D5072-099 

- SIL 2 Temperature Signal Converter 

G.M. International ISM0389-0 

D5072-099 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN/IEC60715 TH 35 DIN

-

Rail located in Safe Area or Zone 2, Group IIC, Temperature T4 

Hazardous Area (according to EN/IEC60079

-

15) within the specified operating temperature limits Tamb 

-

40 to +70 °C, and connected to equipment with a maximum limit for AC power 

supply Um of 250 Vrms or Vdc. 
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D5072-099 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. EN/
IEC60079

-

14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, 

particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 
De

-

energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. 

Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided. 

 

Warning 

Operation 

 Each input channel of Temperature Signal Converter D5072-099 accepts a low level dc signal from millivolt, thermocouple or 2-3-4 wire RTD temperature or transmitting potentiometer 
sensor, located in Hazardous Area, and converts, with isolation, the signal to a 4-20 mA floating output current to drive a Safe Area load. 
Presence of supply power is displayed by a “POWER ON” green signaling LED; integrity of field sensor and connecting line can be monitored by a configurable burnout circuit which, if 
enabled, can drive output signal to upscale or downscale limit. Burnout condition is signaled by red front panel LED for each channel. 
D5072D-099 module has double input and output channel, and can also be programmed to interface a single input and obtain dual output channel (duplicator) or configurable output 
channel (outputs can repeat the corresponding inputs or be proportional to the sum or difference of the two input process variables or with low/high selector function). 

Installation 

 D5072-099 series are Temperature Signal Converter housed in a plastic enclosure suitable for installation on EN/IEC60715 TH 35 DIN-Rail, with or without Power Bus or on customized 

Termination Board. 
D5072-099 unit can be mounted with any orientation over the entire ambient temperature range. 
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without 
suffering or causing any damage 

(for Zone 2 installations check the area to be nonhazardous before servicing)

. Connect only one individual conductor per each clamping point, use 

conductors up to 2.5 mm2 and a torque value of 0.5-0.6 Nm. Use only cables that are suitable for a temperature of at least 85°C. 
The wiring cables have to be proportionate in base to the current and the length of the cable. 
On the section “Function Diagram” and enclosure side a block diagram identifies all connections. 
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 
Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other 
and do not produce any unintentional connection. 
Connect alarm transistors checking the load rating to be within the maximum rating (100 mA at 60 Vdc (

 1 V voltage drop)). 

The enclosure provides, according to EN60529, an IP20 minimum degree of protection (or similar to NEMA Standard 250 type 1). The unit shall be installed in an area of not more than 
pollution degree 2 according to EN/IEC60664-1. For hazardous location, the unit shall be installed in a certified Ex enclosure with a minimum ingress protection of at least IP54 in 
accordance with EN/IEC60079-15, that must have a door or cover accessible only by the use of a tool. 
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a 
cloth lightly moistened by a mixture of detergent in water. 

Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5072-099 must be cleaned only with a damp or antistatic cloth. 

Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized modification must be avoided. 
According to EN61010, D5072-099 series must be connected to SELV or SELV-E supplies. 
All circuits connected to D5072-099 unit must comply with the overvoltage category II (or better) according to EN/IEC60664-1. 

 

 

Start-up 

 Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors 

and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. 
Check conductors for exposed wires that could touch each other causing dangerous unwanted shorts. 
Check that the module has been correctly configured through SWC5090 software. For details please see SWC5090 manual ISM0154 
Turn on power, the “power on” green LED must be lit, output on each channel must be in accordance with the corresponding input signal value and input/output chosen transfer function. 
If possible change the sensor condition and check the corresponding Safe Area output. 

 

Содержание D5072D

Страница 1: ...IL 2 Temperature Signal Converter G M International ISM0389 0 SIL 2 Temperature Signal Converter Multifunction DIN Rail and Termination Board Models D5072S 099 D5072D 099 D5072S 099 D5072D 099 INSTRUC...

Страница 2: ...ded The maximum value of series resistance is Vg 3 5 0 024 Resolution 1 A current output Transfer characteristic linear direct or reverse on all input sensors Response time 20 ms 10 to 90 step Output...

Страница 3: ...omized Termination Boards 250 Vrms or Vdc Um max voltage allowed to the instruments associated with the barrier Data logging and monitoring via software D5072S 099 Input for thermocouple TC or for 3 4...

Страница 4: ...ameters indicated in the table below D5072 099 Terminals Ch1 7 8 9 10 D5072S 099 Ch1 Ch2 7 8 9 10 11 12 Io Isc 23 mA Io Isc 16 mA Po Po 40 mW Po Po 27 mW Ii Imax Pi Pi D5072 099 Terminals Ch1 Ch2 7 8...

Страница 5: ...foot Inductance 1 H per meter 0 20 H per foot Must be Hazardous Area Hazardous Locations Device Parameters D5072 099 Associated Apparatus Parameters Ui Vmax 12 8 V Uo Voc D5072 099 Terminals Ci 0 nF L...

Страница 6: ...r F Power and Fault Bus Supply 24 Vdc Modbus RS485 A B Modbus RS485 Out 1 B SIL 2 In 1 TC mV 2 3 wires RTD Resistance Pot TC ext comp mA Sink I RL mA Sink I RL 5 6 1 2 3 4 9 7 12 10 11 8 Termination b...

Страница 7: ...perature range Electrical connection of conductors up to 2 5 mm are accommodated by polarized plug in removable screw terminal blocks which can be plugged in out into a powered unit without suffering...

Страница 8: ...3272 0 to 1800 32 to 3272 0 050 0 090 B IEC 60584 GOST 8 585 ASTM E230 200 360 1 1 2 0 450 to 1820 842 to 3308 0 to 1820 32 to 3308 0 060 0 108 C ASTM E230 ASTM E988 100 180 0 6 1 1 0 to 2315 32 to 41...

Страница 9: ...NT32 1104 Ch1 rtd multiplier RW FLOAT 1200 Ch2 cold junction fixed value 0 1 C RW SINT32 1202 Ch2 2 wire rtd correction mOhm RW SINT32 1204 Ch2 rtd multiplier RW FLOAT 1500 Ch1 sensor value volt res r...

Страница 10: ...ermocouple 1 rtd 2 voltage 3 resistance 4 potentiometer 8 Sensor Connection Bit pos Value Description 0 2 0 volt tc 2 wires 1 tc external compensation 2 res rtd 2 wires 3 res rtd 3 wires 4 res rtd 4 w...