D1053 

- SIL 2 Analog Signal Converter and Trip Amplifiers 

G.M. International ISM0016-13 

15) 

Type

   

 

[4 Level Menu] 

Displays the alarm type (A or B) configuration. Press “Enter” to set the alarm condition, press the “Select” key to the next menu level item or “Up” key to return to third level. 
If you pressed “Enter” key, you can choose between 5 different alarm conditions; press “Select” key to change the type and then the “Enter” key to confirm the choice. 
The condition types are: 
OFF   

no alarm detection, the relay output is always in normal condition 

HI 

 

high alarm condition, the relay output change status when an alarm condition is detected (input variable goes above the set value) 

LO 

 

low alarm condition, the relay output change status when an alarm condition is detected (input variable goes below the set value) 

LOSEC  

low with start-up alarm condition, the relay output change status when an alarm condition after the start-up is detected (input variable starts below the set 

 

 

value but no alarm condition is signaled, after the warm-up the variable goes above the set value arming the alarm detection, then when the variable goes 

 

 

below the set value the alarm condition is signaled) 

BURN   

burnout alarm condition, the alarm condition change status when a burnout condition appear in the input variable (input variable goes below the “Br LO” set 

 

 

value or goes above the “Br HI” set value).

 

16) 

B Ope

   

 

[4 Level Menu] 

Displays the functionality of alarm in burnout condition (A or B) configuration. Press “Enter” to set the burnout alarm condition, press the “Select” key to the next menu level item 
or “Up” key to return to third level. If you pressed “Enter” key, you can choose between 4 different alarm burnout conditions; press “Select” key to change the type and then the 
“Enter” key to confirm the choice. The types are: 
OFF   

the alarm goes in disabled condition when a burnout is detected 

NOR   

the alarm follow the condition of input variable (not relevant burnout) 

LOCK   

the alarm is locked in the same position as before a burnout is detected 

ON 

 

the alarm goes in enabled condition when a burnout is detected 

Note that a minimum of 1 second delay (“On dl” item) is necessary to obtain the burnout detection on alarm conditions. 

17) 

Relay

   

 

[4 Level Menu] 

Displays the relay normal condition (A or B) configuration. Press “Enter” to set the relay condition, press the “Select” key to the next menu level item or “Up” key to return to 
third level. If you pressed “Enter” key, you can choose between 2 different relay conditions; press “Select” key to change the type and then the “Enter” key to confirm the choice. 
The condition types are: 
ND 

 

relay normally de-energized (energized in alarm condition) 

NE 

 

relay normally energized (de-energized in alarm condition) 

18) 

Hyst

   

 

[4 Level Menu] 

Displays the alarm hysteresis value (A or B) configuration. Press “Enter” to set the deadband value, press the “Select” key to the next menu level item or “Up” key to return to 
third level. If you pressed “Enter” key, you can set the hysteresis value (engineering value); press the “Select” key to highlight the character you want to change and then the 
“Up” and “Down” keys to select the number; confirm the modification with the “Enter” key. The value is settable from 0 to 5000 points regarding the input sensor as specified. 

19) 

On dl

   

 

[4 Level Menu] 

Displays the alarm activation delay (A or B) configuration. Press “Enter” to set the delay time value, press the “Select” key to the next menu level item or “Up” key to return to 
third level. If you pressed “Enter” key, you can set the delay value (100 ms step); press the “Select” key to highlight the character you want to change and then the “Up” and 
“Down” keys to select the number; confirm the modification with the “Enter” key The value is settable from 0 to 1000 seconds in steps of 100 ms.

 

PPC1092, SWC1090 Configuration 

INPUT SECTION:

 

Input:

 input sensor type 

 mA dc (I)  current input, range from –4 to +24 mA 

 V dc (E) 

voltage input, range from –2 to +12 V 

Downscale:

 input value of measuring range corresponding to defined low output value. 

Upscale:

 input value of measuring range corresponding to defined high output value. 

Burnout Low:

 low burnout condition trip point value; 

below this value a burnout fault condition is activated and the analog output is driven to 

the configured state (see Burnout in Output Section). 

Setting this value outside the measuring range will disable this function. 

Burnout High:

 high burnout condition trip point value; 

above this value a burnout fault condition is activated and the analog output is driven to 

the configured state (see Burnout in Output Section). 

Setting this value outside the measuring range will disable this function. 

OUTPUT SECTION:

 

Output:

 analog output type 

 4-20 mA  current output range from 4 to 20 mA 

 0-20 mA  current output range from 0 to 20 mA 

 1-5 V 

voltage output range from 1 to 5 V 

 0-5 V 

voltage output range from 0 to 5 V 

 2-10 V 

voltage output range from 2 to 10 V 

 0-10 V 

voltage output range from 0 to 10 V 

Burnout:

 analog output burnout state 

 None 

burnout function is disabled; analog output represents the input measure as configured 

 Downscale analog output is forced at zero 

 Upscale 

analog output is forced to 22 mA for current output or 11 V for voltage output 

ALARM SECTION:

 

Type:

 alarm type configuration 

 Off  

alarm functionality is disabled 

 High 

alarm is set to high condition, the alarm output is triggered whenever 

 

