background image

 

D5290S-078 

- 5 A SIL 3 Relay Output Module 

G.M. International ISM0152-8 

Functional Safety Manual and Applications 

 

18-13 or 19-24 

17 or 20 

14 or 23 

Application D5290S-078 - SIL 3 Load Normally De-energized Condition (ND) and Normally De-energized Relay, 

with interruption of only one load supply line 

PLC 

Output OFF 

0 Vdc 

Normal state operation 

Energized to trip operation 

 

ND 
Load 
SIL 3 

16 

15 

Service 
Load 
(Not SIL) 

+ / AC 

- / AC 

5) 

21 

22 

18-13 or 19-24 

17 or 20 

14 or 23 

PLC 

Output ON 

24 Vdc 

 

ND 
Load 
SIL 3 

16 

15 

Service 
Load 
(Not SIL) 

+ / AC 

- / AC 

21 

22 

Operation 

Input Signal  

Pins 1-2 or 3-4 

Pins 13-14 

or 23-24 

Pins  

15-16 

Pins  

21-22 

ND Load (SIL 3) 

Pins 14 (or 23),16,21-Supply 

 

Pins 17-18 

or 19-20 

Service 

Load 

Normal  

Low (0 Vdc) 

Open 

Open 

Open 

De-Energized 

 

Closed Energized 

Trip 

High (24 Vdc) 

Closed 

Closed Closed 

Energized 

 

Open De-Energized 

Description:

  

Input Signal from PLC/DCS is normally Low (0 Vdc) and is applied to pins 1-2 or 3-4 in order to Normally De-energize (ND) the internal relays. 
Input Signal from PLC/DCS is High (24 Vdc) during “energize to trip” operation, in order energize the internal relays. 
Load is Normally De-Energized (ND) therefore its safe state is to be energized. Load is connected in parallel to pins 14 (or 23) and 16 and 21. 
Disconnection of Load is done by disconnecting one supply line via three separate contacts in parallel. 
Service Load is normally energized, therefore it de-energizes during “energize to trip” operation. 
The following table describes the status (open or closed) of each output contact when input signal is High or Low. 

Safety Function and Failure behavior:

  

D5290S-078 is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0. 
In the 5th Functional Safety application, the normal state operation of relay module is de-energized, with ND loads.  
In case of alarm or request from process, the relay module is energized (safe state), energizing loads. 
The failure behaviour of all relay modules here considered is described by the following definitions: 
 

 fail-Safe State: it is defined as the output load being energized; 

 

 fail Safe: this failure causes the system to go to the defined fail-safe state without a process demand; 

 

 fail Dangerous: failure mode that does not respond to a demand from the process (i.e. being unable to go to defined fail-safe state), so that output load remains de-energized. 

In addition, there are other definitions of failure behaviours which are not safety-related: 
 

 fail “No effect”: failure mode of a component that plays a part in implementing the safety function but is neither a safe failure nor a dangerous failure; 

 

 fail “Not part”: failure mode of a component which is not part of the safety function but part of the circuit diagram and is listed for completeness. When calculating the SFF this 

     failure mode is not taken into account. It is also not considered for the total failure rate evaluation. 

  Failure rate date: taken from Siemens Standard SN29500. 

Failure rates table according to IEC 61508:2010 Ed.2 : 

λ

sd

 

λ

su

 

λ

dd

 

λ

du

 

SFF

 

0.00 FIT 

299.70 FIT 

0.00 FIT 

3.60 FIT 

98.81% 

PFDavg vs T[Proof] table 

(assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes 

10% of total SIF dangerous failures:       

T[Proof] = 1 year

 

T[Proof] = 6 years

 

PFDavg = 1.58 E-05 - Valid for 

SIL 3

 

PFDavg = 9.46 E-05 - Valid for 

SIL 3

 

PFDavg vs T[Proof] table 

(assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes >10% of total SIF dangerous failures: 

Failure rate table:

 

Failure category

 

Failure rates (FIT)

 

