GMI D1053S Скачать руководство пользователя страница 2

 

D1053 

- SIL 2 Analog Signal Converter and Trip Amplifiers 

G.M. International ISM0016-13 

General Description:

 The single channel DIN Rail Analog Signal Converter and Trip Amplifier D1053S accepts a voltage or current input from externally powered transmitters, 

located in Hazardous Area, and converts, with isolation, the signal to drive a Safe Area load. Output signal can be direct or reverse. Two independent Alarm Trip Amplifiers are also 
provided. Each alarm energizes, or de-energizes, an SPST relay for high, low, low-startup or burnout alarm functions. 
The two alarm relays trip points are settable over the entire input signal range. 

Function:

 1 channel I.S. input from separately powered transmitters, provides 3 port isolation (input/output/supply) and current (source mode) or voltage output signal. 

In addition it provides two SPST relay alarm contacts with adjustable alarm trip point. 

Signalling LEDs:

 Power supply indication (green), alarm A (red), alarm B (red). 

Configurability:

 Totally software configurable, no jumpers or switches, mA or V input/output signal, linear or reverse, alarm trip point, high, low, low-startup or burnout alarm mode, 

NE/ND relay operation, hysteresis, delay time, by GM Pocket Portable Configurator PPC1090, powered by the unit or configured by PC via RS-232 serial line with PPC1092 Adapter 
and SWC1090 Configurator software. 

EMC:

 Fully compliant with CE marking applicable requirements. 

Supply: 

24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits 

 5 Vpp. 

Current consumption @ 24 V: 

65 mA with 20 mA output and relays energized typical. 

Power dissipation:

 1.5 W with 24 V supply, 20 mA output and relays energized typical. 

Max. power consumption: 

at 30 V supply voltage, overload condition, relays energized and PPC1090 connected, 2.1 W. 

Isolation (Test Voltage): 

I.S. In/Outs 1.5 KV; I.S. In/Supply 1.5 KV; Analog Out/Supply 500 V; Analog Out/Alarm Outs 1.5 KV; Alarm Outs/Supply 1.5 KV; Alarm Out/Alarm Out 1.5 KV. 

Input: 

0/4 to 20 mA (-4 to +24 mA reading) separately powered input, voltage drop 

 0.5 V or 0/1 to 5 V or 0/2 to 10 V (-2 to +12 V reading) 1 M

 impedance. 

Integration time: 

100 ms. 

Resolution: 

1 µA on current input, 1 mV on voltage input. 

Visualization: 

1 µA on current input, 1 mV on voltage input. 

Input range: 

-4 to +24 mA on current input, -2 to +12 V on voltage input. 

Burnout: 

enabled or disabled. Analog output can be programmed to detect burnout condition with downscale or highscale forcing. 

Alarms can be programmed to detect burnout condition. 

Burnout range: 

low and high separated trip point value programmable between -5 to +25 mA on current input and -3 to +13 V on voltage input. 

Output: 

0/4 to 20 mA, on max. 600 

 load source mode, current limited at 22 mA or 0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V. 

Resolution: 

2 µA current output or 1 mV voltage output. 

Transfer characteristic: 

linear or reverse. 

Response time: 

 50 ms (10 to 90 % step change). 

Output ripple: 

 20 mVrms on 250 

 load. 

Alarm:

 

Trip point range: 

within rated limits of input sensor (see input for step resolution). 

Delay time: 

0 to 1000 s, 100 ms step. 

Hysteresis: 

0 to 5 mA on current or 0 to 5 V on voltage (see input for step resolution). 

Output: 

voltage free SPST relay contact. 

Contact rating: 

2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load). 

Performance: 

Ref. Conditions 24 V supply, 250 

 load, 23 ± 1 °C ambient temperature. 

Input:

 

Calibration and linearity accuracy:

 

 ± 20 µA on current input or 

 ± 10 mV on voltage input. 

Temperature influence: 

 ± 2 µA, 1 mV of input for a 1 °C change. 

Analog Output:

 

Calibration accuracy: 

 

± 0.1 % of full scale. 

Linearity error: 

 ± 0.05 % of full scale. 

Supply voltage influence: 

 ± 0.05 % of full scale for a min to max supply change. 

Load influence: 

 ± 0.05 % of full scale for a 0 to 100 % load resistance change. 

Temperature influence: 

 ± 0.01 % on zero and span for a 1 °C change. 

Compatibility: 

 

CE mark compliant, conforms to 94/9/EC Atex Directive and to 2004/108/CE EMC Directive. 

Environmental conditions: 

Operating:

 temperature limits -20 to + 60 °C, relative humidity max 95 %. 

Storage:

 temperature limits – 45 to + 80 °C. 

Safety Description:

 

II (1) G [Ex ia Ga] IIC, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I, II 3G Ex nA IIC T4, [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I associated electrical apparatus. 
Uo/Voc = 10.8 V, Io/Isc = 4 mA, Po/Po = 11 mW at terminals 14-15-16. 
Ui/Vmax = 30 V, Ci = 4.5 nF, Li = 0 nH at terminals 14-15-16. 
Um = 250 Vrms, -20 °C 

 Ta 

 60°C. 