 

the input variable goes above the trip point value (Set) 

 Low 

alarm is set to low condition, the alarm output is triggered whenever 

 

 

the input variable goes below the trip point value (Set) 

 Low & Sec  alarm is set to low condition with start-up, the alarm output is inhibited until 

 

 

the input variable goes above the trip point value (Set); afterwards it 

 

 

behaves as a Low configuration; typically used to solve start-up issues 

 Burnout 

a burnout condition of the input triggers the alarm output 

Set:

 input value of measuring range at which the alarm output is triggered 

Hysteresis:

 alarm hysteresis value, valid range: 0 to 5 mA for current input; 0 to 5 V for voltage input 

ON Delay:

 time for which the input variable has to be in alarm condition before the 

alarm output is triggered; configurable from 0 to 1000 seconds in steps of 100 ms. 

Relay:

 relay condition 

 ND 

the relay is in normally de-energized condition, 

 

 

it energizes (the output contact is closed) in alarm condition 

 NE  

the relay is in normally energized condition, 

 

 

it de-energizes (the output contact is opened) in alarm condition 

BurnOut Oper:

 alarm status when a burnout condition is detected 

 Nor 

the burnout detection on the alarm output is disabled, 

 

 

the alarm follows the condition of the input variable 

 Lock 

maintain the same alarm condition as before the burnout detection 

 On  

the alarm condition is activated when a burnout is detected 

 Off  

the alarm condition is deactivated when a burnout is detected 

 

Each alarm output has independent configurations. 

 

 

Содержание D1053S

Страница 1: ...D1053 SIL 2 Analog Signal Converter and Trip Amplifiers ISM0016 13 D1053S INSTRUCTION MANUAL SIL 2 Analog Signal Converter and Trip Amplifiers Din Rail Model D1053S ...

Страница 2: ...ripple 20 mVrms on 250 Ω load Alarm Trip point range within rated limits of input sensor see input for step resolution Delay time 0 to 1000 s 100 ms step Hysteresis 0 to 5 mA on current or 0 to 5 V on voltage see input for step resolution Output voltage free SPST relay contact Contact rating 2 A 250 Vac 500 VA 2 A 250 Vdc 80 W resistive load Performance Ref Conditions 24 V supply 250 Ω load 23 1 C...

Страница 3: ...inear or reverse Two independent trip amplifiers Output for burnout detection High Accuracy µP controlled A D converter Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 Fully programmable operating parameters ATEX IECEx UL C UL FM FM C Russian and Ukrainian Certifications Type Approval Certificate DNV and KR for marine applications High Reliability SMD componen...

Страница 4: ...4 15 16 Io Isc 4 mA Ch1 14 15 16 Po Po 11 mW Ch1 14 15 16 Ii Imax Pi Pi D1053 Terminals Ch1 14 15 16 Ch1 14 15 16 Ch1 14 15 16 D1053 Associated Apparatus Parameters Ci Ci device C cable Li Li device L cable Li Ri device and L cable R cable IIC A B Co Ca 2 135 µF Co Ca 14 995 µF Co Ca 65 995 µF IIB C IIA D IIC A B Lo La 2541 mH Lo La 10167 mH Lo La 20335 mH IIB C IIA D IIC A B Lo Ro 3520 µH Ω Lo Ro...

Страница 5: ... 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1053S 3 4 1 2 RL mA V Supply 24 Vdc Source I Source V Out 1 14 15 16 In 1 I Signal 5 6 7 8 Alarm A Alarm B Set A Set B MODEL D1053S 3 4 1 2 RL mA V Supply 24 Vdc Source I Source V Out 1 14 15 16 In 1 V Signal 5 6 7 8 Alarm A Alarm B Set A Set B For SIL applications alarm contacts ...

Страница 6: ...when connected to live hazardous potential Explosion Hazard to prevent ignition of flammable or combustible atmospheres disconnect power before servicing or unless area is known to be nonhazardous Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury The unit cannot be repaired by the end user and must be returned to the manufacturer or his ...

Страница 7: ...tional installation standards e g EN IEC60079 14 Electrical apparatus for explosive gas atmospheres Part 14 Electrical installations in hazardous areas other than mines BS 5345 Pt4 VDE 165 ANSI ISA RP12 06 01 Installation of Intrinsically Safe System for Hazardous Classified Locations National Electrical Code NEC ANSI NFPA 70 Section 504 and 505 Canadian Electrical Code CEC make sure that conducto...

Страница 8: ... 12 V I dc mA dc input from externally powered transmitter range from 4 to 24 mA 8 Br LO 3 Level Menu Displays the burnout LOW trip point value configuration Press Enter to set the burnout condition trip point value below this value indicate a burnout fault condition set 5 000 to disable press the Select key to the next menu level item or Up key to return to second level If you pressed Enter key y...

Страница 9: ...n Press Enter to set the delay time value press the Select key to the next menu level item or Up key to return to third level If you pressed Enter key you can set the delay value 100 ms step press the Select key to highlight the character you want to change and then the Up and Down keys to select the number confirm the modification with the Enter key The value is settable from 0 to 1000 seconds in...

Отзывы: