2
D5290S-078
- 5 A SIL 3 Relay Output Module
G.M. International ISM0152-8
0.2
0.1
V (V)
I (A)
10
20
30
40
50
100
200
300
0.3 0.5
1
2
3
Resistive
Load
4 5
250
Technical Data
Characteristics
Input:
24 Vdc nom (21.6 to 27.6 Vdc) reverse polarity protected, ripple within voltage limits
≤
5 Vpp.
The following monitoring circuits are mutually exclusive:
1)
Line input monitoring (DIP-Switch selectable):
to allow DCS/PLC line monitoring function (pulse test).
2)
Voltage monitoring (DIP-Switch selectable):
≥
21.6 Vdc for normal operation,
≤
17 Vdc reflects a high impedance (
≤
10 mA consumption) to the control device.
3)
Short circuit fault detection
(DIP-Switch selectable and only for Functional
Safety applications with NE Relay condition):
to allow DCS/PLC to detect short
circuit fault of module.
Current consumption @ 24 V:
60 mA with relay energized, typical.
Power dissipation:
1.5 W with 24 V input voltage, relay energized, typical.
Isolation (Test Voltage):
Input / All Outputs: 2.5 KV; Out S_1 & Out P_1 / Out S_3 & Out P_2, Out S_2, Out S_4: 500 V;
Out S_3 & Out P_2 / Out S_2, Out S_4: 500 V; Out S_2 / Out S_4: 500 V.
Output:
2 voltage free SPDT (= NO c parallel of 2 NC contacts) relay contacts identified with outputs: Out S_1 & Out P_1 and Out S_3 & Out P_2;
2 voltage free SPST (NO) relay contacts identified with: Out S_2 and Out S_4.
Terminals 13-14 (Out S_1), 15-16 (Out S_2), 21-22 (Out S_4) and 23-24 (Out S_3) are: open when relay is de-energized, closed in energized relay condition.
Terminals 17-18 (Out P_1) and 19-20 (Out P_2) are: closed when relay is de-energized, open in energized relay condition.
Contact material:
Ag Alloy (Cd free) or AgSnO
2
.
Contact rating:
5 A 250 Vac 1250 VA, 5 A 250 Vdc 175 W (resistive load).
Contact inrush current:
8 A at 30 Vdc, 250 Vac.
DC Load breaking capacity:
Mechanical / Electrical life:
10 * 10
6
/ 5 * 10
4
operation, typical.
Bounce time NO / NC contact:
4 / 10 ms, typical.
Frequency response:
10 Hz maximum.
Compatibility:
CE mark compliant, conforms to Directive:
2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS.
Environmental conditions:
Operating:
temperature limits - 40 to + 60 °C, relative humidity 95 %, up to 55 °C.
Storage:
temperature limits - 45 to + 80 °C.
Safety Description:
ATEX:
II 3G Ex nA nC IIC T4 Gc
IECEx / INMETRO / NEPSI:
Ex nA nC IIC T4 Gc
FM:
NI / I / 2 / ABCD / T4, I / 2 / AEx nA nC / IIC / T4
FMC:
NI / I / 2 / ABCD / T4, I / 2 / Ex nA nC / IIC / T4
EAC-EX:
2ExnAnCIICT4 X.
UKR TR n. 898:
2ExnAnCIICT4 X.
non-sparking electrical equipment. -40 °C
≤
Ta
≤
60 °C.
Approvals:
BVS 10 ATEX E 114 conforms to EN60079-0, EN60079-15,
IECEx BVS 10.0072 X conforms to IEC60079-0, IEC60079-15.
INMETRO DNV 13.0109 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079-15.
UL & C-UL E477485 conforms to ANSI/UL508
FM 3046304 and FMC 3046304C conforms to Class 3600, 3611, 3810,
ANSI/ISA-60079-0, ANSI/ISA-60079-15, C22.2 No.142, C22.2 No.213, C22.2 No. 60079-0, C22.2 No. 60079-15.
C-IT.ME92.B.00206 conforms to GOST 30852.0, 30852.14.
C
Ц
16.0036 X conforms to
ДСТУ
7113,
ДСТУ
I
ЕС
60079-15.
GYJ14.1406X conforms to GB3836.1, GB3836.8.
TUV Certificate No. C-IS-224248-01, SIL 2 / SIL 3 conforms to IEC61508:2010 Ed. 2.
TÜV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety.
DNV No.A-13625 and KR No. MIL20769-EL002 Certificates for maritime applications.
Mounting:
T35 DIN-Rail according to EN50022 or on customized Termination Board.
Weight:
about 145 g.
Connection:
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm
2
.
Location:
installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4 or Class I, Zone 2, Group IIC, T4.
Protection class:
IP 20.
Dimensions:
Width 22.5 mm, Depth 123 mm, Height 120 mm.
General Description:
The D5290S-078 is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed. 2 for high risk industries.
It provides isolation between input channel and output contacts.
Three mutually exclusive (by DIP-Switch programming) monitoring circuits are provided:
1) line input monitoring, to allow DCS/PLC line monitoring function: when enabled, the module permits a wide compatibility towards different DCS/PLC. Driving line pulse
testing, executed by DCS/PLC, is permitted by a dedicated internal circuit, to prevent relay and LED flickering.
2) low voltage input monitoring: when enabled, the module reflects a high impedance state to the control unit when the driving voltage is below the specified threshold.
3) short circuit fault detection (only for Functional Safety applications with NE Relay condition): when enabled, it allows DCS/PLC to detect short circuit fault of module.
See the following pages for Functional Safety applications with related SIL value.
Mounting on standard DIN-Rail or on customized Termination Boards, in Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2 or Class I, Zone 2.
Functional Safety Management Certification:
G.M. International is certified by TUV to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3.
FSM
SIL 3