Approvals: 

DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26, EN61241-0, EN61241-11, 

IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26, IEC61241-0, IEC61241-11, GM International CRR028 conforms to EN60079-0, EN60079-15, 
UL & C-UL E222308 conforms to UL913 (Div.1), UL 60079-0 (General, All Zones), UL60079-11 (Intrinsic Safety “i” Zones 0 & 1) for UL and 
CSA-C22.2 No.157-92 (Div.1), CSA-E60079-0 (General, All Zones), CSA-E60079-11 (Intrinsic Safety “i” Zones 0 &  1) for C-UL, 
refer to control drawing ISM0138 for complete UL and C-UL safety and installation instructions, 
FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810 and C22.2 No.142, C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15, 
Russia according to GOST 12.2.007.0-75, R 51330.0-99, R 51330.10-99 [Exia] IIC X, Ukraine according to GOST 12.2.007.0,22782.0,22782.5 Exia IIC X, 
EXIDA Report No. GM04/10-27 R003, SIL 2 according to IEC 61508, IEC 61511. Please refer to Functional Safety Manual for SIL applications. 
DNV and KR Type Approval Certificate for marine applications. 

Mounting: 

T35 DIN Rail according to EN50022. 

Weight: 

about 160 g. 

Connection: 

by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm

2

Location:

 Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA 

T4 installation. 

Protection class: 

IP 20. 

Dimensions: 

Width 22.5 mm, Depth 99 mm, Height 114.5 mm. 

 

 

 

Technical Data 

For Safety Related System and SIL2, SIL3 Applications according IEC61508 & IEC61511 Standards refer to “Functional Safety Manual” document number ISM0071 

 

SIL Applications 

 

Characteristics 

Содержание D1053S

Страница 1: ...D1053 SIL 2 Analog Signal Converter and Trip Amplifiers ISM0016 13 D1053S INSTRUCTION MANUAL SIL 2 Analog Signal Converter and Trip Amplifiers Din Rail Model D1053S ...

Страница 2: ...ripple 20 mVrms on 250 Ω load Alarm Trip point range within rated limits of input sensor see input for step resolution Delay time 0 to 1000 s 100 ms step Hysteresis 0 to 5 mA on current or 0 to 5 V on voltage see input for step resolution Output voltage free SPST relay contact Contact rating 2 A 250 Vac 500 VA 2 A 250 Vdc 80 W resistive load Performance Ref Conditions 24 V supply 250 Ω load 23 1 C...

Страница 3: ...inear or reverse Two independent trip amplifiers Output for burnout detection High Accuracy µP controlled A D converter Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 Fully programmable operating parameters ATEX IECEx UL C UL FM FM C Russian and Ukrainian Certifications Type Approval Certificate DNV and KR for marine applications High Reliability SMD componen...

Страница 4: ...4 15 16 Io Isc 4 mA Ch1 14 15 16 Po Po 11 mW Ch1 14 15 16 Ii Imax Pi Pi D1053 Terminals Ch1 14 15 16 Ch1 14 15 16 Ch1 14 15 16 D1053 Associated Apparatus Parameters Ci Ci device C cable Li Li device L cable Li Ri device and L cable R cable IIC A B Co Ca 2 135 µF Co Ca 14 995 µF Co Ca 65 995 µF IIB C IIA D IIC A B Lo La 2541 mH Lo La 10167 mH Lo La 20335 mH IIB C IIA D IIC A B Lo Ro 3520 µH Ω Lo Ro...

Страница 5: ... 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1053S 3 4 1 2 RL mA V Supply 24 Vdc Source I Source V Out 1 14 15 16 In 1 I Signal 5 6 7 8 Alarm A Alarm B Set A Set B MODEL D1053S 3 4 1 2 RL mA V Supply 24 Vdc Source I Source V Out 1 14 15 16 In 1 V Signal 5 6 7 8 Alarm A Alarm B Set A Set B For SIL applications alarm contacts ...

Страница 6: ...when connected to live hazardous potential Explosion Hazard to prevent ignition of flammable or combustible atmospheres disconnect power before servicing or unless area is known to be nonhazardous Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury The unit cannot be repaired by the end user and must be returned to the manufacturer or his ...

Страница 7: ...tional installation standards e g EN IEC60079 14 Electrical apparatus for explosive gas atmospheres Part 14 Electrical installations in hazardous areas other than mines BS 5345 Pt4 VDE 165 ANSI ISA RP12 06 01 Installation of Intrinsically Safe System for Hazardous Classified Locations National Electrical Code NEC ANSI NFPA 70 Section 504 and 505 Canadian Electrical Code CEC make sure that conducto...

Страница 8: ... 12 V I dc mA dc input from externally powered transmitter range from 4 to 24 mA 8 Br LO 3 Level Menu Displays the burnout LOW trip point value configuration Press Enter to set the burnout condition trip point value below this value indicate a burnout fault condition set 5 000 to disable press the Select key to the next menu level item or Up key to return to second level If you pressed Enter key y...

Страница 9: ...n Press Enter to set the delay time value press the Select key to the next menu level item or Up key to return to third level If you pressed Enter key you can set the delay value 100 ms step press the Select key to highlight the character you want to change and then the Up and Down keys to select the number confirm the modification with the Enter key The value is settable from 0 to 1000 seconds in...

Отзывы: