5
D5072-099
- SIL 2 Temperature Signal Converter
G.M. International ISM0389-0
When used with separately powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D5072-099 Associated Apparatus are not exceed-
ed by the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below:
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable),
then 50 % of Co and Lo parameters are applicable and shall not be exceeded
(50 % of the Co and Lo become the limits which must include the cable such that Ci C cable
≤
50 % of Co and Li L cable
≤
50 % of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1
μ
F for Groups I, IIA, IIB and 600 nF for
Group IIC.
If the cable parameters are unknown, the following value may be used: Capacitance 200 pF per meter (60 pF per foot), Inductance 1 µH per meter (0.20 µH per foot).
Must
be
Hazardous Area/
Hazardous Locations
Device Parameters
D5072-099 Associated
Apparatus Parameters
Ui / Vmax = 12.8 V
Uo / Voc
D5072-099
Terminals
≥
Ci = 0 nF, Li= 0 nH
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
CLASS I, ZONE 0, GROUP IIC
SAFE AREA, ZONE 2 GROUP IIC T4,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
Ch1 7 - 8 - 9 - 10
D5072S-099
Ch1
Ch2
7 - 8 - 9
10 - 11 - 12
D5072D-099
Ch1 7 - 8 - 9 - 10
D5072S-099
Ch1
Ch2
7 - 8 - 9
10 - 11 - 12
D5072D-099
=
=
=
5 +
6 -
1
2
3
4
9
7
12
10
MODEL D5072D-099
=
=
=
=
Out 1 (SIL 2)
11
8
+
-
Termination
board
connector
F
Power and
Fault Bus
Supply 24 Vdc
Modbus RS485
A-
B+
Modbus RS485
Out 2 (SIL 2)
=
=
=
In 1
In 2
+
-
TC / mV
2-3 wires
RTD / Resistance
Pot.
2-3 wires
RTD / Resistance
Pot.
TC +
ext. comp.
+
-
TC / mV
TC +
ext. comp.
mA
Sink I
-
+
RL
mA
Sink I
-
+
RL
=
=
=
5 +
6 -
1
2
3 +
4 -
9
7
MODEL D5072D-099 (Alarm / Fault)
=
=
Out 1-A (SIL 2)
8
+
-
Termination
board
connector
F
Power and
Fault Bus
Supply 24 Vdc
Modbus RS485
A-
B+
Modbus RS485
=
=
Alarm / Fault
Out 1-B (SIL 2)
In 1
+
-
TC / mV
2-3 wires
RTD / Resistance
Pot.
TC +
ext. comp.
mA
Sink I
-
+
RL