8
D1053
- SIL 2 Analog Signal Converter and Trip Amplifiers
G.M. International ISM0016-13
PPC1090 Configuration
The configuration procedure follows a unit specific menu. The display shows the actual menu item, the led shows the channel configured and the push button actuates as “Enter”,
“Select”, “Down” and “Up” key. The “Enter” key is pressed to confirm the menu item, the “Select” key is pressed to scroll the menu item, the “Down” and “Up” keys are pressed to
decrement or increment the numeric value of menu item. The “Up” key is also pressed to decrement the menu level. When the PPC1090 is plugged into the unit, the display shows the
barrier model (first level menu). Then press the “Enter” key to the second level menu and the “Select” key to scroll the menu voice. When the selected menu item is displayed press the
“Enter” key to confirm the choice. Follow this procedure for every voice of the menu. When a numeric menu item is to be changed, press the “Select” key to highlight the character and
then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key. To return to a higher level menu press the “Up” key.
D1053S Menu
1)
D1053S
[1 Level Menu]
Displays Model D1053S single channel analog signal converter and trip amplifiers. Press “Enter” key to second level menu.
2)
CF
[2 Level Menu]
Displays the parameters configuration menu. Press “Enter” key to configure the functional parameters, press the “Select” key to the next
menu level item or “Up” key to return to first level.
3)
In
[2 Level Menu]
Displays the input variable monitoring. Press “Enter” to display the current input value reading, press the “Select” key to the next menu
level item or “Up” key to return to first level.
4)
Out
[2 Level Menu]
Displays the analog output variable monitoring. Press “Enter” to display the current output value reading, press the “Select” key to the
next menu level item or “Up” key to return to first level.
5)
Set A
[3 Level Menu]
Displays the SET A Trip Point Value configuration. Press “Enter” to set the trip point value, press the “Select” key to the next menu level
item or “Up” key to return to second level. If you pressed “Enter” key, you can set the set value; press the “Select” key to highlight the
character you want to change and then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key
6)
Set B
[3 Level Menu]
Displays the SET B Trip Point Value configuration. Press “Enter” to set the trip point value, press the “Select” key to the next menu level
item or “Up” key to return to second level. If you pressed “Enter” key, you can set the set value; press the “Select” key to highlight the
character you want to change and then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key
7)
Input
[3 Level Menu]
Displays the input sensor type configuration. Press “Enter” to set the input sensor, press the “Select” key to the next menu level item or
“Up” key to return to second level. If you pressed “Enter” key, you can choose between 2 different sensor; press “Select” key to change
the input sensor and then the “Enter” key to confirm the choice. The input sensor are:
E dc Volt dc input from externally powered transmitter (range from -2 to +12 V)
I dc
mA dc input from externally powered transmitter (range from -4 to +24 mA)
8)
Br LO
[3 Level Menu]
Displays the burnout LOW trip point value configuration. Press “Enter” to set the burnout condition trip point value (below this value
indicate a burnout fault condition, set –5.000 to disable), press the “Select” key to the next menu level item or “Up” key to return to
second level. If you pressed “Enter” key, you can set the value; press the “Select” key to highlight the character you want to change and
then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key
9)
Br HI
[3 Level Menu]
Displays the burnout HIGH trip point value configuration. Press “Enter” to set the burnout condition trip point value (above this value
indicate a burnout fault condition, set 25.000 to disable), press the “Select” key to the next menu level item or “Up” key to return to
second level. If you pressed “Enter” key, you can set the value; press the “Select” key to highlight the character you want to change and
then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key
10)
Out
[3 Level Menu]
Displays the analog output type configuration. Press “Enter” to set the analog output type and range, press the “Select” key to the next
menu level item or “Up” key to return to second level. If you pressed “Enter” key, you can choose between 6 different output types;
press “Select” key to change the output type and range and then the “Enter” key to confirm the choice. The output types are:
4-20 4 to 20 mA current output
0-20
0 to 20 mA current output
1-5
1 to 5 V voltage output
0-5
0 to 5 V voltage output
2-10 2 to 10 V voltage output
0-10
0 to 10 V voltage output
11)
Dn Sc
[3 Level Menu]
Displays the input low scale configuration. Press “Enter” to set the low scale input value, press the “Select” key to the next menu level
item or “Up” key to return to second level. If you pressed “Enter” key, you can set the low input value; press the “Select” key to highlight
the character you want to change and then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key
12)
Up Sc
[3 Level Menu]
Displays the input high scale configuration. Press “Enter” to set the high scale input value, press the “Select” key to the next menu level
item or “Up” key to return to second level. If you pressed “Enter” key, you can set the high input value; press the “Select” key to highlight
the character you want to change and then the “Up” and “Down” keys to select the number; confirm the modification with the “Enter” key
Menu item description
13)
Burn
[3 Level Menu]
Displays the burnout configuration. Press “Enter” to set the burnout condition, press the “Select” key to the next menu level item or “Up” key to return to second level.
If you pressed “Enter” key, you can choose between 3 different burnout conditions; press “Select” key to change the burnout and then the “Enter” key to confirm the choice.
The condition types are:
none
no burnout detection, the analog output follows the input value
br dn
when in burnout condition, the analog output goes to down scale (0 mA or 0 V)
br up
when in burnout condition, the analog output goes to high scale (22 mA or 11 V)
14)
Alr A / Alr B
[3 Level Menu]
Displays the Alarm A / Alarm B configuration menu. Press “Enter” to set the alarm condition, press the “Select” key to the next menu level item or “Up” key to return to second level.