λ

dd

 = Total Dangerous Detected failures 

0.00 

λ

du

 = Total Dangerous Undetected failures 

3.60 

λ

sd

 = Total Safe Detected failures 

0.00 

λ

su

 = Total Safe Undetected failures 

299.70 

λ

tot safe

 = Total Failure Rate (Safety Function) = 

λ

dd

 + 

λ

du

 + 

λ

sd

 + 

λ

su

 303.30 

λ

not part

 = “Not Part” failures 

0.00 

λ

tot device

 = Total Failure Rate (Device) = 

λ

tot safe

 + 

λ

no effect

 + 

λ

not part

  

402.60

 

MTBF (device, single channel) = (1 / 

λ

tot device

) + MTTR (8 hours) 

283 years

 

MTTF

S

 (Total Safe) = 1 / (

λ

sd

 + 

λ

su

380 years 

MTTF

D

 (Dangerous) = 1 / 

λ

du

 

31709 years 

λ

no effect

 = “No effect” failures 

99.30 

MTBF (safety function, single channel) = (1 / 

λ

tot safe

) + MTTR (8 hours) 

376 years 

T[Proof] = 20 years

 

PFDavg = 3.15 E-04 - Valid for 

SIL 3

 

Systematic capability SIL 3.

 

Содержание D5290S-078

Страница 1: ...IL 3 Relay Output Module G M International ISM0152 8 5 A SIL 3 Relay Output Module for NE or ND Loads with NE or ND Relay condition DIN Rail and Termination Board Model D5290S 078 D5290S 078 INSTRUCTI...

Страница 2: ...14 conforms to EN60079 0 EN60079 15 IECEx BVS 10 0072 X conforms to IEC60079 0 IEC60079 15 INMETRO DNV 13 0109 X conforms to ABNT NBR IEC60079 0 ABNT NBR IEC60079 15 UL C UL E477485 conforms to ANSI U...

Страница 3: ...tion n 6 Systematic capability SIL 3 Installation in Zone 2 Division 2 5 A SIL 3 SIL 2 contacts for NE or ND loads with NE or ND Relay condition 8 A inrush current at 30 Vdc 250 Vac Line input monitor...

Страница 4: ...tor 22 21 19 20 23 24 Out S_1 NO contact 13 14 Out P_1 NC contact 17 18 16 15 Out S_2 NO contact Out S_4 NO contact Out P_2 NC contact Out S_3 NO contact To prevent relay contacts from damaging connec...

Страница 5: ...operation of relay module is energized with NE Normally Energized loads In case of alarm or request from process the relay module is de energized safe state de energizing loads The failure behaviour o...

Страница 6: ...ication the normal state operation of relay module is energized with NE Normally Energized loads In case of alarm or request from process the relay module is de energized safe state de energizing load...

Страница 7: ...nd mode as a Type A module having Hardware Fault Tolerance HFT 0 In the 3rd Functional Safety application the normal state operation of relay module is energized with NE Normally Energized loads In ca...

Страница 8: ...energized with ND Normally De energized loads In case of alarm or request from process the relay module is de energized safe state energizing loads The failure behaviour of all relay modules here cons...

Страница 9: ...ribed by the following definitions fail Safe State it is defined as the output load being energized fail Safe this failure causes the system to go to the defined fail safe state without a process dema...

Страница 10: ...s a Type A module having Hardware Fault Tolerance HFT 0 In the 6th Functional Safety application the normal state operation of relay module is de energized with ND loads In case of alarm or request fr...

Страница 11: ...5 the short circuit of each single relay coil and to verify the ohmic continuity of the contacts as described in the following procedure 1 Do not supply the input channel terminals 1 2 or 3 4 of modul...

Страница 12: ...i e IP54 to IP65 or NEMA type 12 13 consistent with the effective operating environment of the specific installation Units must be protected against dirt dust extreme mechanical e g vibration impact a...

Страница 13: ...g ON 1 line input monitoring 2 low voltage input monitoring 3 short circuit fault detection 4 T proof relay testing DIP switch configurations 1 2 3 4 5 6 7 8 ON OFF OFF OFF OFF OFF OFF ON ON 1 2 3 4 5...

Отзывы: