- SIL 2 Temperature Signal Converter
G.M. International ISM0389-0
General Description:
The single and dual channel Temperature Signal Converter D5072S-099 and D5072D-099 accepts a low level dc signal from millivolt, thermocouple or resistance/
RTD or transmitting potentiometer sensor, located in Hazardous Area, and converts, with isolation, the signal to drive a Safe Area load, suitable for applications requiring SIL 2 level
(according to IEC 61508:2010 ed.2) in safety related systems for high risk industries. Output signal can be direct or reverse. Modbus RTU RS-485 output is available on Bus connector.
Cold junction compensation can be programmed as:
- Automatic: provided by an internal temperature sensor;
- Fixed: to a user-customizable temperature value;
- External: making use of an external RTD;
- Remote: (only D5072D) connecting compensation RTD to one of the two channels.
For D5072D-099 module: duplicator function provides two independent outputs from one single input. Output function can be configured as: average, subtractor, low/high or redundan-
cy selector. Modules are provided with alarm function, which is available via solid state contact output, Termination Board and Power Bus. Mounting on standard DIN-Rail, with or
without Power Bus, or on customized Termination Boards, in Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2 or Class I, Zone 2.
Technical Data
Characteristics
Supply:
24 Vdc nom (18 to 30 Vdc) reverse polarity protected, ripple within voltage limits
≤
5 Vpp, 2 A time lag fuse internally protected.
Current cons. @ 24 V:
50 mA (D5072D-099), 35 mA (D5072S-099) with 20 mA out typical.
Power dissip. @ 24 V:
1.0 W (D5072D-099), 0.75 W (D5072S-099) with 20 mA out typical.
Isolation (Test Voltage):
I.S. In/Out 2.5 KV; I.S. In/Supply 2.5 KV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V.
Input:
See section “Input specifications” for more details on Input sensors.
4-wire RTD input only on D5072S-099. Possibility of configuring user customized sensor (TC or RTD). Choice between °C/°F.
Integration time:
from 50 ms to 500 ms depending on sensor and fast/slow integration.
Resolution:
1 µV on mV/TC, 1 m
Ω
on RTD/resistance, 0.0001 % on transmitting pot.
Visualization:
0.1 °C on temp.,10 µV on mV, 10 m
Ω
on resistance, 0.1 % on pot.
Input range:
within sensor limits (-500 to +500 mV for mV, 0-4 k
Ω
for resistance).
Measuring RTD current:
≤
0.15 mA.
2 wire RTD line resistance compensation:
≤
50
Ω
(programmable).
Thermocouple Reference Junction Compensation:
programmable as
automatic with internal compensator, fixed (–60 to +100 °C), external with any supported RTD, or remote
using 1 channel (D5072D-099).
Thermocouple burnout current:
≤
50 µA.
Fault:
enabled or disabled. Analog output can be programmed to reflect fault conditions via downscale, highscale or customized value forcing. Fault conditions are also signaled via BUS
and by red LED on front panel for each channel. Fault conditions are: Sensor burnout, Sensor out of range, Output saturation, Internal fault, Cable resistance fault.
Output:
Fully customizable 0/4 to 20 mA, on max. 300
Ω
load source mode, current limited at 24 mA. In sink mode, external voltage generator range is V min. 3.5V at 0
Ω
load and V
max. 30V. If generator voltage Vg > 10 V, a series resistance
≥
(Vg - 10)/0.024
Ω
is needed. The maximum value of series resistance is (Vg - 3.5)/0.024
Ω
.
Resolution:
1 µA current output.
Transfer characteristic:
linear, direct or reverse on all input sensors.
Response time:
≤
20 ms (10 to 90 % step).
Output ripple:
≤
20 mVrms on 250
Ω
load.
Damping factor:
≤
30 s, configurable.
Modbus Output:
Modbus RTU protocol, from 4800 to 115.200 bps.
Alarm:
Trip point range:
within rated limits of input sensor (see input step resolution).
ON-OFF delay time:
0 to 1000 s, 100 ms step.
Hysteresis:
within rated limits of input sensor.
Output:
voltage free SPST photoMOS: 100 mA, 60 Vdc (
≤
1 V voltage drop).
Performance:
Ref. Conditions 24 V supply, 250
Ω
load, 23 ± 1 °C ambient temperature, slow integration mode, 4-wires (for D5072S-099) or 3-wires (for D5072D-099) configuration for
RTD.
Input:
Calibration and linearity accuracy:
see section “Input Specifications”.
Temperature influence:
see section “Input Specifications”.
Ref. Junction Compensation influence:
≤
± 1 °C (internal PT1000 sensor).
Analog Output:
Calibration accuracy:
≤
±0.05 % of full scale.
Linearity error:
≤
±0.05 % of full scale.
Supply voltage influence:
≤
±0.02 % of full scale for a min to max supply change.
Load influence:
≤
±0.02 % of full scale for a 0 to 100 % load resistance change.
Temperature influence:
≤
±1µA for a 1 °C change.
Compatibility:
CE mark compliant, conforms to Directive:
2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS.
Environmental conditions:
Operating:
temperature limits – 40 to + 70 °C, relative humidity 95 %, up to 55 °C.
Storage:
temperature limits – 45 to + 80 °C.
Safety Description:
ATEX:
II 3(1)G Ex nA [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
IECEx / INMETRO / NEPSI:
Ex nA [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I,
EAC-EX:
2Ex nA [ia Ga] IIC T4 Gc X, [Ex ia Da] IIIC, [Ex ia Ma] I.
UKR TR n. 898:
2ExnAiaIICT4 X, ExiaI X
associated apparatus and non-sparking electrical equipment.
D5072S-099: Uo/Voc = 7.2 V, Io/Isc = 23 mA, Po/Po = 40 mW,
Ui/Vmax = 12.8 V, Ci = 0 nF, Li = 0 nH at terminals 7-8-9-10.
D5072D-099: Uo/Voc = 7.2 V, Io/Isc = 16 mA, Po/Po = 27 mW,
Ui/Vmax = 12.8 V, Ci = 0 nF, Li = 0 nH at terminals 7-8-9, 10-11-12.
Um = 250 Vrms or Vdc, -40 °C
≤
Ta
≤
70 °C.
Approvals:
BVS 12 ATEX E 053 X conforms to EN60079-0, EN60079-11, EN60079-15.
IECEx BVS 12.0050X conforms to IEC60079-0, IEC60079-11, IEC60079-15.
INMETRO DNV 13.0110 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079-11, ABNT NBR IEC60079-15, ABNT NBR IEC60079-26.
C-IT.MH62.B.04182 conforms to GOST R IEC 60079-0,GOST R IEC 60079-11, GOST R IEC 60079-15.
C
Ц
16.0036 X conforms to
ДСТУ
7113,
ГОСТ
22782.5-78,
ДСТУ
I
ЕС
60079-15.
GYJ14.1406X conforms to GB3836.1, GB3836.4; GB3836.8, GB3836.20.
SIL 2 according to IEC 61508:2010 ed.2
(pending)
.
Mounting:
EN/IEC60715 TH 35 DIN-Rail, with or without Power Bus or on customized Termination Board.
Weight:
about 135 g D5072D-099, 130 g D5072S-099.
Connection:
by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm
2
.
Location:
installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4 or Class I, Zone 2, Group IIC, T4.
Protection class:
IP 20.
Dimensions:
Width 12.5 mm, Depth 123 mm, Height 120 mm.
The module is fully programmable. Operating parameters can be changed from PC via PPC5092 adapter connected to USB serial line and SWC5090 software.
Measured values and diagnostic alarms can be read on both serial configuration or Modbus output line.
SWC5090 software also allows the Monitoring and Recording of values. For details please see SWC5090 manual ISM0154.
Programming