- 5 A SIL 3 Relay Output Module
G.M. International ISM0152-8
Configuration
An eight position DIP Switch is located on component side of pcb in order to set four mutually exclusive configurations:
1) line input monitoring, to allow DCS/PLC line input monitoring function (driving line pulse testing);
2) low voltage input monitoring (UVLO—under voltage lock out): module reflects a high impedance state to the control unit when the driving voltage is below the specified threshold;
3) short circuit fault detection: it allows DCS/PLC to detect short circuit fault of module;
4) T-proof relay testing.
ON
1) line input monitoring:
2) low voltage input monitoring:
3) short circuit fault detection:
4) T-proof relay testing:
DIP switch configurations:
1
2
3
4
5
6
7
8
ON
OFF OFF OFF OFF OFF OFF ON ON
1
2
3
4
5
6
7
8
ON
OFF OFF OFF OFF OFF OFF ON OFF
1
2
3
4
5
6
7
8
ON
OFF ON OFF ON OFF ON ON ON
T-proof relays enable
1
3
5
1
3
5
Normal Operation
ON ON
OFF
ON
OFF
OFF
T-proof relays (dip1 = relay1;
dip3 = relay2; dip5 = relay3)
1
2
3
4
5
6
7
8
ON
ON OFF ON OFF ON OFF ON ON
Please, see next page for testing procedure at T-proof.
WARNING:
after T-proof test, dip-switch 1-3-5 must be set to “OFF” position for normal operation.
Can be used only for Functional Safety applications
n° 1, 2, 3, 4 with NE Relay condition
Must not used for Functional Safety applications
n° 5, 6 with ND Relay condition!
This is factory settings