using the wiring diagram on the corresponding section, as an example: 
Connect 24 Vdc power supply positive at terminal “5” and negative at terminal “6”. 
For Model D6031S connect positive output of channel 1 at terminal “1” and negative output at “2”. 
For Model D6031D in addition to channel 1 connections above, connect positive output of channel 2 at terminal “3” and negative output at “4”. 
For Model D6031S, in case of Proximity or Voltage free Contact, connect the wires at terminal “7” for positive and “8” for negative. 
For Model D6031D in addition to channel 1 connections above, connect terminal “9” for positive and “10” for negative on channel 2. 
 
Connect SPST output transistors checking the load rating to be within the maximum rating (100 mA at 35 Vdc (

 1.5 V voltage drop)). 

Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. 
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water. 
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. 
According to EN61010, D6031 series must be connected to SELV or SELV-E supplies. 

 

 

Start-up 

 Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires. Check conductors for exposed wires that 
could touch each other causing dangerous unwanted shorts. Turn on power, the “power on” green led must be lit, status and fault led on each channel must be in accordance with 
condition of the corresponding input line. If possible close and open input lines one at time checking the corresponding status and fault LEDs condition as well as output to be correct. 

 

Содержание D6031D

Страница 1: ...y Detector Repeater Open Collector Output G M International ISM0214 2 SIL 3 Switch Proximity Detector Repeater Transistor Open Collector Output DIN Rail and Termination Board Models D6031S D6031D D6031S D6031D INSTRUCTION MANUAL ...

Страница 2: ...lly protected Current consumption 24 V 22 mA for 2 channels D6031D 12 mA for 1 channel D6031S with short circuit input and transistor closed typical Power dissipation 0 53 W for 2 channels D6031D 0 30 W for 1 channel D6031S with 24 V supply voltage short circuit input and transistor closed typical Isolation Test Voltage In Out 2 5 KV In Supply 2 5 KV In In 500 V Out Supply 500 V Out Out 500 V Inpu...

Страница 3: ...t detection Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 EN61326 3 1 for safety system In field programmability by DIP Switch TÜV Certification TÜV Functional Safety Certification High Density two channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks with or without Power Bus or customized Termination Boards...

Страница 4: ... D5031D Duplicator and Fault Out 5 6 1 2 Out 1 Signal SIL 3 7 8 Termination board connector Supply 24 Vdc Power and Fault Bus F 3 4 Out 2 Duplicator or Fault 9 10 In Proximity voltage free Contact voltage free Contact R1 R2 Resistors R1 R2 used with voltage free contact required for line fault detection Terminals 9 10 must be shorted to set module as Duplicator or Fault Out MODEL D5031S 6 1 2 Out ...

Страница 5: ...in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022 with or without Power Bus or on customized Termination Board D6031 unit can be mounted with any orientation over the entire ambient temperature range Electrical connection of conductors up to 2 5 mm are accommodated by polarized plug in removable screw terminal blocks which can be plugged in out into a powered un...

Страница 6: ...ity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 5 OFF 1 ON 5 ON NC 1 2 1 NO 2 Output 1 NO 2 Output NC 1 2 Position in fault condition 1 2 2 ON 2 OFF Input Input Output Input Output Input CH2 Setting Line fault detection IN OUT Operation NO NC or NC NO NO NO or NC NC Disabled switch proximity...

Страница 7: ...C Mode ON OFF OFF ON Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition No Fault No Fault 1 OFF 5 OFF 5 ON Output 2 Operation Input Input Output 1 Input Output 1 Input 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 NC 1 2 1 NO 2 Output 1 1 NO 2 Output 1 NC 1 2 NC 3 4 3 NO 4 Set SW4 equal to SW2 Set SW4 opposite to SW2 6 6 ON...

Страница 8: ...on 1 2 3 4 7 8 must be set to OFF position 3 4 6 Not used 5 6 7 8 ON CH Setting Line fault detection IN OUT Operation NO NC or NC NO NO NO or NC NC Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition 1 OFF 5 OFF 1 ON 5 ON Input Input Output Input Output Input 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 NC 1 2 1 NO 2 Output...

Страница 9: ...n fault condition for SIL application if line fault detection enabled SW1 ON ON OFF ON Parallel for SIL applica tion Set equal to SW2 Not specified Fault condition OFF Reverse Set opposite to SW2 OFF for SIL application ON OFF NO ON NC for SIL applica tion OFF Fault Output D6031D used as double channel Configuration Summary Table WARNING dip switch 6 7 8 must be set to OFF position D6031D used as ...

Отзывы: