background image

 

D6031 

- SIL 3 Switch/Proximity Detector Repeater Open Collector Output 

G.M. International ISM0214-2 

General Description:

 The single and dual channel Switch/Proximity Detector Repeater, D6031S and D6031D module is a unit suitable for applications requiring SIL 3 level 

(according to IEC 61508:2010 Ed. 2) in safety related systems for high risk industries. 
The unit can be configured for switch or proximity detector (EN60947-5-6, NAMUR), NO or NC and for NO or NC optocoupled open collector transistor output. 
Each channel enables a load to be controlled by a switch, or a proximity detector. 
Fault detection circuit (DIP switch configurable) is available for both proximity sensor and switch equipped with end of line resistors. 
In case of fault, when enabled it de-energizes the corresponding output transistor and turns the fault LED on; when disabled the corresponding output transistor repeats the input line 
open or closed status as configured. 
D6031D is programmable via dip switches as single input and two independent outputs. Out 2 can be programmed for output duplicating Out 1 or Fault detection Out. 
In case of duplication, transistor driving can be independently configured for each output. 
In case of fault output, transistor driving can be programmed as normally close or normally open. 
Mounting on standard DIN-Rail, with or without Power Bus, or on customized Termination Boards. 

 

Functional Safety Management Certification: 

G.M. International is certified by TÜV to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. 

 

 

 

Technical Data 

Characteristics 

Supply:

 24 Vdc nom (18 to 30 Vdc) reverse polarity protected, ripple within voltage limits 

 5 Vpp, 2 A time lag fuse internally protected. 

Current consumption @ 24 V:

 22 mA for 2 channels D6031D, 12 mA for 1 channel D6031S with short circuit input and transistor closed, typical. 

Power dissipation:

 0.53 W for 2 channels D6031D, 0.30 W for 1 channel D6031S with 24 V supply voltage, short circuit input and transistor closed, typical. 

Isolation (Test Voltage):

 In/Out 2.5 KV; In/Supply 2.5 KV; In/In 500 V; Out/Supply 500 V; Out /Out 500 V. 

Input switching current levels:

 ON 

 2.1 mA (1.9 to 6.2 mA range), OFF 

 1.2 mA (0.4 to 1.3 mA range), switch current 

 1.65 mA ± 0.2 mA hysteresis. 

Fault current levels: 

open fault 

 0.2 mA, short fault 

 6.8 mA (when enabled both faults de-energize channel transistor with single channel unit D6031S or 

de-energize channel transistor with D6031D used as dual channel unit or actuate the fault transistor out with D6031D used as fault signaling unit). 

Input equivalent source: 

8 V 1 K

 typical (8 V no load, 8 mA short circuit). 

Output:

 voltage free SPST optocoupled open-collector transistor. 

Open-collector rating: 

100 mA at 35 Vdc (

 1.5 V voltage drop). 

Leakage current: 

 50 µA at 35 Vdc. 

Response time: 

 100 µs. 

Frequency response: 

5 KHz maximum. 

Compatibility: 

 

CE mark compliant, conforms to Directive: 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

Environmental conditions: 

Operating:

 temperature limits – 40 to + 70 °C, relative humidity 95 %, up to 55 °C. 

Storage:

 

temperature limits – 45 to + 80 °C. 

Approvals:

 

TÜV Certificate No. C-IS-722134640-01, SIL 2 / SIL 3 conforms to IEC61508:2010 Ed.2. 
TÜV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. 

Mounting:

 

T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board. 

Weight:

 about 130 g D6031D, 110 g D6031S. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm

2

Protection class:

 IP 20. 

Dimensions: 

Width 12.5 mm, Depth 123 mm, Height 120 mm. 

FSM

SIL 3

Содержание D6031D

Страница 1: ...y Detector Repeater Open Collector Output G M International ISM0214 2 SIL 3 Switch Proximity Detector Repeater Transistor Open Collector Output DIN Rail and Termination Board Models D6031S D6031D D6031S D6031D INSTRUCTION MANUAL ...

Страница 2: ...lly protected Current consumption 24 V 22 mA for 2 channels D6031D 12 mA for 1 channel D6031S with short circuit input and transistor closed typical Power dissipation 0 53 W for 2 channels D6031D 0 30 W for 1 channel D6031S with 24 V supply voltage short circuit input and transistor closed typical Isolation Test Voltage In Out 2 5 KV In Supply 2 5 KV In In 500 V Out Supply 500 V Out Out 500 V Inpu...

Страница 3: ...t detection Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 EN61326 3 1 for safety system In field programmability by DIP Switch TÜV Certification TÜV Functional Safety Certification High Density two channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks with or without Power Bus or customized Termination Boards...

Страница 4: ... D5031D Duplicator and Fault Out 5 6 1 2 Out 1 Signal SIL 3 7 8 Termination board connector Supply 24 Vdc Power and Fault Bus F 3 4 Out 2 Duplicator or Fault 9 10 In Proximity voltage free Contact voltage free Contact R1 R2 Resistors R1 R2 used with voltage free contact required for line fault detection Terminals 9 10 must be shorted to set module as Duplicator or Fault Out MODEL D5031S 6 1 2 Out ...

Страница 5: ...in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022 with or without Power Bus or on customized Termination Board D6031 unit can be mounted with any orientation over the entire ambient temperature range Electrical connection of conductors up to 2 5 mm are accommodated by polarized plug in removable screw terminal blocks which can be plugged in out into a powered un...

Страница 6: ...ity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 5 OFF 1 ON 5 ON NC 1 2 1 NO 2 Output 1 NO 2 Output NC 1 2 Position in fault condition 1 2 2 ON 2 OFF Input Input Output Input Output Input CH2 Setting Line fault detection IN OUT Operation NO NC or NC NO NO NO or NC NC Disabled switch proximity...

Страница 7: ...C Mode ON OFF OFF ON Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition No Fault No Fault 1 OFF 5 OFF 5 ON Output 2 Operation Input Input Output 1 Input Output 1 Input 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 NC 1 2 1 NO 2 Output 1 1 NO 2 Output 1 NC 1 2 NC 3 4 3 NO 4 Set SW4 equal to SW2 Set SW4 opposite to SW2 6 6 ON...

Страница 8: ...on 1 2 3 4 7 8 must be set to OFF position 3 4 6 Not used 5 6 7 8 ON CH Setting Line fault detection IN OUT Operation NO NC or NC NO NO NO or NC NC Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition 1 OFF 5 OFF 1 ON 5 ON Input Input Output Input Output Input 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 NC 1 2 1 NO 2 Output...

Страница 9: ...n fault condition for SIL application if line fault detection enabled SW1 ON ON OFF ON Parallel for SIL applica tion Set equal to SW2 Not specified Fault condition OFF Reverse Set opposite to SW2 OFF for SIL application ON OFF NO ON NC for SIL applica tion OFF Fault Output D6031D used as double channel Configuration Summary Table WARNING dip switch 6 7 8 must be set to OFF position D6031D used as ...

Отзывы: